14. Detailed Settings in EEPROM of Outdoor Unit

Never use the DN code unlisted in the following table.
DN
04
Operation for using snowfall sensor
05
Outdoor fan silent mode
0C Indoor unit drain pump forced operation
Measures against smell when indoor
0D
unit cooling thermostat OFF
1A Demand 1 current (%)
1B
Demand 2 current (%)
1E
Demand remote controller display
23
E06 ignore function
Dew condensation prevention control of
2A
indoor unit
2B
DP operation time for slime measures
3E
PSccutgt delay-start setting
Indoor unit fan's intermittent operation
44
and operating time when in cooling
thermostat OFF
Indoor unit fan's intermittent operation
45
and stopped time when in cooling
thermostat OFF
49
Automatic backup mode setting
81
Outdoor unit capacity
8F
High static pressure setting
The minimum operating time 1 until
A3
defrosting
Validity/invalidity of capacity control
A7
when cooling operation
Item
0=No sensor & control (P)
1=Sensor & control
2=No Sensor & no control
3=Sensor & no control
0=Invalid (P)
1=Silent mode 1
2=Silent mode 2 ,,,,, 12=Silent mode 12
0=Invalid
1=stop for 2 hours and drive for 20 min. constantly
2=stop for 20 min. and drive for 20 min. constantly
3=Drive constantly
4-6=delay drive when thermostat OFF
7=delay drive when thermostat OFF (P)
0=Invalid (P)
1=Measures against smell
0=0% ,,,,,40=40% ,,,,,45=45% ,,,,,100=100% (P) ,,,,,140=140%
-1=No control
0=0% ,,,,,40=40% ,,,,,70=70% (P) ,,,,,100=100% ,,,,,140=140%
-1=No control
0=No display
1=When demand control active, "demand - actived" displayed (P)
2=When forced thermostat OFF with demand control active,
"demand - actived" displayed
-1=invalid (P),,,,, 0=0,,,,, 1=1,,,,, 13=13
14-52=Never use
0=Invalid (P)
1=30 min, 2=40 min, 3=50 min, 4=60 min
20=20 min, 30=30 min (P), 40=40 min
50=50 min, 60=60 min
0=8 sec delay-start (P)
1=(system address ×1×8) sec delay-start
2=(system address ×2×8) sec delay-start
3=(system address ×3×8) sec delay-start
30=30 sec , 60=60 sec (P) ,,,,, 240=240 sec
5=5 min (P) , 10=10 min , 15=15 min , 20=20 min , 25=25 min
30=30 min
0=Display (P) 1=non-displayed
0=Invalid , 1=22 , 2=25 , 3=28 , 4=32 , 5=36 , 6=40 , 7=45 ,
8=50 , 9=56 , 10=63 , 11=71 , 12=80 , 13=90 , 14=100 ,
15=112 , 16=125 , 17=140 , 18=160 , 19=180 , 20=210 ,
21=224 , 22=250 , 23=280 , 24=335 , 25=355 , 26=420 ,
27=450 , 28=500 , 29=560 , 30=600 , 31=630 , 32=670 ,
33=710 , 34=800 , 35=840
0=Invalid (P)
1=High static pressure mode
2-6=Never use
20=20min, 21=21min ,,,,, 40=40min (P)
41 - 90=Never use
0=Invalid (P), 1=Valid
Setting No.
1 - 47
3WAY VRF SYSTEM
Control Functions
(P) : Factory preset mode
1
2
3
4
5
6
7
8
9