<Setting>
Refer to the following table and set the parameters:
Signal
Setting
Name
0
RL
1
RM
2
RH
3
RT
Second function selection
4
AU
Current input selection
5
STOP
Start self-holding selection
6
MRS
Output shut-off stop
External thermal relay input (*2)
The inverter stops when the externally
7
OH
provided thermal relay for overheat
protection, motor's embedded temperature
relay etc. is actuated.
15-speed selection (combination with 3
8
REX
speeds RL, RM, RH) (*3)
9
JOG
Jog operation selection
10
RES
Reset
14
X14
PID control presence/absence selection
16
X16
PU-external operation switch-over
- - -
STR
Reverse rotation start
*1.When Pr. 59 = "1 or 2", the functions of the RL, RM and RH signals change as
listed above.
*2.Actuated when the relay contact "opens".
*3.When using the REX signal, an external command cannot be used to make a
reverse rotation start.
REMARKS
One function can be assigned to two or more terminals. In this case, the function is activated
when one of the multiple terminals used for assignment turns on.
The speed command priorities are higher in order of jog, multi-speed setting (RH, RM, RL,
REX) and AU.
Use common terminals to assign multi-speeds (7 speeds) and remote setting. They cannot
be set individually.
(Common terminals are used since these functions are designed for speed setting and need
not be set at the same time.)
Functions
Pr. 59 = "0"
Pr. 59 = "1", "2" (*1)
Pr. 59 = "0"
Pr. 59 = "1", "2" (*1)
Pr. 59 = "0"
Pr. 59 = "1", "2" (*1)
Terminal function selection parameters
Low-speed operation
command
Remote setting
(setting clear)
Middle-speed
operation command
Remote setting
(deceleration)
High-speed operation
command
Remote setting
(acceleration)
99
Related Parameters
Pr. 4 to Pr. 6, Pr. 24 to Pr. 27,
Pr. 80 to Pr. 87
Pr. 59
Pr. 4 to Pr. 6, Pr. 24 to Pr. 27,
Pr. 80 to Pr. 87
Pr. 59
Pr. 4 to Pr. 6, Pr. 24 to Pr. 27,
Pr. 80 to Pr. 87
Pr. 59
Pr. 44 to Pr. 47, H7
Refer to page 160.
Pr. 4 to Pr. 6, Pr. 24 to Pr. 27,
Pr. 80 to Pr. 87
Pr. 15, Pr. 16
Pr. 75
Pr. 88 to Pr. 94
Pr. 79 (setting: 8)
(can be assigned to STR