Panasonic U-72MF2U9 Technical Data Manual
Panasonic U-72MF2U9 Technical Data Manual

Panasonic U-72MF2U9 Technical Data Manual

3way vrf system
Hide thumbs Also See for U-72MF2U9:
Table of Contents

Advertisement

U-72MF2U9
U-96MF2U9
U-120MF2U9
U-144MF2U9
Model No.
Outdoor Unit
Type
Outdoor Unit Type
MF2 3WAY VRF System
To be connecting Indoor Units
Indoor Units
Type
Indoor Unit Type
U2
4-Way Cassette 36"x36"
4-Way Cassette 24"x24"
Y2
D1
S-07MD1U6
1-Way Cassette
Concealed Duct
F2
S-07MF2U6
-Medium Static
Concealed Duct
M2
S-07MM2U6
-Low Static
Concealed Duct
E1
-High Static
T2
Ceiling
K2
S-07MK2U6
Wall Mounted
P1
S-07MP1U6
Floor Standing
S-07MR1U6
R1
Concealed Floor Standing
85464869283000
3WAY VRF System
72
U-72MF2U9
U-96MF2U9
7
9
12
S-12MY2U6
S-09MD1U6
S-12MD1U6
S-09MF2U6
S-12MF2U6
S-09MM2U6
S-12MM2U6
S-12MT2U6
S-09MK2U6
S-12MK2U6
S-09MP1U6
S-12MP1U6
S-09MR1U6
S-12MR1U6
Nominal Capacity
96
120
U-120MF2U9
Nominal Capacity
15
18
24
S-24MU2U6
S-18MY2U6
S-15MF2U6
S-18MF2U6
S-24MF2U6
S-15MM2U6
S-18MM2U6
S-18MT2U6
S-24MT2U6
S-18MK2U6
S-24MK2U6
S-15MP1U6
S-18MP1U6
S-24MK1U6
S-15MR1U6
S-18MR1U6
S-24MR1U6
This air conditioner uses the refrigerant R410A.
Order No. SBPAC1509016CE
144
U-144MF2U9
36
48
S-36MU2U6
S-36MF2U6
S-48MF2U6 S-54MF2U6
S-36ME1U6
S-48ME1U6
TD831183-00
REFERENCE NO.
54

Advertisement

Table of Contents
loading

Summary of Contents for Panasonic U-72MF2U9

  • Page 1 Order No. SBPAC1509016CE 3WAY VRF System U-72MF2U9 U-96MF2U9 U-120MF2U9 U-144MF2U9 Model No. Outdoor Unit Nominal Capacity Type Outdoor Unit Type MF2 3WAY VRF System U-72MF2U9 U-96MF2U9 U-120MF2U9 U-144MF2U9 To be connecting Indoor Units Indoor Units Nominal Capacity Type Indoor Unit Type 4-Way Cassette 36"x36"...
  • Page 2: Special Precautions

    IMPORTANT! When Transporting Please Read Before Starting Be careful when picking up and moving the indoor and outdoor units. Get a partner to help, and bend your knees This air conditioning system meets strict safety and when lifting to reduce strain on your back. Sharp edges or operating standards.
  • Page 3: Check Of Density Limit

    • Do not leak refrigerant while piping work for an installation or re-installation, and while repairing CAUTION refrigeration parts. Handle liquid refrigerant carefully as it may cause • Do not touch the air inlet or the sharp frostbite. aluminum fins of the outdoor unit. You When Servicing may get injured.
  • Page 4: Precautions For Installation Using New Refrigerant

    Precautions for Installation Using New Refrigerant 1. Care regarding tubing 1-1. Process tubing Material: Use clean, dry, free of oil, refrigeration grade, seamless, phosphorous deoxidized copper tube rated for R410A only. Wall thickness shall comply with the applicable legislation. The minimal wall thickness must be in accordance with the table below.
  • Page 5 3-2. Use R410A exclusive cylinder only. Valve Single-outlet valve (with siphon tube) Liquid refrigerant should be recharged with the cylinder standing on end as shown. Liquid New refrigerant R410A cannot be used for earlier models 1. Compressor specifications are different. If recharging a R22 or R407C compressor with R410A, durability will significantly decrease since some of the materials used for compressor parts are...
  • Page 6: Table Of Contents

    Contents Section 1: OUTLINE OF 3WAY VRF SYSTEM ..............Line-up ......................Features of 3WAY VRF SYSTEM ..............Section 2: DESIGN OF 3WAY VRF SYSTEM ................ Model Selection and Capacity Calculator ............System Design ..................... 2-17 ELECTRICAL WIRING ................. 2-21 SELECTING THE INSTALLATION SITE ............2-28 HOW TO INSTALL THE OUTDOOR UNIT ...........
  • Page 7 Section 6: ELECTRICAL DATA ....................Outdoor Unit ....................Indoor Unit * Refer to the VRF SYSTEMS INDOOR UNIT TECHNICAL DATA (TD831178) Section 7: PCB AND FUNCTIONS ..................Outdoor Unit Control PCB ................Indoor Unit Control PCB Switches and Functions * Refer to the VRF SYSTEMS INDOOR UNIT TECHNICAL DATA (TD831178) Section 8: CAPACITY TABLE ....................
  • Page 8 – MEMO –...
  • Page 9: Section 1: Outline Of 3Way Vrf System

    Outline of 3WAY VRF SYSTEM Outline of 3WAY VRF SYSTEM Contents Contents 1. OUTLINE OF 3WAY VRF SYSTEM Line-up ..........................2. Features of 3WAY VRF SYSTEM ..................1 - 1...
  • Page 10: Line-Up

    Outline of 3WAY VRF SYSTEM Outline of 3WAY VRF SYSTEM 1. Line-up 1. Line-up Indoor units 4-Way Cassette 36” X 36” (Type U2) S-24MU2U6 S-36MU2U6 4-Way Cassette 24” X 24” (Type Y2) S-12MY2U6 S-18MY2U6 1-Way Cassette (Type D1) S-07MD1U6 S-09MD1U6 S-12MD1U6 Concealed Duct -Medium Static (Type F2)
  • Page 11 Outdoor units Type Capacity: BTU/h (kW) 72,000 (21.1) Cooling / Heating / 81,000 (23.7) U-72MF2U9 *1. The tubing is routed out from the bottom. *2. The tubing is routed out from the front. Outdoor Unit 45-9/32(1,150) (Installation hole pitch) Top view...
  • Page 12 Outline of 3WAY VRF SYSTEM Outline of 3WAY VRF SYSTEM 1. Line-up 1. Line-up Type Capacity: BTU/h (kW) 120,000 (35.2) Cooling / Heating / 135,000 (39.6) U-120MF2U9 *1. The tubing is routed out from the bottom. *2. The tubing is routed out from the front. Outdoor Unit 45-9/32(1,150) (Installation hole pitch)
  • Page 13: Features Of 3Way Vrf System

    Outline of 3WAY VRF SYSTEM Outline of 3WAY VRF SYSTEM 2. Features of 3WAY VRF SYSTEM 2. Features of 3WAY VRF SYSTEM 2-1. Outline of 3WAY VRF SYSTEM System example Since all pipings are concentrated into one pipe shaft, you CONCENTRATION can minimize piping space and construc-...
  • Page 14 2. Features of 3WAY VRF SYSTEM 2. Features of 3WAY VRF SYSTEM Dimensions *1. The tubing is routed 6, 8, 10, 12 Ton out from the bottom. 6-Ton U-72MF2U9 8-Ton U-96MF2U9 *2. The tubing is routed out from the front. 10-Ton U-120MF2U9 12-Ton U-144MF2U9...
  • Page 15 Outline of 3WAY VRF SYSTEM Outline of 3WAY VRF SYSTEM 2. Features of 3WAY VRF SYSTEM 2. Features of 3WAY VRF SYSTEM Capacity control The compressor combination (DC inverter compressor + DC inverter compressor) allows smooth capacity control from 0.6-Ton to 30-Ton. Realization of smooth capacity control from 0.6-Ton to 30-Ton Capacity control is possible smoothly with a DC inverter compressor.
  • Page 16 – MEMO – 1 - 8...
  • Page 17: Section 2: Design Of 3Way Vrf System

    Design of 3WAY VRF SYSTEM Design of 3WAY VRF SYSTEM Contents Contents 2. DESIGN OF 3WAY VRF SYSTEM 1. Model Selection and Capacity Calculator................1-1. Operating Range ......................1-2. Procedure for Selecting Models and Calculating Capacity..........1-3. Tubing Length........................ 1-4. Tubing Size ........................1-5.
  • Page 18 Design of 3WAY VRF SYSTEM Design of 3WAY VRF SYSTEM Contents Contents 8. Optional Parts ........................2-45 8-1. Installing Distribution Joint ..................... 2-45 8-2. Optional Distribution Joint Kits ..................2-46 8-3. Optional Solenoid Valve kit (CZ-P56HR2U / CZ-P160HR2U)........2-48 8-4. Solenoid Valve kit (CZ-P456HR2U / CZ-P656HR2U / CZ-P856HR2U / CZ-P4160HR2U)..2-53 2 - 2...
  • Page 19: Model Selection And Capacity Calculator

