Daikin Altherma EDHQ011BB6V3 Installation Manual page 46

Unit for to water heat pump system
Hide thumbs Also See for Altherma EDHQ011BB6V3:
Table of Contents

Advertisement

Local shift value weather dependent
The local shift value weather dependent field setting is only relevant
in case weather dependent set point (see field setting
dependent set point" on page
[d-03] Local shift value weather dependent: determines the
shift value of the weather dependent set point around
outdoor temperature of 0°C.
T
t
[1-02]
R
[1-03]
[1-00]
0°C
T
Target water temperature
t
T
Outdoor temperature
A
R Range
L Local shift value
[1-00]~[1-04] Applicable field settings of the weather dependent set
point [1].
Outdoor temperature range
[d-03]
(T
0
1
–2°C~2°C
2
3
–4°C~4°C
4
[E] Unit information readout
[E-00] Readout of the software version (example: 23)
[E-01] Readout of the EEPROM version (example: 23)
[E-02] Readout of the unit model identification (example: 11)
[E-03] Readout of the liquid refrigerant temperature
[E-04] Readout of the inlet water temperature
NOTICE
[E-03] and [E-04] readouts are not permanently
refreshed. Temperature readouts are updated after
looping through the field setting first codes again only.
Installation manual
43
"[1] Weather
32) is selected.
L
[1-01]
T
A
)
Local shift value
A
2
4
2
4
[F] Option setup
Pump operation
The pump operation field setting apply to the pump operation logic
only when DIP switch SS2-3 is OFF.
When the pump operation function is disabled the pump will stop if
the outdoor temperature is higher than the value set by [4-02] or if the
outdoor temperature drops below the value set by [F-01]. When the
pump operation is enabled, the pump operation is possible at all
outdoor temperatures. Refer to
on page
29.
[F-00] Pump operation: specifies wether the pump operation
function is enabled (1) or disabled (0).
Space cooling permission
[F-01] Space cooling permission temperature: defines the
outdoor temperature below which space cooling is turned off.
INFORMATION
This function is only valid for EB units when space
cooling is selected.
Bottom plate heater control
Applies only to installation with an E(D/B)LQ unit or in case the option
bottom plate heater kit is installed.
[F-02] Bottom plate heater ON temperature: defines the
outdoor temperature below which the bottom plate heater will
be activated in order to prevent ice build-up in the bottom
plate at lower outdoor temperatures.
[F-03] Bottom
plate
temperature difference between bottom plate heater ON
temperature and the bottom plate heater OFF temperature.
Bottom plate heater
ON
OFF
[F-02]
T
Outdoor temperature
A
CAUTION
The bottom plate heater is controlled via X14A. Make sure
[F-04] is correctly set.
Functionality of X14A
[F-04] Functionality of X14A: specifies if the logic of X14A
follows the output signal for the solar kit model (EKSOLHW)
(0) or if the logic of X14A follows the output for the bottom
plate heater (1).
INFORMATION
Independent from field setting [F-04], the contact X3-X4
(EKRP1HB) follows the logic of the output signal for the
solar kit model (EKSOLHW). See figure below for the
schematic location of this contact.
X2M
YC Y1 Y2 Y3 Y4
"10.3. Pump operation configuration"
heater
hysteresis:
defines
[F-03]
T
A
OFF ON
SS1
X1M
E(D/B)(H/L)Q011~016BB
Unit for air to water heat pump system
4PW67904-1 – 01.2011