Panasonic U-72MF2U9 Service Manual page 111

3way vrf system
Table of Contents

Advertisement

6. Mode Settings
n Setting mode 2
<Operating procedure>
â
Press and hold the
simultaneously for 4 seconds or longer.
ê
Press the temperature setting
code. The item codes and setting data are shown in the table below.
ô
Press the timer time
To confirm the changed setting data, press the
(At this time, "
" display stops blinking and remains lit.)
û
During this mode, "
outdoor unit address "System XX-YY" (System XX = System address, YY =
Address at outdoor unit sub-bus), item code number (DN value in the table
below), and the setting data (6 digits).
(The setting data is displayed in 6 digits. The display changes between the first 3 digits (Fig.
digits (Fig.
). When the first 3 digits are displayed, the bottom point of the colon is lit.)
A
B
á
To exit setting mode, press the
5
List of Item Codes
DN
Parameter
81
Outdoor unit capacity
(CHECK) button,
button, and
and
buttons to change the item
and
buttons to change the setting data.
" is displayed, blinking. The display shows the set
(CHECK) button. Returns to the normal display mode.
Display of first 3 digits
A
1
3
<Refrigerant type> A
A
and
shows 000 410 (R410A).)
000 = Disabled 210 = Type 72 280 = Type 96 355 = Type 120 420 = Type 144
Outdoor Unit Maintenance Remote Controller
button
button.
Display of last 3 digits
B
2
B
B are displayed alternately. (Example
Description
3 - 13
3WAY VRF SYSTEM
5
3
1
Fig. 7
) and the last 3
A
B
2
1
2
3
4
5
6
7
8
9