    Design of 3WAY VRF SYSTEM Design of 3WAY VRF SYSTEM 1. Model Selection and Capacity Calculator 1. Model Selecting and Capacity Calculator 1-1. Operating Range Heating Cooling Operating Operating range range Indoor air intake temp. F (DB) Indoor air intake temp. F (WB) Use this air conditioner under the following temperature range.
  • Page 20 Design of 3WAY VRF SYSTEM 1. Model Selection and Capacity Calculator 1-2. Procedure for Selecting Models and Calculating Capacity Model Selection Procedure Select the model and calculate the capacity for each refrigerant system according to the procedure shown below. Calculation of the indoor air-conditioning load Calculate the maximum air-conditioning load for each room or zone.
  • Page 21: Tubing Length

    Design of 3WAY VRF SYSTEM Design of 3WAY VRF SYSTEM 1. Model Selecting and Capacity Calculator 1. Model Selection and Capacity Calculator 1-3. Tubing Length Select the installation location so that the length and size of refrigerant tubing are within the allowable range shown in the figure below. Main tubing length (maximum tubing size) LM = LA + LB …...
  • Page 22 1. Model Selecting and Capacity Calculator Design of 3WAY VRF SYSTEM 1. Model Selection and Capacity Calculator 5: If the tubing length marked “L” (L2 - L4) exceeds 131 ft. (40m), increase the tubing size at the portion after the 1st distribution joint by 1 rank for the liquid tube, suction tube and discharge tube.
  • Page 23 Design of 3WAY VRF SYSTEM Design of 3WAY VRF SYSTEM 1. Model Selection and Capacity Calculator 1. Model Selecting and Capacity Calculator Example 1 Outdoor L4: 99ft. (30m) unit 1 Portion increased by LF: 49ft. (15m) one size is overlapped L2': 238ft.
  • Page 24 Design of 3WAY VRF SYSTEM Design of 3WAY VRF SYSTEM 1. Model Selecting and Capacity Calculator 1. Model Selection and Capacity Calculator 1-4. Tubing Size Table 2 Main Tubing Size (LA) Between 1st distribution joint for outdoor unit and 1st distribution joint (for indoor unit) Unit: in.
  • Page 25 Design of 3WAY VRF SYSTEM 1. Model Selection and Capacity Calculator Table 5 Refrigerant Charge Amount at Shipment (for outdoor unit) BTU/h (kW) 72,000 (21.1) 96,000 (28.1) 120,000 (35.2) 144,000 (42.2) Initial amount oz (g) 293 (8,300) 293 (8,300) 353 (10,000) 416 (11,800) Table 6 Indoor Unit Tubing Connection Size ( 1 –...
  • Page 26 Design of 3WAY VRF SYSTEM Design of 3WAY VRF SYSTEM 1. Model Selecting and Capacity Calculator 1. Model Selection and Capacity Calculator Table 10 Necessary Amount of Additional Refrigerant Charge Per Outdoor Unit Further charge a certain amount listed below in addition to the amount of refrigerant charge. Combination number of outdoor unit Additional amount oz (g)
  • Page 27 Design of 3WAY VRF SYSTEM 1. Model Selection and Capacity Calculator 1-8. Installation Standards Relationship between A/C units and refrigerant tubing 4-tube layout 3-tube layout 2-tube layout Solenoid Outdoor unit Outdoor unit Outdoor unit valve kit Suction tube Suction tube Gas tube Discharge tube Discharge tube...
  • Page 28 Design of 2WAY VRF SYSTEM Design of 3WAY VRF SYSTEM 1. Model Selecting and Capacity Calculator 1. Model Selection and Capacity Calculator 1-10. Calculation of Actual Capacity of Indoor Unit Calculating the actual capacity of each indoor unit Because the capacity of a multi air-conditioner changes according to the temperature conditions, tubing length, elevation difference and other factors, select the correct model after taking into account the various correction values.
  • Page 29 Design of 2WAY VRF SYSTEM Design of 3WAY VRF SYSTEM 1. Model Selecting and Capacity Calculator 1. Model Selection and Capacity Calculator 2. Indoor unit capacity correction coefficient Indoor unit capacity correction (BTU/h) = (G) × ( I ) × (D) Indoor unit capacity correction ≤...
  • Page 30 Design of 2WAY VRF SYSTEM Design of 3WAY VRF SYSTEM 1. Model Selecting and Capacity Calculator 1. Model Selection and Capacity Calculator 3. Graph of capacity correction coeffi cients Graph of outdoor unit capacity characteristics (1 – (2)) Outdoor unit cooling capacity characteristics Outdoor unit heating capacity characteristics 14 23 32 41 50 59 68 77 86 95 104 113 122 -13 2...
  • Page 31 Design of 2WAY VRF SYSTEM Design of 3WAY VRF SYSTEM 1. Model Selecting and Capacity Calculator 1. Model Selection and Capacity Calculator Graph of indoor unit capacity characteristics (2 – (2)) Indoor unit cooling capacity characteristics Indoor unit heating capacity characteristics indicates the rating point.
  • Page 32 Design of 2WAY VRF SYSTEM Design of 3WAY VRF SYSTEM 1. Model Selecting and Capacity Calculator 1. Model Selection and Capacity Calculator The capacity loss that is caused by the tubing length can be reduced by increasing the sizes of the discharge tubes and suction tubes.
  • Page 33: System Design

    Design of 3WAY VRF SYSTEM 2. System Design 2-1. System Example Below are the tables created using the "PAC System Diagram Software". Outdoor unit 1 60ft. 30ft. 30ft. 50ft. Elevation 15ft. 15ft. 15ft. 30ft. difference : 15ft. 15ft. 15ft. 30ft. Indoor Indoor Indoor...
  • Page 34 Design of 3WAY VRF SYSTEM 2. System Design 2-2. Example of Tubing Size Selection and Refrigerant Charge Amount Additional refrigerant charging Based on the values in Tables 2, 3, 4, 6, 9 and 10, use the liquid tubing size and length, and calculate the amount of additional refrigerant charge using the formula below.
  • Page 35 Design of 3WAY VRF SYSTEM 2. System Design Example: Example of each tubing length Main tubing Distribution joint tubing Outdoor unit LA = 131 ft. (40m) Outdoor side Indoor side LB = 16 ft. (4.9m) A = 7 ft. (2.1m) 1 = 98 ft.
  • Page 36 Design of 3WAY VRF SYSTEM 2. System Design 2-3. Installing Distribution Joint Pay special attention to any location, such as a basement, etc., where leaking refrigerant can CAUTION accumulate, since refrigerant gas is heavier than air. (1) Refer to “HOW TO ATTACH DISTRIBUTION JOINT” enclosed with the optional distribution joint kit (CZ-P900PH1U, CZ-P224BH1U, CZ-P680BH1U, CZ-P1350BH1U).
  • Page 37: Electrical Wiring

    3-2. Recommended Wire Length and Wire Diameter for Power Supply System Outdoor unit Indoor unit Time delay fuse or Time delay fuse or Type Type circuit capacity circuit capacity U-72MF2U9 45 A 15 A U-96MF2U9 60 A D1, U2, Y2, F2, M2, T2, P1, R1 15 A U-120MF2U9 60 A...
  • Page 38: Wiring System Diagram

    Design of 3WAY VRF SYSTEM 3. ELECTRICAL WIRING 3-3. Wiring System Diagram Indoor unit (No. 1) Power supply Outdoor unit 208 / 230V, 60Hz, 1-PH INV unit Power supply Ground 208 / 230V, 60Hz, 3-PH Remote Controller Ground Indoor unit (No. 2) Inter-outdoor unit control wiring Power supply 208 / 230V, 60Hz, 1-PH...
  • Page 39 Design of 3WAY VRF SYSTEM Design of 3WAY VRF SYSTEM 3. ELECTRICAL WIRING 3. ELECTRICAL WIRING CAUTION (1) When linking outdoor units in a network, see the section “ATTENTION!”. (2) Do not install the inter-unit control wiring in a way that forms a loop. Outdoor unit Outdoor unit Outdoor unit...
  • Page 40 3. Electrical Wiring 3. ELECTRICAL WIRING Design of 3WAY VRF SYSTEM 3. ELECTRICAL WIRING 3-4. Connecting Multiple Indoor Units to a Single Solenoid Valve Kit It is possible to connect multiple indoor units to one solenoid valve kit. The indoor units can be controlled individually or be operated as a group. It is possible to adopt multiple units with a common use of the solenoid valve kit per piece of refrigerant.
  • Page 41 Design of 3WAY SYSTEM Design of 3WAY VRF SYSTEM 3. ELECTRICAL WIRING 3. Electrical Wiring Necessity of setting changes by combination of each method Type of combination: Necessity of setting Method 1 only: Setting is unnecessary. Method 2 included: Setting up in common use of a solenoid valve kit from “Remote Control” is necessary. * * Method 2 only is set.
  • Page 42 Design of 3WAY VRF SYSTEM 3. ELECTRICAL WIRING Loose wiring may cause the terminal to overheat or result in unit malfunction. WARNING A fire hazard may also exist. Therefore, ensure that all wiring is tightly connected. When connecting each power wire to the terminal, follow the instructions on “How to connect wiring to the terminal” and fasten the wire securely with the fixing screw of the terminal board.
  • Page 43 Design of 3WAY VRF SYSTEM Design of 3WAY VRF SYSTEM 3. ELECTRICAL WIRING 3. ELECTRICAL WIRING Wiring sample Electronic component box Inter-unit control wiring (U1, U2) 2P terminal board * Inter-outdoor unit control wiring (1, 2) 2P terminal board * Terminal board for power supply 3P terminal board * Earth terminal *...
  • Page 44: Selecting The Installation Site

