Electrical Data - Daikin RY24PEV1K Service Manual

Duct type
Table of Contents

Advertisement

4.2 Electrical Data

Model
FD(Y)M24PEV1K R(Y)24PEV1K
FD(Y)M30PEV1K R(Y) 30PEV1K
FD(Y)M36PEV1K R(Y)36PEY1K
FD(Y)M42PEV1K R(Y)42PEY1K
FD(Y)M48PEV1K R(Y)48PEY1k
Notes:
RLA: Rated load amperes
LRA: Locked rotor amperes
FLA: Full load amperes
27
Compressor
Power
Qty.
LRA
Supply
V,Ph,Hz
Each Each
1
66
220-240V
1PH 50Hz
1
76
1
53
380-415V
3PH
1
73
50Hz
1
73
Fan Motor
Supply
Condenser
RLA
Blower
Fan Motors
Motor
FLA
FLA
Each
Each
11.2
0.61
1.35
14.8
0.8
1.35
6.5
0.8
4.5
8.06
0.8
4.5
9.4
0.8
4.5
SiK401004_A
Max. Fuse
Min.
Breaker Size
Disconnect Size
(Indoor/Outdoor)
(Indoor/Outdoor)
Amps
Amps
6/25
2.5/14.6
6/25
2.5/19.3
10/20
5.7/9.1
10/25
5.7/10.2
10/25
5.7/11.1
SPECIFICATIONS

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents