Specification Of Power Supply Wire And Air Switch - Daikin RY24PEV1K Service Manual

Duct type
Table of Contents

Advertisement

SiK401004_A

4.3 Specification of Power Supply Wire and Air Switch

4.3.1 Outdoor Unit
RY24PEV1K
RY30PEV1K
RY30PEV1K
RY36PEY1K
RY42PEY1K
RY48PEY1K
4.3.2 Indoor Unit
 Duct Type
FD(Y)M24PEV1K
FD(Y)M30PEV1K
FD(Y)M36PEV1K
INSTALLATION
Power Supply
Model
(V, Ph, Hz)
220-240, 1, 50
R24PEV1K
220-240, 1, 50
380-415, 3, 50
R36PEY1K
380-415, 3, 50
R42PEY1K
380-415, 3, 50
R48PEY1K
Power Supply
Model
220-240, 1, 50
220-240, 1, 50
220-240, 1, 50
FD(Y)42PEV1K
220-240, 1, 50
FD(Y)48PEV1K
220-240, 1, 50
Capacity of
breaker
(A)
25
25
20
25
25
Capacity of
breaker
(V, Ph, Hz)
(A)
6
6
10
10
10
Minimum Sectional
Minimum Sectional
Area of Power
Area of Earth Wire
2
(mm
)
4.0
4.0
4.0
4.0
4.0
Minimum Sectional
Minimum Sectional
Area of Power
Area of Earth Wire
2
(mm
)
1.0
1.0
1.5
1.5
1.5
Supply Wire
2
(mm
)
4.0
4.0
4.0
4.0
4.0
Supply Wire
2
(mm
)
1.0
1.0
1.5
1.5
1.5