    Design of 3WAY VRF SYSTEM 4. SELECTING THE INSTALLATION SITE 4-1. Outdoor Unit Leave space open above the CAUTION unit. AVOID: Construct louvers or other heat sources, exhaust fans, etc. openings in the wall, if damp, humid or uneven locations necessary, to ensure adequate indoors (no-ventilation location) ventilation.
  • Page 45 Design of 3WAY VRF SYSTEM 4. SELECTING THE INSTALLATION SITE 4-2. Shield for Horizontal Exhaust Discharge 4-3. Installing the Outdoor Unit in Heavy Snow Areas It is necessary to install an air-discharge chamber (field supply) to direct exhaust from the fan horizontally if it is difficult In locations where wind-blown snow can be a problem, to provide a minimum space of 7 ft.
  • Page 46 Design of 3WAY VRF SYSTEM 4. SELECTING THE INSTALLATION SITE 4-5. Dimensions of Wind Ducting Reference diagram for air-discharge chamber (field supply) Note: Can be installed so that the air direction is to the front or rear direction. unit: in. (mm) Air direction: Front direction Top view 46-11/16...
  • Page 47 Design of 3WAY VRF SYSTEM 4. SELECTING THE INSTALLATION SITE Reference diagram for air-discharge chamber (field supply) (continued) Combination of units For various types of combination. unit: in. (mm) Top view (Before installing air-discharge chamber) Top view 39-31/64 (1003) 3/64 (1) 5/64 (2) Front view Right side view...
  • Page 48 Design of 3WAY VRF SYSTEM 4. SELECTING THE INSTALLATION SITE 4-6. Dimensions of Snow Ducting Reference diagram for snow-proof ducting (field supply) Note: Can be installed so that the air direction is to the front or rear direction. unit: in. (mm) Air direction: Front direction 42-1/4 (1073)
  • Page 49 Design of 3WAY VRF SYSTEM 4. SELECTING THE INSTALLATION SITE Reference diagram for snow-proof ducting (field supply) (continued) Combination of units For various types of combination. unit: in. (mm) 8-17/64 (210) 8-17/64 (210) 7-3/32 (180) 7-3/32 (180) Top view (Before installing snow-proof ducting) Top view 39-31/64 (1003)
  • Page 50: How To Install The Outdoor Unit

    Design of 3WAY VRF SYSTEM 5. HOW TO INSTALL THE OUTDOOR UNIT 5-1. Transporting When transporting the unit, have it delivered as close to the installation site as possible without unpacking. Use a hook for suspending the unit. CAUTION When hoisting the outdoor unit, pass ropes or straps under the bottom plate as shown in the figure at right.
  • Page 51 Design of 3WAY VRF SYSTEM 5. HOW TO INSTALL THE OUTDOOR UNIT Unit: in. (mm) Air intake 19/32 (15) 45-9/32 (1150) (Installation hole pitch) 46-29/64 (1180) A : 37-61/64 (964) [Installation hole pitch] * The tubing is routed out from the front. B : 28-47/64 (730) [Installation hole pitch] * The tubing is routed out from the bottom.
  • Page 52 Design of 3WAY VRF SYSTEM Design of 3WAY VRF SYSTEM 5. HOW TO INSTALL THE OUTDOOR UNIT 5. HOW TO INSTALL THE OUTDOOR UNIT 5-4. Prepare the Tubing Material: Use clean, dry, free of oil, refrigeration grade, seamless, phosphorous deoxidized copper tube rated for R410A only. Wall thickness shall comply with the applicable legislation.
  • Page 53 Design of 3WAY VRF SYSTEM 5. HOW TO INSTALL THE OUTDOOR UNIT Tubing cover Refrigerant tube port Use caulking, putty, or a similar material to fill any gaps at the refrigerant tube port ) in order to prevent rainwater, dust or foreign substances from entering the unit. * Perform this work even if the tubing is routed out in a downward direction.
  • Page 54 Design of 3WAY VRF SYSTEM 5. HOW TO INSTALL THE OUTDOOR UNIT Precautions for brazing Be sure to replace the air inside the tube with nitrogen to prevent oxide film from forming during the brazing process. Be sure to use a damp cloth or other means to cool the valve unit during brazing.
  • Page 55: How To Process Tubing

    Design of 3WAY VRF SYSTEM 6. HOW TO PROCESS TUBING The liquid tubing side is connected by a flare nut, and the gas (3) Remove the flare nut from the unit and be sure to mount it tubing side is connected by brazing. on the copper tube.
  • Page 56 Design of 3WAY VRF SYSTEM 6. HOW TO PROCESS TUBING Caution Before Connecting Tubes Tightly (1) Apply a sealing cap or water-proof tape to prevent dust or water from entering the tubes before they are used. (2) Be sure to apply refrigerant lubricant to the matching surfaces of the flare and union before connecting them together.
  • Page 57 Design of 3WAY VRF SYSTEM 6. HOW TO PROCESS TUBING 6-3. Insulating the Refrigerant Tubing 6-4. Taping the Tubes (1) At this time, the refrigerant tubes (and electrical wiring Tubing Insulation if local codes permit) should be taped together with armoring tape in 1 bundle.
  • Page 58: Air Purging

    Design of 3WAY VRF SYSTEM 7. AIR PURGING 7. AIR PURGING Vacuum pump Manifold gauge Air and moisture in the refrigerant system may have Outlet undesirable effects as indicated below. Inlet pressure in the system rises operating current rises cooling (or heating) efficiency drops moisture in the refrigerant circuit may freeze and block capillary tubing water may lead to corrosion of parts in the refrigerant...
  • Page 59 Design of 3WAY VRF SYSTEM 7. AIR PURGING (3) Do a leak test of all joints of the tubing (both indoor and outdoor) and all service valves. Bubbles indicate Manifold valve a leak. Wipe off the soap with a clean cloth after a leak test.
  • Page 60 Design of 3WAY VRF SYSTEM 7. AIR PURGING (2) When the desired vacuum is reached, close the “Lo” knob of the manifold valve and turn off the vacuum Manifold valve pump. Please confirm that the gauge pressure is under –14.7 psig (–0.1 MPa) {–755 mmHg, 5 Torr} Pressure after 4 to 5 minutes of vacuum pump operation.
  • Page 61: Optional Parts

    Design of 3WAY VRF SYSTEM 8. Optional Parts 8-1. Installing Distribution Joint Pay special attention to any location, such as a basement, etc., where leaking refrigerant can CAUTION accumulate, since refrigerant gas is heavier than air. (1) Refer to “HOW TO ATTACH DISTRIBUTION JOINT” enclosed with the optional distribution joint kit (CZ-P900PH1U, CZ-P224BH1U, CZ-P680BH1U, CZ-P1350BH1U).
  • Page 62: Optional Distribution Joint Kits

    Design of 3WAY VRF SYSTEM 8. Optional Parts 8-2. Optional Distribution Joint Kits Refer to the installation instructions packaged with the distribution joint kit for the installation procedure. Table 15 Model name Cooling capacity after distribution Remarks 1. CZ-P900PH1U 307,100 BTU/h (90.0kW) or less For outdoor unit * In case the total capacity of indoor units 2.
  • Page 63 Design of 3WAY VRF SYSTEM 8. Optional Parts Table 17 Dimensions for connections of each part Unit: in. (mm) Position ø1-1/2" ø1-1/4" ø1-1/8" ø1" ø7/8" ø3/4" ø5/8" ø1/2" ø3/8" – Dimension (ø38.1) (ø31.75) (ø28.58) (ø25.4) (ø22.22) (ø19.05) (ø15.88) (ø12.7) (ø9.52) –...
  • Page 64: Optional Solenoid Valve Kit (Cz-P56Hr2U / Cz-P160Hr2U)

    Design of 3WAY VRF SYSTEM 8. Optional Parts 8-3. Optional Solenoid Valve kit (CZ-P56HR2U / CZ-P160HR2U) 8-3-1. Accessories Part Name Figure Q'ty Remarks Washer For suspension bolts Suspension hook Used to suspend the Solenoid Valve Kit Tapping screw For suspension hook ( L=15/32"...
  • Page 65 Design of 3WAY VRF SYSTEM 8. Optional Parts Be sure to secure the solenoid valve kit to the structure and the hanging bolts, etc. using the top or side holes of the hanging hooks. Do not place the solenoid valve kit directly on the ceiling surface. When installing the solenoid valve kit, remember to Rear side install it with the top surface facing upward.
  • Page 66 Design of 3WAY VRF SYSTEM 8. Optional Parts How to use the fittings Suspension bolt (3/8" or M10) (field supplied) Nut (field supplied) (3/8" or M10) Washer (supplied) Suspension hook ● Tapping screw (L=15/32"(12mm) : supplied ) ● Never use a long screw other than the accessory screw.
  • Page 67 Design of 3WAY VRF SYSTEM 8. Optional Parts 8-3-5. ELECTRICAL WIRING 8-3-5-1. General Precautions on Wiring Before wiring, confirm the rated voltage of the unit as shown on its nameplate, then carry out the wiring closely following the wiring diagram. Each wiring connection must be done in accordance with the wiring system diagram.
  • Page 68 Design of 3WAY VRF SYSTEM 8. Optional Parts 8-3-5-4. Procedure Connect the power supply wire to the solenoid valve kit, using Solenoid valve relay kit Ⅰ the Class wire.(Fig. 3) * Wiring fixed Connect the solenoid valve kit to the solenoid valve relay kit, with clamper Ⅱ...
  • Page 69: Solenoid Valve Kit (Cz-P456Hr2U / Cz-P656Hr2U / Cz-P856Hr2U / Cz-P4160Hr2U)

    Design of 3WAY VRF SYSTEM 8. Optional Parts 8-4. Solenoid Valve kit (CZ-P456HR2U / CZ-P656HR2U / CZ-P856HR2U / CZ-P4160HR2U) 8-4-1. Accessories Q'ty Part Name Figure Remarks Type Type Type Type 4160 Washer For suspension bolts Tapping screw For Solenoid Valve Relay Kit ( L=5/16"...
  • Page 70 Design of 3WAY VRF SYSTEM 8. Optional Parts Be sure to secure the solenoid valve kit to the structure and the suspension bolts. Do not place the solenoid valve kit directly on the ceiling surface. When installing the solenoid valve kit, remember to install it with the top surface facing upward. (See the figure shown in the subsection "How to use the fittings"...
  • Page 71 Design of 3WAY VRF SYSTEM 8. Optional Parts 8-4-3. Valve Dimensions and Hanging Method Indoor Unit Capacity Solenoid Valve Kit No. of port per 1 port There are 4 types of solenoid valve kits: type 456, 656, 856 and type 4160. The corresponding indoor CZ-P456HR2U unit model capacities are shown in the table at right.
  • Page 72 Design of 3WAY VRF SYSTEM 8. Optional Parts Type 456 Type 656 Type 856 Type 4160 K (SUCTION) Ø3/4 (Ø19.05) Ø1 (Ø25.4) Ø1-1/8 (Ø28.58) Ø1-1/8 (Ø28.58) L (DISCHARGE) Ø5/8 (Ø15.88) Ø3/4 (Ø19.05) Ø7/8 (Ø22.22) Ø1 (Ø25.4) M (LIQUID) Ø3/8 (Ø9.52) Ø1/2 (Ø12.7) Ø1/2 (Ø12.7) Ø5/8 (Ø15.88)
  • Page 73 Design of 3WAY VRF SYSTEM 8. Optional Parts 8-4-4. Wiring, Tubing and Heat Insulation 8-4-4-1. Refrigerant tubing Remove the protection tubes before connection. Cool the tubes with damp cloth or other means Liquid tube Remove the protection tubes when connecting to the left side. Gas tube Cool the tubes with damp cloth or other means when brazing the joint with a torch.
  • Page 74 Design of 3WAY VRF SYSTEM 8. Optional Parts 8-4-5. ELECTRICAL WIRING 8-4-5-1. General Precautions on Wiring Before wiring, confirm the rated voltage of the unit as shown on its nameplate, then carry out the wiring closely following the wiring diagram. Each wiring connection must be done in accordance with the wiring system diagram.
  • Page 75 Design of 3WAY VRF SYSTEM 8. Optional Parts 8-4-5-3. Wiring System Diagram Class Ⅰ Terminal board field supplied Power supply Indoor unit 1 Solenoid valve relay kit 1 Solenoid valve kit 208/230V Electrical box 60Hz 1PH Control board Control board (CR-SV80A-N) Class Ⅱ...
  • Page 76 Design of 3WAY VRF SYSTEM 8. Optional Parts 8-4-5-4. Procedure Connect the power supply wire to the solenoid valve kit, using Solenoid valve relay kit Ⅰ the Class wire. (Fig. 8) Connect the solenoid valve kit to the solenoid valve relay kit, Ⅱ...
  • Page 77 Design of 3WAY VRF SYSTEM 8. Optional Parts 8-4-6. Tubing system design limitation 8-4-6-1. Design limitations overview Type Limitations Remarks It is possible that 2 ports Connectable ≤ 19,100 BTU/h (5.6kW) is used in parallel. Indoor capacity See "8-4-6-5. 2 ports to ≤...
  • Page 78 Design of 3WAY VRF SYSTEM 8. Optional Parts 8-4-6-2. Series connection by 2 Multiple type solenoid valve kit The length between the Multiple type solenoid valve kits ○ Available combination OK : shall be within 0.66ft (0.2m). × N/A : 1 First box 2 Second box (See right table for detail about 2 box combination.)
  • Page 79 Design of 3WAY VRF SYSTEM 8. Optional Parts 8-4-6-3. Connection with Distribution Joint Multiple type solenoid valve kit after the distribution joint kit is possible. Indoor Indoor Indoor Indoor Outdoor possible Multiple type Multiple type solenoid valve kit solenoid valve kit Single type Single type solenoid valve kit...
  • Page 80 Design of 3WAY VRF SYSTEM 8. Optional Parts 8-4-6-5. 2 ports to be used in parallel ● 2 ports to be used in parallel for the unit 24-48 type Use 856 type, 656 type and 456 type Multiple type solenoid valve kit. ●...
  • Page 81 Design of 3WAY VRF SYSTEM 8. Optional Parts 8-4-6-7. Single Floor Building Layout Multiple type solenoid valve kit after the distribution joint is possible. Outdoor La= Farthest indoor unit 0.49ft ≤ 0.49ft ≤ (0.15 m ≤ ) (0.15 m ≤ ) Single type Indoor solenoid valve kit...
  • Page 82 – MEMO – 2 - 66...
  • Page 83: Wireless Remote Controller

    Control of 3WAY VRF SYSTEM Control of 3WAY VRF SYSTEM Contents Contents 3. Control of 3WAY VRF SYSTEM Excepting the electrical control equipment described below, refer to the Technical Data. 1. High-spec Wired Remote Controller (CZ-RTC3) 2. High-spec Wired Remote Controller (CZ-RTC5) 3.
  • Page 84 – MEMO – 3 - 2...
  • Page 85: Section 6: Electrical Data

    3WAY VRF SYSTEM Unit Specifications Electrical Data 3WAY VRF SYSTEM Unit Specifications Contents Contents 4. 3WAY VRF SYSTEM UNIT SPECIFICATIONS 1. Outdoor Unit ........................4-2 1-1. Specifications ......................4-2 1-2. AHRI Registration Values ..................4-9 1-3. Dimensional Data ..................... 4-10 1-4.
  • Page 86: Outdoor Unit

    3WAY VRF SYSTEM Unit Specifications 1. Outdoor Unit 1-1. Specifications Unit Specifications (1) Outdoor unit MODEL U-72MF2U9 U-96MF2U9 Performance test condition AHRI Standard 1230 AHRI Standard 1230 Cooling capacity Btu/h (kW) 72,000 (21.1) 96,000 (28.1) Nominal Heating capacity Btu/h (kW) 81,000 (23.7)
  • Page 87 3WAY VRF SYSTEM Unit Specifications 1. Outdoor Unit Unit Specifications (2) Outdoor unit MODEL U-120MF2U9 U-144MF2U9 Performance test condition AHRI Standard 1230 AHRI Standard 1230 Cooling capacity Btu/h (kW) 120,000 (35.2) 144,000 (42.2) Nominal Heating capacity Btu/h (kW) 135,000 (39.6) 162,000 (47.5) Indoor unit Ducted (Type F2)
  • Page 88 3WAY VRF SYSTEM Unit Specifications 1. Outdoor Unit Unit Specifications (3) Combination Model Name WU-168MF2U9 WU-192MF2U9 U-72MF2U9 U-72MF2U9 Outdoor unit Single Model Name U-96MF2U9 U-120MF2U9 Performance test condition AHRI Standard 1230 AHRI Standard 1230 Cooling capacity Btu/h (kW) 168,000 (49.2) 192,000 (56.3)
  • Page 89 3WAY VRF SYSTEM Unit Specifications 1. Outdoor Unit Unit Specifications (4) Combination Model Name WU-216MF2U9 WU-240MF2U9 U-96MF2U9 U-120MF2U9 Outdoor unit Single Model Name U-120MF2U9 U-120MF2U9 Performance test condition AHRI Standard 1230 AHRI Standard 1230 Cooling capacity Btu/h (kW) 216,000 (63.3) 240,000 (70.3) Nominal Heating capacity...
  • Page 90 3WAY VRF SYSTEM Unit Specifications 1. Outdoor Unit Unit Specifications (5) Combination Model Name WU-264MF2U9 WU-288MF2U9 U-120MF2U9 U-144MF2U9 Outdoor unit Single Model Name U-144MF2U9 U-144MF2U9 Performance test condition AHRI Standard 1230 AHRI Standard 1230 Cooling capacity Btu/h (kW) 264,000 (77.4) 288,000 (84.4) Nominal Heating capacity...
  • Page 91 3WAY VRF SYSTEM Unit Specifications 1. Outdoor Unit Unit Specifications (6) Combination Model Name WU-312MF2U9 WU-336MF2U9 U-72MF2U9 U-120MF2U9 U-96MF2U9 U-120MF2U9 Outdoor unit Single Model Name U-120MF2U9 U-120MF2U9 Performance test condition AHRI Standard 1230 AHRI Standard 1230 Cooling capacity Btu/h (kW) 312,000 (91.4)
  • Page 92 3WAY VRF SYSTEM Unit Specifications 1. Outdoor Unit Unit Specifications (7) Combination Model Name WU-360MF2U9 U-120MF2U9 U-120MF2U9 Outdoor unit Single Model Name U-120MF2U9 Performance test condition AHRI Standard 1230 Cooling capacity Btu/h (kW) 360,000 (105.5) Nominal Heating capacity Btu/h (kW) 405,000 (118.7) Indoor unit Ducted (Type F2)
  • Page 93: Ahri Registration Values

