11 11
Finishing
A. Mantel Projections
Figure 11.1 shows the minimum vertical and corresponding
maximum horizontal dimensions of appliance mantels or
other combustible projections above the top front edge of
the appliance.
6
5
4
12-1/4
3
11-1/2
2
10-3/4
1
10
9-1/4
8-1/2
Figure 11.1 Clearances to Mantels or other Combustibles above
Appliance.
Top of
Appliance
1 in. (25 mm) min.
A
to perpendicular wall
6.25 in. (159 mm) min.
B
from fireplace opening
to perpendicular wall
Figure 11.2 Mantel Leg or Wall Projections
(Acceptable on both sides of opening)
34
16
15
14
19-3/4
13
19
12
18-1/4
11
17-1/2
10
16-3/4
9
16
8
15-1/4
7
14-1/2
13-3/4
13
Measured from top of fireplace opening (in inches)
Drywall
A
48 in.
(1219 mm)
max.
B
Mantel Leg or
Perpendicular Wall
Heatilator • ICON DV • 4042-300 Rev R • 06/07
B. Facing Material
30 in. minimum
to ceiling
18
17
21-1/4
20-1/2
High Temperature Sealant (300° F/149° C min.)
Figure 11.3 Noncombustible Facing Diagram
•
Appliance front may be covered with non-combustible
material only.
•
Do NOT overlap combustible materials onto appliance
front.
•
Install combustible materials only up to specifi ed
clearances on top, front and sides.
•
Seal joints between the fi nished wall and appliance
top and sides using only a 300° F minimum sealant.
WARNING
Fire Risk
Do NOT obstruct air inlet or outlet grilles.
Do NOT modify grilles.
•
Modifying or covering grilles could cause
temperature rise and fi re hazard.
Finishing materials must not interfere with:
•
Air fl ow through grilles or louvers.
•
Operation of louvers or doors.
•
Access for service.
Finish wall material may be
combustible - Top and Sides
0 in.
Top and Side Seal Joint
WARNING
Fire Risk
Explosion Risk
•
Facing and/or fi nishing materials must never
overhang into the glass opening.
•
Overhanging materials may ignite.
•
May interfere with proper operation of glass
assembly.
WARNING
Fire Risk
Finish all edges and fronts to clearances and
specifi cations listed in manual.
0 in.
0 in.