Panasonic U-72MF2U9 Service Manual page 54

3way vrf system
Table of Contents

Advertisement

13. Other Functions
13-2. Setting when at Thermostat OFF
13-2-1. Thermostat OFF in cooling mode
When decreasing the indoor airflow volume at the cooling thermostat OFF or dry thermostat OFF, follow the setting
procedure below.
EEPROM setting in main outdoor unit
CODE: ED
Setting No.
0 (factory preset mode)
1
2
1
3
4
*1 If setting at thermostat ON, the system will return to the normal indoor fan control or solenoid valve kit mode.
*2 Whenever changing thermostat ON and OFF, solenoid valve kit sounds ON and OFF.
*3 When setting at Stop mode, be sure to set the room sensor to the remote control thermostat.
2
EEPROM setting in indoor unit
CODE: 32
Setting No.
0
3
1
*4 Operation when in the intermittent airflow setting
• When in the thermostat OFF, LL airflow and stop mode repeats alternately and the mechanical valve and
solenoid valve kit remain in the forced condition.
• Interval intermittent operation can be changed by EEPROM setting.
4
EEPROM setting in indoor unit
CODE: 44
Setting No.
5
30
60 (factory preset mode)
90
. .
.
210
6
240
13-2-2. Thermostat OFF in heating mode
If setting without hot air in heating thermostat OFF, follow the setting procedure below.
7
EEPROM setting in main outdoor unit
CODE: CD
Setting No.
0 (factory preset mode)
8
1
*1 If setting at thermostat ON, the system will return to the normal indoor fan control or solenoid valve kit mode.
*2 Whenever changing thermostat ON and OFF, solenoid valve kit sounds ON and OFF.
9
Indoor fan mode
w/o force
STOP *3
LL
Interval mode *4
Never use
Indoor unit sensor (factory preset mode)
Remote control sensor
Indoor unit fan operating
time [sec]
30
60
90
. .
.
210
240
Indoor unit
expansion valve
w/o force
20
Indoor unit
expansion valve
w/o force
w/o force
20
20
20
-
CODE: 45
Setting No.
5 (factory preset mode)
10
15
20
25
30
SVK
w/o force
0000
1 - 46
3WAY VRF SYSTEM
Control Functions
SVK
Louver
w/o force
0010
w/o force
0010
w/o force
0010
w/o force
-
-
Indoor unit fan stopped
time [min]
5
10
15
20
25
30

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

U-96mf2u9U-120mf2u9U-144mf2u9

Table of Contents