5) Forward action
Increases the manipulated
variable (output frequency) if
deviation X = (set point -
measured value) is negative,
and decreases the manipulated
variable if deviation is positive.
Relationships between deviation and manipulated variable (output frequency)
Reverse action
Forward action
(3) Wiring example
Pr. 60 = 14
Pr. 64 = 15
Pr. 65 = 16
Pr. 88 = 20
Forward rotation
Reverse rotation
potentiometer
(Set point setting)
AC1
200/220V 50/60Hz
CAUTION
*1.The power supply must be selected in accordance with the power
specifications of the detector used.
*2.The output signal terminals used depends on the Pr. 64, Pr. 65 settings.
*3.The input signal terminal used depends on the setting of Pr. 60 to Pr. 63.
The contact input signal (AU Signal) need not be turned on.
Set point
Too cold
Hot
Deviation
Positive
Negative
NFB
R/L1
Power
S/L2
supply
T/L3
STF
STR
SD
PID control
RH(X14)(*3)
selection
RUN(FUP,FDN)
10
Setting
2
5
4
0
power supply
φ
Operation selection function parameters
[Cooling]
+
X>0
X<0
-
Feedback signal
(Measured value)
down
up
Deviation
Inverter
Motor
U
IM
V
W
Upper limit
(Lower limit)
Limit signal
common
Forward
rotation output
(*2)
Reverse
SE
rotation output
A
C
Forward (reverse)
rotation output
signal common
(Measured value) 4 to 20mA
24V
(*1)
115
Measured value
Set point
Pump
P
For
2-wire
For
type
3-wire
Detector
type
-
+
-
+
+
(OUT)
(COM)
(24V)
2

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Fr-s520e-0.1kFr-s540e-0.4kFr-s510we-0.1k

Table of Contents