2.2 Dry Mode

Dry mode operation is as follows
T
amb
unit fan runs and indoor unit fan runs at low speed.
T
amb
outdoor unit fan stop running.
T
set
compressor is running for continuous 6min, it will stop for another continuous 4min, which
will be circularly executed. The indoor unit fan runs at low speed.
33
≥T
+2C: Cooling mode will be entered. In that case, the compressor and outdoor
set
≤T
-2C: Cooling OFF status will be entered. In that case, the compressor and
set
-2C<T
<T
+2C: ON-OFF alternated status will be entered. In that case, after
amb
set
Dry Mode
Manual OFF
SiK401004_A
FUNCTION CONTROL