Heat & Glo SL-550TR-E Installation Manual page 21

Hide thumbs Also See for SL-550TR-E:
Table of Contents

Advertisement

Top Vent - Horizontal Termination
One Elbow
V
Minimum
1
90 Elbow *
1/2 ft.*
152 mm
1-1/2 ft.* 457 mm
2-1/2 ft.* 762 mm
3-1/2 ft.
1.1 m
4-1/2 ft.
1.4 m
Fire Risk.
• When using SLP-HRC-SS and SLP-HRC-ZC-SS
termination caps on top vented fi replaces, a one
foot minimum vertical vent section is required before
installing fi rst elbow.
• When using DVP-TB1 termination cap on top vented fi replaces,
a three foot minimum vertical vent section is required before
installing fi rst elbow.
Figure 4.8
Heat & Glo • SL-550/750TR-E, SL-550/750/950TR-IPI-E Installation Manual • 2118-910 Rev. C • 4/16
H
Maximum
1
SL-550TR-E
SL-550TR-E
SL-550TR-IPI-E
SL-750TR-IPI-E
2 ft.
610 mm
2 ft.
610 mm
2 ft.
610 mm
2 ft.
610 mm
3 ft.
914 mm
3 ft.
914 mm
5 ft.
1.5 m
5 ft.
7 ft.
2.1 m
7 ft.
14 ft.
4.3 m
14 ft.
H MAX. =14 ft. (4.3 m)
V + H MAX. = 40 ft. (12.2 m)
* See warning below
WARNING *
SL-950TR-IPI-E
1 ft.
305 mm
2 ft.
610 mm
3 ft.
914 mm
1.5 m
5 ft.
1.5 m
2.1 m
7 ft.
2.1 m
4.3 m
14 ft.
4.3 m
H
1
Note: Use SLP Series
components only.
Note: There MUST be a 25%
reduction in total H when using
fl ex vent except when using the
simple up and out installation.
See Figure 4.6.
V
1
21