C. Install the Heat Shield and Horizontal Termination Cap
WARNING
Fire Risk
Impaired performance of appliance.
Telescoping fl ue section of termination
cap MUST be used when connecting pipe
section to termination cap.
Maintain a 1-1/2 in. (38 mm) minimum
overlap on telescoping fl ue section of
termination cap.
WARNING
Fire Risk
Exhaust Fumes Risk
Impaired performance of appliance.
Overlap pipe slip sections at least
1-1/2 in. (38 mm).
Use pilot holes for screws.
Screws must not exceed 1 in. long.
Pipe may separate if not properly
joined.
Heat Shield Requirements for Horizontal Termination
For all horizontally vented appliances, a heat shield MUST
be placed 1 in. (25 mm) above the top of the vent between
the wall shield fi restop and the base of the termination cap.
There are two sections of the standard heat shield. One sec-
tion is factory-attached to the wall shield fi restop. The other
section is factory-attached to the cap. See Figure 3.1.
If the wall thickness does not allow the required 1-1/2 in.
(38 mm) heat shield overlap when installed, an extended
heat shield must be used.
Imporant Notice: Heat shields may NOT be field
constructed.
The extended heat shield may need to be cut to length. You
will attach the cut heat shield to the existing cap heat shield
or wall shield fi restop heat shield (refer to Figure 3.1) using
the supplied screws. You MUST maintain a 1-1/2 in. (38 mm)
overlap of the extended heat shield and the existing shields
(both ends of the heat shield). The small leg on the extended
heat shield should rest on the top of the vent (pipe section)
to properly space it from the pipe section.
26
Heatilator • ICON DV • 4042-300 Rev R • 06/07
Install the Horizontal Termination Cap
Vent termination must not be recessed in the wall. Siding
may be brought to the edge of the cap base.
Flash and seal as appropriate for siding material at outside
edges of cap.
When installing a horizontal termination cap, follow the cap
location guidelines as prescribed by current ANSI Z223.1
and CAN/CGA-B149 installation codes.
WARNING
Burn Risk
Local codes may require installation of a
cap shield to prevent anything or anyone
from touching the hot cap.
Heat Shield or
Extended
Heat Shield
Wall Shield Firestop
Inner Vent
Outer Vent
INTERIOR
Figure 8.12 Venting Through the Wall
Note: Where required, an exterior wall fl ashing is available.
When penetrating a brick wall, a brick extension kit is
available for framing the brick.
Heat Shield
1-1/2 in. (38 mm) min.
overlap
EXTERIOR
SHEATHING