    Types Capacity Btu/h Btu/h 17°F Btu/h 95°F 47°F 47°F Ducted 69,000 12.7 22.3 27.6 77,000 3.70 56,000 2.66 U-72MF2U9 Non-Ducted 69,000 2.56 13.3 28.5 30.2 77,000 3.90 56,000 Mixed Ducted and Non-Ducted 69,000 13.0 56,000 2.61 25.4 28.9 77,000 3.80...
  • Page 94 3WAY VRF SYSTEM Unit Specifications 1. Outdoor Unit 1-3. Dimensional Data U-72MF2U9, U-96MF2U9, U-120MF2U9, U-144MF2U9 unit : in.(mm) *1. The tubing is routed out from the bottom. *2. The tubing is routed out from the front. 45-9/32(1,150) (Installation hole pitch)
  • Page 95: Multiple Unit Installation Example

    *2. The tubing is routed out from the front. 46-29/64(1,180) 46-29/64(1,180) 45-9/32(1,150) 45-9/32(1,150) (Installation hole pitch) (Installation hole pitch) Top view Front view Side view U-72MF2U9 U-96MF2U9 U-120MF2U9 U-144MF2U9 WU-168MF2U9 inch 2-23/64 95-9/32 3-35/64 94-3/32 Installation hole pitch (mm) (60)
  • Page 96 *2. The tubing is routed out from the front. 46-29/64(1,180) 46-29/64(1,180) 46-29/64(1,180) 45-9/32(1,150) 45-9/32(1,150) 45-9/32(1,150) (Installation hole pitch) (Installation hole pitch) (Installation hole pitch) Top view Front view Side view U-72MF2U9 U-96MF2U9 U-120MF2U9 WU-312MF2U9 2-23/64 144-3/32 3-35/64 142-29/32 inch Installation hole pitch (mm) (60) (3,660) (90)
  • Page 97: Refrigerant Flow Diagram

    3WAY VRF SYSTEM Unit Specifi cations 1. Outdoor Unit 3WAY VRF SYSTEM Unit Specifications 1. Outdoor Unit 1-5. Refrigerant Flow Diagram U-72MF2U9 / U-96MF2U9 Solenoid valve Solenoid Outside air valve Electronic control valve Oil separator 4-way valve Solenoid valve 4-way...
  • Page 98 3WAY VRF SYSTEM Unit Specifi cations 1. Outdoor Unit 3WAY VRF SYSTEM Unit Specifications 1. Outdoor Unit U-120MF2U9 / U-144MF2U9 Solenoid valve Outside air Solenoid valve Electronic control valve Oil separator 4-way valve Solenoid valve 4-way Electronic valve control valve Solenoid Solenoid valve...
  • Page 99: Noise Criterion Curves

    3WAY VRF SYSTEM Unit Specifi cations 1. Outdoor Unit 3WAY VRF SYSTEM Unit Specifications 1. Outdoor Unit 1-6. Noise Criterion Curves 60Hz Standard mode Quiet mode U-72MF2U9 U-96MF2U9 MODEL MODEL SOUND LEVEL SOUND LEVEL 53.0 56.0 dB(A) dB(A) (Quiet mode 50.0) (Quiet mode 53.0)
  • Page 100 – MEMO – 4 - 16...
  • Page 101 Test Run Contents 5. TEST RUN *Refer to the SERVICE MANUAL & TEST RUN SERVICE MANUAL (SM830246) 5 - 1...
  • Page 102 – MEMO – 5 - 2...
  • Page 103 Electrical Data Contents Contents 6. ELECTRICAL DATA 1. Outdoor Unit ........................6-2 Electric Wiring Diagram U-72MF2U9 ................ Electric Wiring Diagram U-96MF2U9 ................ Electric Wiring Diagram U-120MF2U9 ..............Electric Wiring Diagram U-144MF2U9 ..............2. Indoor Unit * Refer to the VRF SYSTEMS INDOOR UNIT TECHNICAL DATA (TD831178)
  • Page 104: Outdoor Unit

    Electrical Data Electrical Data 1. Outdoor Unit 1. Outdoor Unit (1) Electric Wiring Diagram U-72MF2U9 6 - 2...
  • Page 105 Electrical Data Electrical Data 1. Outdoor Unit 1. Outdoor Unit Schematic Diagram U-72MF2U9 6 - 2 6 - 3...
  • Page 106: Electric Wiring Diagram U-96Mf2U9

    Electrical Data Electrical Data 1. Outdoor Unit 1. Outdoor Unit (2) Electric Wiring Diagram U-96MF2U9 6 - 4...
  • Page 107 Electrical Data Electrical Data 1. Outdoor Unit 1. Outdoor Unit Schematic Diagram U-96MF2U9 6 - 2 6 - 5...
  • Page 108: Electric Wiring Diagram U-120Mf2U9

    Electrical Data Electrical Data 1. Outdoor Unit 1. Outdoor Unit (3) Electric Wiring Diagram U-120MF2U9 6 - 6 6 - 2...
  • Page 109 Electrical Data Electrical Data 1. Outdoor Unit 1. Outdoor Unit Schematic Diagram U-120MF2U9 6 - 2 6 - 7...
  • Page 110: Electric Wiring Diagram U-144Mf2U9

    Electrical Data Electrical Data 1. Outdoor Unit 1. Outdoor Unit (4) Electric Wiring Diagram U-144MF2U9 6 - 2 6 - 8...
  • Page 111 Electrical Data Electrical Data 1. Outdoor Unit 1. Outdoor Unit Schematic Diagram U-144MF2U9 6 - 2 6 - 9...
  • Page 112 – MEMO – 6 - 10...
  • Page 113: Indoor Unit

    PCB and Functions PCB and Functions Contents Contents 7. PCB AND FUNCTIONS 1. Outdoor Unit Control PCB ....................7-2 1-1. Outdoor Unit Control PCB CR-72MF2U9 / A748186............7-2 1-2. Outdoor Unit Control PCB CR-144MF2U9 / A748187..........7-3 1-3. Outdoor Unit HIC PCB A747843...................7-4 1-4.
  • Page 114: Pcb And Functions

    PCB and Functions PCB and Functions 1. Outdoor Unit Control PCB 1. Outdoor Unit Control PCB 1-1. Outdoor Unit Control PCB CR-72MF2U9 / A748186 ( U-72MF2U9 / U-96MF2U9 ) Terminal pin HIC3 ( CN43 ) ( CN67 ) RC1 plug...
  • Page 115: Outdoor Unit Control Pcb Cr-144Mf2U9 / A748187

    PCB and Functions PCB and Functions 1. Outdoor Unit Control PCB 1. Outdoor Unit Control PCB 1-2. Outdoor Unit Control PCB CR-144MF2U9 / A748187 ( U-120MF2U9 / U-144MF2U9 ) Terminal pin HIC7 ( CN78 ) HIC3 ( CN43 ) ( CN67 ) RC1 plug ( CN75 ) OC plug...
  • Page 116: Outdoor Unit Hic Pcb A747843

    PCB and Functions PCB and Functions 1. Outdoor Unit Control PCB 1. Outdoor Unit Control PCB 1-3. Outdoor Unit HIC PCB A747843 (U-72MF2U9 / U-120MF2U9 / U-144MF2U9) 1-4. Outdoor Unit HIC PCB A747846 (U-96MF2U9) 7 - 4 7 - 4...
  • Page 117: Outdoor Unit Filter Pcb A747842 / A747845

    1. Outdoor Unit Control PCB 1. Outdoor Unit Control PCB 1-5. Outdoor Unit Filter PCB A747842 A747845 (U-72MF2U9 / U-120MF2U9 / U-144MF2U9) (U-96MF2U9) 1-6. Outdoor Unit FAN PCB A747844 (U-72MF2U9 / U-96MF2U9 / U-120MF2U9 / U-144MF2U9) 7 - 5 7 - 5...
  • Page 118: Functions (For A748186, A748187)

