10.2. Room thermostat installation configuration
When no room thermostat is connected to
the unit, toggle switch SS2-3 should be set to
OFF.
When the room thermostat is connected to
the unit, toggle switch SS2-3 should be set to
ON.
On the room thermostat, confirm the correct settings (6®02=yes,
6®05=9, 6®06=5) to prevent the pump from repeatedly turning on
and off (i.e. chattering), and thereby impacting the lifetime of
the pump.
INFORMATION
When a room thermostat is connected to the unit, the
heating and cooling schedule timers are never
available. Other schedule timers are not affected. For
more information on the schedule timers, refer to the
operation manual.
When a room thermostat is connected to the unit, and
the = button or y button is pressed, the
centralised control indicator e will flash to indicate
that the room thermostat has priority and controls
on/off operation and changeover operation.
The following table summarizes the required configuration and
thermostat wiring at the terminal block (X2M: 1, 2, 3, 4) in the switch
box. Pump operation is listed in the third column. The three last
columns indicate whether the following functionality is available on
the user interface (UI) or handled by the thermostat (T):
space heating or cooling on/off (y)
heating/cooling changeover (=)
heating and cooling schedule timers (pr)
Thermostat
Configuration
No thermostat
• SS2-3=OFF
• wiring: (non)
X2M
1 2 3 4
• SS2-3=ON
• wiring:
X2M
1 2 3 4
Heating only
• SS2-3=ON
thermostat
• wiring: (see
installation
manual of the
room
thermostat kit)
Thermostat with
• SS2-3=ON
heating/cooling
• wiring: (see
switch
installation
manual of the
room
thermostat kit)
(a) The pump will stop when space heating/cooling is turned off or when the water
reaches the desired water temperature as set on the user interface. With space
heating/cooling turned on, the pump will then run every 5 minutes during 3
minutes to check the water temperature.
Installation manual
29
1
2
3
1
2
3
y
y
y
y
=
=
=
=
Pump operation
determined by
leaving water
(a)
temperature
UI
UI
on when space
heating or
cooling is on
(y)
UI
UI
on when heating
request by room
thermostat
T
on when heating
request or
cooling request
T
T
by room
thermostat
10.3. Pump operation configuration
INFORMATION
4
To set the pump speed, refer to
speed" on page
Without room thermostat: DIP switch SS2-3=OFF
4
When no thermostat is connected to the unit, pump operation will be
determined by the leaving water temperature.
To force continuous pump operation when no room thermostat is
connected do the following:
-
set toggle switch SS2-3 to ON,
-
short-circuit the terminal numbers 1-2-4 on the terminal block
in the switch box.
With room thermostat DIP switch: SS2-3=ON
When the thermostat is connected to the unit, the pump will operate
continuously whenever there is heating or cooling demand requested
by the thermostat.
Dual set point
When dual set point is enabled, the pump operation will be
determined depending on the status of the DIP switch SS2-3 and set
point selection contacts. Refer to the table below.
INFORMATION
When dual set point is enabled, the "forced continuous
pump operation" is not possible. When SS2-3 is ON while
SP1 and SP2 are both closed, the pump operation will be
the same operation as "with room thermostat" and the
second set point will be the applicable set point. Refer to
the table below.
The following table summarizes the required configuration and wiring
at the terminal block (X2M: 1, 2, 4) in the switch box. Pump operation
is listed in the third column. The three last columns indicate whether
p p p p r r r r
the following functionality is available on the user interface (
handled by the set point selection contacts SP1 and SP2:
space heating or cooling on/off (y)
UI
heating/cooling changeover (=)
heating and cooling schedule timers (pr)
Configuration
• [7-02]=1
UI
• SS2-3=OFF
• wiring:
X2M
1 2 3 4
SP2
SP1
• [7-02]=1
• SS2-3=ON
• wiring:
X2M
1 2 3 4
SP2
SP1
SP1 = First set point contact
SP2 = Second set point contact
(a) The pump will stop when space heating/cooling is turned off or when the water
reaches the desired water temperature as set on the user interface. With space
heating/cooling turned on, the pump will then run every 5 minutes during 3
minutes to check the water temperature.
"10.8. Setting the pump
31.
Dual set point
y
y
y
y
Pump operation
determined by leaving
(a)
water temperature
UI
on when main or/and
sub set point is
requested
SP2/SP1
Unit for air to water heat pump system
) or
UI
=
=
=
=
p p p p r r r r
UI
UI
UI
E(D/B)(H/L)Q011~016BB
4PW67904-1 – 01.2011

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents