Panasonic U-72MF2U9 Service Manual page 135

3way vrf system
Table of Contents

Advertisement

2. Detailed Settings Function
Item code
Item
(1B)
Forced thermostat ON time
Cooling discharge
temperature shift
Heating discharge
temperature shift
Temperature shift for
cooling/heating change in
auto heat/cool mode
(Upper limit)
(Lower limit)
(Upper limit)
Change to remote
(Lower limit)
control temperature
setting range
(Upper limit)
(Lower limit)
(Upper limit)
(Lower limit)
Humidifier operation
Filter (CN70) input
switching
Indoor unit electronic
control valve
T10 terminal switching
No.
0000
5 minutes
0001
4 minutes
–010
Shifts discharge temperature setting 20°F down.
–009
Shifts discharge temperature setting 18°F down.
–008
Shifts discharge temperature setting 16°F down.
0010
Shifts discharge temperature setting 20°F up.
–010
Shifts discharge temperature setting 20°F down.
–009
Shifts discharge temperature setting 18°F down.
–008
Shifts discharge temperature setting 16°F down.
0010
Shifts discharge temperature setting 20°F up.
0001
±2°F
0002
±4°F
0003
±6°F
0007
±14°F
0018
64°F (Lower limit at shipment)
0019
66°F
0029
84°F
0030
86°F (Upper limit at shipment)
0016
60°F (Lower limit at shipment)
0017
62°F
0029
84°F
0030
86°F (Upper limit at shipment)
0018
64°F (Lower limit at shipment)
0019
66°F
0029
84°F
0030
86°F (Upper limit at shipment)
0017
62°F (Lower limit at shipment)
0018
64°F
0026
78°F
0027
80°F (Upper limit at shipment)
0000
Normal
0001
Ignore heat exchanger temperature conditions.
0000
Filter input (differential pressure switch input)
0001
Alarm input (for trouble input about air cleaner or similar device)
Humidifier input (Operates linked with drain pump when humidifier is
0002
ON.)
0000
Present (Setting at shipment)
0002
None
0000
Normal (Used as optional relay PCB or JEMA standard HA terminal.)
0001
Used for OFF reminder
0002
Fire prevention input
4 - 13
3WAY VRF SYSTEM
Remote Controller Functions
Setting data
Description
1
2
3
4
5
6
7
8
9

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

U-96mf2u9U-120mf2u9U-144mf2u9

Table of Contents