    PCB and Functions PCB and Functions 1. Outdoor Unit Control PCB 1. Outdoor Unit Control PCB 1-7. Functions (for A748186, A748187) A. ADD pin (2P, White) Auto address setting pin (CN30) • Short-circuit this pin for 1 second or longer to automatically set the addresses at the indoor units that are connected to that outdoor unit and are within the same system.
  • Page 119 PCB and Functions PCB and Functions 1. Outdoor Unit Control PCB 1. Outdoor Unit Control PCB Terminal pin (3P, Black) For communications circuit impedance matching (CN67) • A connecting socket (2P, White) is attached to the terminal pin at the time of shipment from the factory.
  • Page 120 PCB and Functions PCB and Functions 1. Outdoor Unit Control PCB 1. Outdoor Unit Control PCB Table 7-1. Setting the System Address [SW1: Rotary switch (Black), SW2: 2P DIP (Black)] SW2 setting SW2 setting Outdoor Outdoor system system setting setting address address (10s digit)
  • Page 121 Capacity Table Capacity Table Contents Contents 8. CAPACITY TABLE 1. Capacity Ratio of Outdoor Unit ..................8-2 1-1. U-72MF2U9 (Cooling) ....................8-2 1-2. U-72MF2U9 (Heating) ....................8-4 1-3. U-96MF2U9 (Cooling) ....................8-6 1-4. U-96MF2U9 (Heating) ....................8-8 1-5. U-120MF2U9 (Cooling) ....................8-10 1-6. U-120MF2U9 (Heating) ....................8-12 1-7.
  • Page 122: Capacity Table

    Capacity Table 1. Capacity Ratio of Outdoor Unit 1-1. U-72MF2U9 (Cooling) Capacity Ratio 50 - 130 % TC : Total capacity (MBH), PI : Power input (kW) Indoor air temp. : °FWB Combination(%) Outdoor : Indoor/outdoor air temp. capacity ratio °FDB...
  • Page 123 Capacity Table 1. Capacity Ratio of Outdoor Unit U-72MF2U9 (Cooling) Capacity Ratio 50 - 130 % TC : Total capacity (MBH), PI : Power input (kW) Indoor air temp. : °FWB Combination(%) Outdoor : Indoor/outdoor air temp. capacity ratio °FDB 36.9...
  • Page 124: U-72Mf2U9 (Heating)

    Capacity Table 1. Capacity Ratio of Outdoor Unit 1-2. U-72MF2U9 (Heating) Capacity Ratio 50 - 130 % TC : Total capacity (MBH), PI : Power input (kW) Indoor air temp. : °FDB Combination(%) Outdoor :Indoor/outdoor air temp. capacity ratio °FDB °FWB...
  • Page 125 Capacity Table 1. Capacity Ratio of Outdoor Unit U-72MF2U9 (Heating) Capacity Ratio 50 - 130 % TC : Total capacity (MBH), PI : Power input (kW) Indoor air temp. : °FDB Combination(%) Outdoor :Indoor/outdoor air temp. capacity ratio °FDB °FWB -12.8...
  • Page 126: U-96Mf2U9 (Cooling)

    Capacity Table 1. Capacity Ratio of Outdoor Unit 1-3. U-96MF2U9 (Cooling) Capacity Ratio 50 - 130 % TC : Total capacity (MBH), PI : Power input (kW) Indoor air temp. : °FWB Combination(%) Outdoor :Indoor/outdoor air temp. capacity ratio °FDB 79.9 4.49 97.8...
  • Page 127 Capacity Table 1. Capacity Ratio of Outdoor Unit U-96MF2U9 (Cooling) Capacity Ratio 50 - 130 % TC : Total capacity (MBH), PI : Power input (kW) Indoor air temp. : °FWB Combination(%) Outdoor :Indoor/outdoor air temp. capacity ratio °FDB 49.2 2.16 60.2 2.64...
  • Page 128: U-96Mf2U9 (Heating)

    Capacity Table 1. Capacity Ratio of Outdoor Unit 1-4. U-96MF2U9 (Heating) Capacity Ratio 50 - 130 % TC : Total capacity (MBH), PI : Power input (kW) Indoor air temp. : °FDB Combination(%) Outdoor :Indoor/outdoor air temp. capacity ratio °FDB °FWB -12.8 -13.0...
  • Page 129 Capacity Table 1. Capacity Ratio of Outdoor Unit U-96MF2U9 (Heating) Capacity Ratio 50 - 130 % TC : Total capacity (MBH), PI : Power input (kW) Indoor air temp. : °FDB Combination(%) Outdoor :Indoor/outdoor air temp. capacity ratio °FDB °FWB -12.8 -13.0 68.7...
  • Page 130: U-120Mf2U9 (Cooling)

    Capacity Table 1. Capacity Ratio of Outdoor Unit 1-5. U-120MF2U9 (Cooling) Capacity Ratio 50 - 130 % TC : Total capacity (MBH), PI : Power input (kW) Indoor air temp. : °FWB Combination(%) Outdoor :Indoor/outdoor air temp. capacity ratio °FDB 99.8 5.71 122.3...
  • Page 131 Capacity Table 1. Capacity Ratio of Outdoor Unit U-120MF2U9 (Cooling) Capacity Ratio 50 - 130 % TC : Total capacity (MBH), PI : Power input (kW) Indoor air temp. : °FWB Combination(%) Outdoor :Indoor/outdoor air temp. capacity ratio °FDB 61.4 2.74 75.2 3.35...
  • Page 132: U-120Mf2U9 (Heating)

    Capacity Table 1. Capacity Ratio of Outdoor Unit 1-6. U-120MF2U9 (Heating) Capacity Ratio 50 - 130 % TC : Total capacity (MBH), PI : Power input (kW) Indoor air temp. : °FDB Combination(%) Outdoor :Indoor/outdoor air temp. capacity ratio °FDB °FWB -12.8 -13.0...
  • Page 133 Capacity Table 1. Capacity Ratio of Outdoor Unit U-120MF2U9 (Heating) Capacity Ratio 50 - 130 % TC : Total capacity (MBH), PI : Power input (kW) Indoor air temp. : °FDB Combination(%) Outdoor :Indoor/outdoor air temp. capacity ratio °FDB °FWB -12.8 -13.0 95.0...
  • Page 134: U-144Mf2U9 (Cooling)

    Capacity Table 1. Capacity Ratio of Outdoor Unit 1-7. U-144MF2U9 (Cooling) Capacity Ratio 50 - 130 % TC : Total capacity (MBH), PI : Power input (kW) Indoor air temp. : °FWB Combination(%) Outdoor :Indoor/outdoor air temp. capacity ratio °FDB 119.8 6.20 146.7...
  • Page 135 Capacity Table 1. Capacity Ratio of Outdoor Unit U-144MF2U9 (Cooling) Capacity Ratio 50 - 130 % TC : Total capacity (MBH), PI : Power input (kW) Indoor air temp. : °FWB Combination(%) Outdoor :Indoor/outdoor air temp. capacity ratio °FDB 73.7 2.97 90.3 3.63...
  • Page 136: U-144Mf2U9 (Heating)

    Capacity Table 1. Capacity Ratio of Outdoor Unit 1-8. U-144MF2U9 (Heating) Capacity Ratio 50 - 130 % TC : Total capacity (MBH), PI : Power input (kW) Indoor air temp. : °FDB Combination(%) Outdoor :Indoor/outdoor air temp. capacity ratio °FDB °FWB -12.8 -13.0...
  • Page 137 Capacity Table 1. Capacity Ratio of Outdoor Unit U-144MF2U9 (Heating) Capacity Ratio 50 - 130 % TC : Total capacity (MBH), PI : Power input (kW) Indoor air temp. : °FDB Combination(%) Outdoor :Indoor/outdoor air temp. capacity ratio °FDB °FWB -12.8 -13.0 101.3...
  • Page 138: Cooling Capacity Of Indoor Unit

