Heat & Glo SL-550TR-E Installation Manual page 24

Hide thumbs Also See for SL-550TR-E:
Table of Contents

Advertisement

Top Vent - Vertical Termination
No Elbow
V
= 60 ft. Max. (18.3 m)
1
Note: If installing a vertical vent/termination off the top of
the appliance, the optional vertical termination baffl e may
be needed.
Note: Use SLP Series
components only.
Figure 4.11
Exhaust restrictors are recommended for these vertically
terminated products which have excessive draft. Exhaust
restrictors will compensate for high draft, and restore vi-
sual fl ame height. If the vent confi guration has a total
vertical of 15-60 feet, an exhaust restrictor may be need-
ed. The exhaust restrictor can be located in the appliance
manual bag.
Heat & Glo • SL-550/750TR-E, SL-550/750/950TR-IPI-E Installation Manual • 2118-910 Rev. C • 4/16
24
V
1
Exhaust restrictor Instructions
1. Install the exhaust restrictor over the center of the ex-
haust outlet in the fi rebox. See Figure 4.12.
2. Center the exhaust restrictor in the open end of the
exhaust outlet and secure through the slots on the ex-
haust restrictor with the 2-1/4 in. self-tapping screws
provided in the appliance manual bag.
To access the exhaust
openings, remove the
exhaust baffl e. To re-
move exhaust baffl e, re-
move the two wing nuts.
Top Vent Application
Exhaust restrictor
Rear Vent Application
Exhaust restrictor
Note: Be sure to rein-
stall the exhaust baffl e
after exhaust restrictor
installation.
Figure 4.12
EXHAUST BAFFLE