S
-
TART
UP AND CONFIGURATION
The indoor unit should be configured by the installer to match the
installation environment (outdoor climate, installed options, etc.) and
user expertise.
It is important that all information in this chapter is read
sequentially by the installer and that the system is
configured as applicable.

DIP switch settings overview

DIP switch SS2 is located on the switch box PCB (see
main components" on page
11) and allows configuration of domestic
hot water tank installation, room thermostat connection and pump
operation.
WARNING
Switch off the power supply before opening the switch box
service panel and making any changes to the DIP switch
settings.
DIP
switch
SS2
Description
1
Not applicable for installer
2
Domestic hot water tank
installation
(see
"Domestic hot water
tank installation
configuration" on page
3
Room thermostat
connection
(see
"Room thermostat
installation configuration"
on page
21)
(a)
4
This setting
decides the
operation mode of the
heat pump when there is a
simultaneous demand for
more space
heating/cooling and
domestic water heating.
(a) Only applicable in case DIP switch 2 = ON.
(b) Heating/cooling or domestic water heating mode can be restricted by schedule
timer and/or field settings (4, 5, 8).
Room thermostat installation configuration
When no room thermostat is connected to
the indoor unit, toggle switch SS2-3 should be
set to OFF.
When the room thermostat is connected to
the indoor unit, toggle switch SS2-3 should be
set to ON.
On the room thermostat, confirm the correct settings (6®02=yes,
6®05=9, 6®06=5) to prevent the pump from repeatedly turning on
and off (i.e. chattering), and thereby impacting the lifetime of
the pump.
EKHBH/X008BA
Indoor unit for air to water heat pump system
4PW54185-1B
"Switch box
1
2
3
4
ON
OFF
(Default)
Installed
Not installed
(Default)
22)
Room thermostat
No room
connected
thermostat
connected
(Default)
Heating/cooling
Priority to highest
priority
demand side
1
1
When the room thermostat is connected to the indoor
unit, the heating and cooling schedule timers are
never available. Other schedule timers are not
affected. For more information on the schedule timers,
refer to the operation manual.
When the room thermostat is connected to the indoor
unit, and the = button or y button is pressed, the
centralised control indicator e will flash to indicate
that the room thermostat has priority and controls
on/off operation and change over operation.
The following table summarizes the required configuration and
thermostat wiring at the terminal block (X2M: 1, 2, 3, 4) in the switch
box. Pump operation is listed in the third column. The three last
columns indicate whether the following functionality is available on
the user interface (UI) or handled by the thermostat (T):
space heating or cooling on/off (y)
heating/cooling changeover (=)
heating and cooling schedule timers (pr)
Thermostat
No thermostat
Heating only
thermostat
Thermostat with
heating/cooling
switch
(b)
(a) The pump will stop when space heating/cooling is turned off or when the water
reaches the desired water temperature as set on the user interface. With space
heating/cooling turned on, the pump will then run every 5 minutes during 3
minutes to check the water temperature.
2
3
4
2
3
4
Pump
Configuration
operation
• SS2-3 = OFF
determined by
• wiring: (non)
leaving water
(a)
temperature
X2M
1 2 3 4
• SS2-3 = ON
on when space
• wiring:
heating or
cooling is on
X2M
(y)
1 2 3 4
• SS2-3 = ON
on when
• wiring: (see
heating
installation
request by
manual of the
room
room
thermostat
thermostat kit)
on when
• SS2-3 = ON
heating
• wiring: (see
request or
installation
manual of the
cooling request
room
by room
thermostat kit)
thermostat
y
y
=
=
p p p p r r r r
y
y
=
=
UI
UI
UI
UI
UI
UI
T
T
T
Installation manual