    Capacity Table 2. Cooling Capacity of Indoor Unit 2-1. Concealed duct - Medium Static (Type F2) Indoor Unit : S-07MF2U6 Outdoor Unit : U-144MF2U9 Power supply : 208 - 230V 1phase-60Hz TC : Total Cooling Capacity (MBH) , SHC : Sensible Heat Capacity (MBH) RATING CAPACITY: 7.5 MBH AIR FLOW RATE : 494 CFM...
  • Page 139 Capacity Table 2. Cooling Capacity of Indoor Unit Indoor Unit : S-09MF2U6 Outdoor Unit : U-144MF2U9 Power supply : 208 - 230V 1phase-60Hz TC : Total Cooling Capacity (MBH) , SHC : Sensible Heat Capacity (MBH) RATING CAPACITY: 9.6 MBH AIR FLOW RATE : 494 CFM EVAPORATOR CONDENSER...
  • Page 140 Capacity Table 2. Cooling Capacity of Indoor Unit Indoor Unit : S-12MF2U6 Outdoor Unit : U-144MF2U9 Power supply : 208 - 230V 1phase-60Hz TC : Total Cooling Capacity (MBH) , SHC : Sensible Heat Capacity (MBH) RATING CAPACITY: 12.0 MBH AIR FLOW RATE : 494 CFM EVAPORATOR CONDENSER...
  • Page 141 Capacity Table 2. Cooling Capacity of Indoor Unit Indoor Unit : S-15MF2U6 Outdoor Unit : U-144MF2U9 Power supply : 208 - 230V 1phase-60Hz TC : Total Cooling Capacity (MBH) , SHC : Sensible Heat Capacity (MBH) RATING CAPACITY: 15.0 MBH AIR FLOW RATE: 494 CFM EVAPORATOR CONDENSER...
  • Page 142 Capacity Table 2. Cooling Capacity of Indoor Unit Indoor Unit : S-18MF2U6 Outdoor Unit : U-144MF2U9 Power supply : 208 - 230V 1phase-60Hz TC : Total Cooling Capacity (MBH) , SHC : Sensible Heat Capacity (MBH) RATING CAPACITY: 19.0 MBH AIR FLOW RATE : 565 CFM EVAPORATOR CONDENSER...
  • Page 143 Capacity Table 2. Cooling Capacity of Indoor Unit Indoor Unit : S-24MF2U6 Outdoor Unit : U-144MF2U9 Power supply : 208 - 230V 1phase-60Hz TC : Total Cooling Capacity (MBH) , SHC : Sensible Heat Capacity (MBH) RATING CAPACITY: 25.0 MBH AIR FLOW RATE : 742 CFM EVAPORATOR CONDENSER...
  • Page 144 Capacity Table 2. Cooling Capacity of Indoor Unit Indoor Unit : S-36MF2U6 Outdoor Unit : U-144MF2U9 Power supply : 208 - 230V 1phase-60Hz TC : Total Cooling Capacity (MBH) , SHC : Sensible Heat Capacity (MBH) RATING CAPACITY: 36.0 MBH AIR FLOW RATE : 1,201 CFM EVAPORATOR CONDENSER...
  • Page 145 Capacity Table 2. Cooling Capacity of Indoor Unit Indoor Unit : S-48MF2U6 Outdoor Unit : U-144MF2U9 Power supply : 208 - 230V 1phase-60Hz TC : Total Cooling Capacity (MBH) , SHC : Sensible Heat Capacity (MBH) RATING CAPACITY: 47.8 MBH AIR FLOW RATE : 1,271 CFM EVAPORATOR CONDENSER...
  • Page 146 Capacity Table 2. Cooling Capacity of Indoor Unit Indoor Unit : S-54MF2U6 Outdoor Unit : U-144MF2U9 Power supply : 208 - 230V 1phase-60Hz TC : Total Cooling Capacity (MBH) , SHC : Sensible Heat Capacity (MBH) RATING CAPACITY: 54.6 MBH AIR FLOW RATE : 1,342 CFM EVAPORATOR CONDENSER...
  • Page 147: Wall Mounted (Type K2)

    Capacity Table 2. Cooling Capacity of Indoor Unit 2-2. Wall Mounted (Type K2) Indoor Unit : S-07MK2U6 Outdoor Unit : U-144MF2U9 Power supply : 208 - 230V 1phase-60Hz TC : Total Cooling Capacity (MBH) , SHC : Sensible Heat Capacity (MBH) RATING CAPACITY: 7.5 MBH AIR FLOW RATE : 320 CFM...
  • Page 148 Capacity Table 2. Cooling Capacity of Indoor Unit Indoor Unit : S-09MK2U6 Outdoor Unit : U-144MF2U9 Power supply : 208 - 230V 1phase-60Hz TC : Total Cooling Capacity (MBH) , SHC : Sensible Heat Capacity (MBH) RATING CAPACITY: 9.6 MBH AIR FLOW RATE : 335 CFM EVAPORATOR CONDENSER...
  • Page 149 Capacity Table 2. Cooling Capacity of Indoor Unit Indoor Unit : S-12MK2U6 Outdoor Unit : U-144MF2U9 Power supply : 208 - 230V 1phase-60Hz TC : Total Cooling Capacity (MBH) , SHC : Sensible Heat Capacity (MBH) RATING CAPACITY: 12.0 MBH AIR FLOW RATE : 385 CFM EVAPORATOR CONDENSER...
  • Page 150 Capacity Table 2. Cooling Capacity of Indoor Unit Indoor Unit : S-18MK2U6 Outdoor Unit : U-144MF2U9 Power supply : 208 - 230V 1phase-60Hz TC : Total Cooling Capacity (MBH) , SHC : Sensible Heat Capacity (MBH) RATING CAPACITY: 18.0 MBH AIR FLOW RATE : 565 CFM EVAPORATOR CONDENSER...
  • Page 151 Capacity Table 2. Cooling Capacity of Indoor Unit Indoor Unit : S-24MK2U6 Outdoor Unit : U-144MF2U9 Power supply : 208 - 230V 1phase-60Hz TC : Total Cooling Capacity (MBH) , SHC : Sensible Heat Capacity (MBH) RATING CAPACITY: 25.0 MBH AIR FLOW RATE : 635 CFM EVAPORATOR CONDENSER...
  • Page 152: 4-Way Cassette 24"×24" (Type Y2)

    Capacity Table 2. Cooling Capacity of Indoor Unit 2-3. 4-Way Cassette 24”×24” (Type Y2) Indoor Unit : S-12MY2U6 Outdoor Unit : U-144MF2U9 Power supply : 208 - 230V 1phase-60Hz TC : Total Cooling Capacity (MBH) , SHC : Sensible Heat Capacity (MBH) RATING CAPACITY: 12.0 MBH AIR FLOW RATE : 345 CFM...
  • Page 153 Capacity Table 2. Cooling Capacity of Indoor Unit Indoor Unit : S-18MY2U6 Outdoor Unit : U-144MF2U9 Power supply : 208 - 230V 1phase-60Hz TC : Total Cooling Capacity (MBH) , SHC : Sensible Heat Capacity (MBH) RATING CAPACITY: 19.0 MBH AIR FLOW RATE : 365 CFM EVAPORATOR CONDENSER...
  • Page 154: Concealed Duct - Low Static (Type M2)

    Capacity Table 2. Cooling Capacity of Indoor Unit 2-4. Concealed duct - Low Static (Type M2) Indoor Unit : S-07MM2U6 Outdoor Unit : U-144MF2U9 Power supply : 208 - 230V 1phase-60Hz TC : Total Cooling Capacity (MBH) , SHC : Sensible Heat Capacity (MBH) RATING CAPACITY: 7.5 MBH AIR FLOW RATE : 283 CFM...
  • Page 155 Capacity Table 2. Cooling Capacity of Indoor Unit Indoor Unit : S-09MM2U6 Outdoor Unit : U-144MF2U9 Power supply : 208 - 230V 1phase-60Hz TC : Total Cooling Capacity (MBH) , SHC : Sensible Heat Capacity (MBH) RATING CAPACITY: 9.6 MBH AIR FLOW RATE : 300 CFM EVAPORATOR CONDENSER...
  • Page 156 Capacity Table 2. Cooling Capacity of Indoor Unit Indoor Unit : S-12MM2U6 Outdoor Unit : U-144MF2U9 Power supply : 208 - 230V 1phase-60Hz TC : Total Cooling Capacity (MBH) , SHC : Sensible Heat Capacity (MBH) RATING CAPACITY: 12.0 MBH AIR FLOW RATE : 318 CFM EVAPORATOR CONDENSER...
  • Page 157 Capacity Table 2. Cooling Capacity of Indoor Unit Indoor Unit : S-15MM2U6 Outdoor Unit : U-144MF2U9 Power supply : 208 - 230V 1phase-60Hz TC : Total Cooling Capacity (MBH) , SHC : Sensible Heat Capacity (MBH) RATING CAPACITY: 15.0 MBH AIR FLOW RATE : 371 CFM EVAPORATOR CONDENSER...
  • Page 158 Capacity Table 2. Cooling Capacity of Indoor Unit Indoor Unit : S-18MM2U6 Outdoor Unit : U-144MF2U9 Power supply : 208 - 230V 1phase-60Hz TC : Total Cooling Capacity (MBH) , SHC : Sensible Heat Capacity (MBH) RATING CAPACITY: 19.0 MBH AIR FLOW RATE : 442 CFM EVAPORATOR CONDENSER...
  • Page 159: 4-Way Cassette 36"×36" (Type U2)

    Capacity Table 2. Cooling Capacity of Indoor Unit 2-5. 4-Way Cassette 36”×36” (Type U2) Indoor Unit : S-24MU2U6 Outdoor Unit : U-144MF2U9 Power supply : 208 - 230V 1phase-60Hz TC : Total Cooling Capacity (MBH) , SHC : Sensible Heat Capacity (MBH) RATING CAPACITY: 25.0 MBH AIR FLOW RATE : 777 CFM...
  • Page 160 Capacity Table 2. Cooling Capacity of Indoor Unit Indoor Unit : S-36MU2U6 Outdoor Unit : U-144MF2U9 Power supply : 208 - 230V 1phase-60Hz TC : Total Cooling Capacity (MBH) , SHC : Sensible Heat Capacity (MBH) RATING CAPACITY: 36.0 MBH AIR FLOW RATE : 1,165 CFM EVAPORATOR CONDENSER...
  • Page 161: Ceiling (Type T2)

