12. Backup Operation
12. Backup Operation
Alarm list 2 (Backup operation continues as long as the problems are not solved.)
Alarm display
F04
F05
F06
F07
F08
F12
1
F14
F16
F17
2
F23
F24
H05
3
H08
H15
4
H27
P03
P17
A :
When there is one outdoor unit in the system, only compressor that has sensor failure stops.
5
When there are multiple outdoor units in the system, only the outdoor unit which contains the problem
stops but the other outdoor units in the system operate normally.
B :
When there is one outdoor unit in the system, the backup operation does not work.
When there are multiple outdoor units in the system, only the outdoor unit which contains the problem
stops but the other outdoor units in the system operate normally.
6
* Backup operation caused by an alarm listed in "alarm list 2" will finish automatically after 24 hours if the same
alarm does not occur again for 24 hours.
12-1-2. Start of automatic backup operation
If the above alarms occur, the alarm is displayed on the remote controller, etc.
7
Pressing the remote controller button again starts automatic backup mode.
12-1-3. Backup operation information display
If a wired remote controller is present,
8
9
DISCH1 thermistor at the discharge of 1st compressor reading is abnormal
DISCH2 thermistor at the discharge of 2nd compressor reading is abnormal
EXG1 thermistor at the gas side of 1st heat exchanger of the outdoor unit
has failure (EXG1)
EXL1 thermistor at the liquid side of 1st heat exchanger of the outdoor unit
has failure (EXL1)
TO thermistor for outdoor ambient air temperature has failure (TO)
SCT thermistor at the suction refrigerant of compressors has failure (SCT)
SCG thermistor at the outlet of subcooling heat exchanger in outdoor unit
has failure (SCG)
High pressure sensor of the outdoor unit has failure (HPS)
Low pressure sensor of the outdoor unit has failure (LPS)
EXG2 thermistor at the gas side of 2nd heat exchanger of the outdoor unit
has failure (EXG2)
EXL2 thermistor at the liquid side of 2nd heat exchanger of the outdoor unit
has failure (EXL2)
DISCH1 thermistor at the discharge of 1st compressor is disconnected,
shorted or misplaced (DISCH1)
OIL1 thermistor for the oil of 1st compressor has failure (OIL1)
DISCH2 thermistor at the discharge of 2nd compressor is disconnected,
shorted or misplaced (DISCH2)
OIL2 thermistor for the oil of 2nd compressor has failure (OIL2)
1st compressor discharge temperature too high
2nd compressor discharge temperature too high
display blinks during operation.
1 - 42
3WAY SYSTEM
3WAY VRF SYSTEM
Control Functions
Control Functions
B
B
B
B
B
B
B
B
B
B
B
B
B
B
B
B
B

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

U-96mf2u9U-120mf2u9U-144mf2u9

Table of Contents