Connection to the Stand-Alone Option
1.6.3
Connection of the power regeneration common
converter (FR-CV)
When connecting the FR-CV type power regeneration common converter, connect the
inverter terminals (P, N) and FR-CV type power regeneration common converter
terminals as shown below so that their signals match with each other.
NFB
MC
Three-phase
AC power
supply
CAUTION
1. Use sink logic (factory setting) when the FR-CV is connected. The FR-CV
cannot be connected when source logic is selected.
2. The power input terminals R, S, T must be open. Incorrect connection will
damage the inverter. Opposite polarity of terminals N, P will damage the
inverter.
3. The voltage phases of terminals R/L11, S/L21, T/MC1 and terminals R2/L1,
S2/L2, T2/L3 must be matched before connection.
4. Use Pr. 60 to Pr. 63 (input terminal function selection) to assign the terminals
used for the RES and MRS signals.
5. Do not insert NFB between terminals P-N (P/L+ - P, N/L - N)
6. Make sure to connect the terminal R/L11, S/L21, T/MC1 to the power supply.
Running the inverter without connecting the terminals will damage the
power regeneration common converter.
7. The N terminal is not provided for the FR-S520E-0.1K to 0.75K.
Dedicated stand-alone
reactor (FR-CVL)
1
R/L
R2/L
11
S/L
S2/L
21
22
T/L
T2/L
31
32
FR-CV power regenerative
common converter
(Caution 3)
12
R2/L
1
S2/L
P/L+
2
T2/L
N/L-
3
(Caution 6)
P24
R/L
11
SD
S/L
21
RDYA
T/MC1
RDYB
RSO
SE
40
R
S
(Caution 2)
T
Inverter
(Caution 5)
P
N
(Caution 7)
PC
SD
(Caution 1)
MRS (Caution 4)
RES (Caution 4)
U
IM
V
W

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Fr-s520e-0.1kFr-s540e-0.4kFr-s510we-0.1k

Table of Contents