    Capacity Table 2. Cooling Capacity of Indoor Unit 2-6. Ceiling (Type T2) Indoor Unit : S-12MT2U6 Outdoor Unit : U-144MF2U9 Power supply : 208 - 230V 1phase-60Hz TC : Total Cooling Capacity (MBH) , SHC : Sensible Heat Capacity (MBH) RATING CAPACITY: 12.0 MBH AIR FLOW RATE : 494 CFM...
  • Page 162 Capacity Table 2. Cooling Capacity of Indoor Unit Indoor Unit : S-18MT2U6 Outdoor Unit : U-144MF2U9 Power supply : 208 - 230V 1phase-60Hz TC : Total Cooling Capacity (MBH) , SHC : Sensible Heat Capacity (MBH) RATING CAPACITY: 19.0 MBH AIR FLOW RATE : 530 CFM EVAPORATOR CONDENSER...
  • Page 163 Capacity Table 2. Cooling Capacity of Indoor Unit Indoor Unit : S-24MT2U6 Outdoor Unit : U-144MF2U9 Power supply : 208 - 230V 1phase-60Hz TC : Total Cooling Capacity (MBH) , SHC : Sensible Heat Capacity (MBH) RATING CAPACITY: 25.0 MBH AIR FLOW RATE : 742 CFM EVAPORATOR CONDENSER...
  • Page 164: 1-Way Cassette (Type D1)

    Capacity Table 2. Cooling Capacity of Indoor Unit 2-7. 1-Way Cassette (Type D1) Indoor Unit : S-07MD1U6 Outdoor Unit : U-144MF2U9 Power supply : 208 - 230V 1phase-60Hz TC : Total Cooling Capacity (MBH) , SHC : Sensible Heat Capacity (MBH) RATING CAPACITY: 7.5 MBH AIR FLOW RATE : 280 CFM...
  • Page 165 Capacity Table 2. Cooling Capacity of Indoor Unit Indoor Unit : S-09MD1U6 Outdoor Unit : U-144MF2U9 Power supply : 208 - 230V 1phase-60Hz TC : Total Cooling Capacity (MBH) , SHC : Sensible Heat Capacity (MBH) RATING CAPACITY: 9.6 MBH AIR FLOW RATE : 280 CFM EVAPORATOR CONDENSER...
  • Page 166 Capacity Table 2. Cooling Capacity of Indoor Unit Indoor Unit : S-12MD1U6 Outdoor Unit : U-144MF2U9 Power supply : 208 - 230V 1phase-60Hz TC : Total Cooling Capacity (MBH) , SHC : Sensible Heat Capacity (MBH) RATING CAPACITY: 12.0 MBH AIR FLOW RATE : 320 CFM EVAPORATOR CONDENSER...
  • Page 167: Concealed Duct - High Static (Type E1)

    Capacity Table 2. Cooling Capacity of Indoor Unit 2-8. Concealed duct - High Static (Type E1) Indoor Unit : S-36ME1U6 Outdoor Unit : U-144MF2U9 Power supply : 208 - 230V 1phase-60Hz TC : Total Cooling Capacity (MBH) , SHC : Sensible Heat Capacity (MBH) RATING CAPACITY: 36.0 MBH AIR FLOW RATE : 1,060 CFM...
  • Page 168 Capacity Table 2. Cooling Capacity of Indoor Unit Indoor Unit : S-48ME1U6 Outdoor Unit : U-144MF2U9 Power supply : 208 - 230V 1phase-60Hz TC : Total Cooling Capacity (MBH) , SHC : Sensible Heat Capacity (MBH) RATING CAPACITY: 47.8 MBH AIR FLOW RATE : 1,270 CFM EVAPORATOR CONDENSER...
  • Page 169: Floor Standing (Type P1)

    Capacity Table 2. Cooling Capacity of Indoor Unit 2-9. Floor Standing (Type P1) Indoor Unit : S-07MP1U6 Outdoor Unit : U-144MF2U9 Power supply : 208 - 230V 1phase-60Hz TC : Total Cooling Capacity (MBH) , SHC : Sensible Heat Capacity (MBH) RATING CAPACITY: 7.5 MBH AIR FLOW RATE : 247 CFM...
  • Page 170 Capacity Table 2. Cooling Capacity of Indoor Unit Indoor Unit : S-09MP1U6 Outdoor Unit : U-144MF2U9 Power supply : 208 - 230V 1phase-60Hz TC : Total Cooling Capacity (MBH) , SHC : Sensible Heat Capacity (MBH) RATING CAPACITY: 9.6 MBH AIR FLOW RATE : 247 CFM EVAPORATOR CONDENSER...
  • Page 171 Capacity Table 2. Cooling Capacity of Indoor Unit Indoor Unit : S-12MP1U6 Outdoor Unit : U-144MF2U9 Power supply : 208 - 230V 1phase-60Hz TC : Total Cooling Capacity (MBH) , SHC : Sensible Heat Capacity (MBH) RATING CAPACITY: 12.0 MBH AIR FLOW RATE : 318 CFM EVAPORATOR CONDENSER...
  • Page 172 Capacity Table 2. Cooling Capacity of Indoor Unit Indoor Unit : S-15MP1U6 Outdoor Unit : U-144MF2U9 Power supply : 208 - 230V 1phase-60Hz TC : Total Cooling Capacity (MBH) , SHC : Sensible Heat Capacity (MBH) RATING CAPACITY: 15.0 MBH AIR FLOW RATE : 424 CFM EVAPORATOR CONDENSER...
  • Page 173 Capacity Table 2. Cooling Capacity of Indoor Unit Indoor Unit : S-18MP1U6 Outdoor Unit : U-144MF2U9 Power supply : 208 - 230V 1phase-60Hz TC : Total Cooling Capacity (MBH) , SHC : Sensible Heat Capacity (MBH) RATING CAPACITY: 19.0 MBH AIR FLOW RATE : 530 CFM EVAPORATOR CONDENSER...
  • Page 174 Capacity Table 2. Cooling Capacity of Indoor Unit Indoor Unit : S-24MP1U6 Outdoor Unit : U-144MF2U9 Power supply : 208 - 230V 1phase-60Hz TC : Total Cooling Capacity (MBH) , SHC : Sensible Heat Capacity (MBH) RATING CAPACITY: 24.0 MBH AIR FLOW RATE : 601 CFM EVAPORATOR CONDENSER...
  • Page 175: Concealed Floor Standing (Type R1)

    Capacity Table 2. Cooling Capacity of Indoor Unit 2-10. Concealed Floor Standing (Type R1) Indoor Unit : S-07MR1U6 Outdoor Unit : U-144MF2U9 Power supply : 208 - 230V 1phase-60Hz TC : Total Cooling Capacity (MBH) , SHC : Sensible Heat Capacity (MBH) RATING CAPACITY: 7.5 MBH AIR FLOW RATE : 247 CFM...
  • Page 176 Capacity Table 2. Cooling Capacity of Indoor Unit Indoor Unit : S-09MR1U6 Outdoor Unit : U-144MF2U9 Power supply : 208 - 230V 1phase-60Hz TC : Total Cooling Capacity (MBH) , SHC : Sensible Heat Capacity (MBH) RATING CAPACITY: 9.6 MBH AIR FLOW RATE : 247 CFM EVAPORATOR CONDENSER...
  • Page 177 Capacity Table 2. Cooling Capacity of Indoor Unit Indoor Unit : S-12MR1U6 Outdoor Unit : U-144MF2U9 Power supply : 208 - 230V 1phase-60Hz TC : Total Cooling Capacity (MBH) , SHC : Sensible Heat Capacity (MBH) RATING CAPACITY: 12.0 MBH AIR FLOW RATE : 318 CFM EVAPORATOR CONDENSER...
  • Page 178 Capacity Table 2. Cooling Capacity of Indoor Unit Indoor Unit : S-15MR1U6 Outdoor Unit : U-144MF2U9 Power supply : 208 - 230V 1phase-60Hz TC : Total Cooling Capacity (MBH) , SHC : Sensible Heat Capacity (MBH) RATING CAPACITY: 15.0 MBH AIR FLOW RATE : 318 CFM EVAPORATOR CONDENSER...
  • Page 179 Capacity Table 2. Cooling Capacity of Indoor Unit Indoor Unit : S-18MR1U6 Outdoor Unit : U-144MF2U9 Power supply : 208 - 230V 1phase-60Hz TC : Total Cooling Capacity (MBH) , SHC : Sensible Heat Capacity (MBH) RATING CAPACITY: 19.0 MBH AIR FLOW RATE : 530 CFM EVAPORATOR CONDENSER...
  • Page 180 Capacity Table 2. Cooling Capacity of Indoor Unit Indoor Unit : S-24MR1U6 Outdoor Unit : U-144MF2U9 Power supply : 208 - 230V 1phase-60Hz TC : Total Cooling Capacity (MBH) , SHC : Sensible Heat Capacity (MBH) RATING CAPACITY: 24.0 MBH AIR FLOW RATE : 601 CFM EVAPORATOR CONDENSER...
  • Page 181 201512...

This manual is also suitable for:

U-144mf2u9U-96mf2u9U-120mf2u9

Table of Contents