OTHER DAMAGE TO THE EQUIPMENT. BE SURE ONLY At delivery, the package should be checked and any damage should TO USE ACCESSORIES MADE BY DAIKIN WHICH ARE be reported immediately to the carrier claims agent. SPECIFICALLY DESIGNED FOR USE WITH THE...
In accordance with the foundation drawing in the figure, fix the ELECTING INSTALLATION SITE unit securely by means of the foundation bolts. (Prepare four sets of M12 foundation bolts, nuts and washers each which are available on the market.) Make sure to provide for adequate measures in order It is best to screw in the foundation bolts until their length are to prevent that the outdoor unit be used as a shelter 20 mm from the foundation surface.
Allowable pipe length Installation of refrigerant piping is possible as front connection, side connection and bottom connection. See the table below concerning lengths and heights. Refer to figures 2~5. Assume that the longest line in the figure corresponds with the actual longest pipe, and the highest unit in the figure corresponds with the actual highest unit.
In case of simultaneous operation system NOTE Refer to the table for stop valve tightening Upward and downward piping should be performed at the main torques. piping line. Be sure to use both a spanner and a torque Use branch piping kit (optional) for branching refrigerant pipes. wrench when connecting or disconnecting pipes Precautions to be taken.
Leak test Pair system: refer to figure 2 Evacuate the pipes and check vacuum. (No pressure increase for 1 minute.) L1 (m) one way length of liquid pipe Break the vacuum with a minimum of 2 bar of nitrogen. RP200 G=(L1–30)x0.06 Conduct leak test by applying soap water, etc.
LECTRICAL WIRING WORK EST OPERATION All wiring must be performed by an authorized electrician. For the test run procedure, refer to the indoor unit installation manual. All components procured on the site and all electric construction should comply with the applicable local and national codes. ISPOSAL REQUIREMENTS Be sure to use a dedicated power circuit.