Buderus Logano plus GB402 Installation And Maintenance Instructions Manual page 64

Table of Contents

Advertisement

10
Troubleshooting
Display
Fault
1)
Type
code
code
V
9Y
500
501
502
503
V
CY
566
V
CY
567
V
CO
568
V
CO
569
Tab. 21 Fault displays
1) V = interlocking; B = blocking
64
Cause
Description
Internal SAFe
Internal SAFe
relay faulty.
electronics faulty.
Return
The control unit
temperature
receives unrealistic
values from the
< -5 °C
return sensor.
(interruption).
Return
The control unit
temperature
receives unrealistic
values from the
> 130 °C
return sensor.
(short circuit).
Water
Water pressure
pressure
sensor interruption
sensor fault
(voltage > 3.5 V).
(cable break).
Water
Water pressure
pressure
sensor short circuit
sensor fault
(voltage < 0.5 V).
(short circuit).
Test procedure/cause
Press "Reset" and wait to
see if the fault has been
removed.
Check cabling between
SAFe and return sensor.
Check electrical
connection of the SAFe
cable.
Check resistance values of
temperature sensor
according to table.
Check voltage at the
temperature sensor
terminals inside the SAFe
according to table.
Check cabling between
SAFe and return sensor.
Check electrical
connection of the SAFe
cable.
Check resistance values of
temperature sensor
according to table.
Check voltage at the
temperature sensor
terminals inside the SAFe
according to table.
Check lead to water
pressure sensor.
Check water pressure
sensor.
Check lead to water
pressure sensor.
Check water pressure
sensor.
Logano plus GB402 - Subject to technical modifications!
Action
Replace the SAFe if the
fault persists after
"Reset" has been
pressed.
Replace cable if
required.
Remedy contact
problem if required.
Replace temperature
sensor if required.
Replace SAFe if
resistance values of the
temperature sensor are
correct, but voltage
values are incorrect.
Replace cable if
required.
Remedy contact
problem if required.
Replace temperature
sensor if required.
Replace SAFe if
resistance values of the
temperature sensor are
correct, but voltage
values are incorrect.
Remedy any
interruption.
Replace water pressure
sensor.
Remedy any short
circuit.
Replace water pressure
sensor.

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents