10
Troubleshooting
Display
Fault
1)
Type
code
code
V
4Y
523
V
4U
524
V
4A
575
B
5L
542
Tab. 21 Fault displays
1) V = interlocking; B = blocking
60
Cause
Description
Boiler
Temperature too
temperature
low at the boiler
sensor break.
temperature
sensor
(< -5 °C)
Boiler sensor
The boiler sensor
short circuit.
detected an
excessively high
temperature
(> 130 °C).
Intelligent high
The boiler flow
limit safety
temperature has
cut-out
reached its
responds.
maximum
permissible level.
Incomplete
The MC10
communication
generates this fault
with the SAFe.
if not all required
data is supplied by
the SAFe.
Test procedure/cause
Check the sensor lead.
Check the plug-in
connection.
Check sensor values
according to table.
Check the voltage at the
temperature sensor
according to table (SAFe
documentation).
Check the sensor lead.
Check the plug-in
connection.
Check sensor values
according to table.
Check the voltage at the
temperature sensor
according to table (SAFe
documentation).
The high limit safety cut-out
has responded.
Check the cabling between
the SAFe and the MC10.
Logano plus GB402 - Subject to technical modifications!
Action
Replace in case of
damage.
Clean or replace if
contaminated.
Replace in case of
damage.
Refit plug it is found to
be loose.
Replace the
temperature sensor in
case of deviations.
Replace the SAFe in
case of deviations.
Replace in case of
damage.
Clean or replace if
contaminated.
Replace in case of
damage.
Refit plug it is found to
be loose.
Replace the
temperature sensor in
case of deviations.
Replace the SAFe in
case of deviations.
Check gas valve.
(Does the flame
extinguish after a control
shutdown?)
Replace the SAFe if the
connections are OK.