SRX5800 Services Gateway Cabinet Requirements

Copyright © 2014, Juniper Networks, Inc.
Chapter 4: Preparing the Site for the SRX5800 Services Gateway Installation
Airflow must always be from front to back with respect to the rack. If the device has
side to rear airflow, then provisions must be made to ensure that fresh air from the
front of the rack is supplied to the inlets, and exhaust exits the rear of the rack. The
device must not interfere with the cooling of other systems in the rack. Fillers must be
used as appropriate in the rack to ensure there is no recirculation of heated exhaust
air back to the front of the rack. Care must also be taken around cables to ensure that
there is no leakage of air in situations where recirculation might result.
Figure 27: Chassis Dimensions and Clearance Requirements for the
Services Gateway
Overview of Installing the SRX5800 Services Gateway on page 47
SRX5800 Services Gateway Rack Size and Strength Requirements on page 51
Spacing of Rack-Mounting Bracket Holes for the SRX5800 Services Gateway on
page 52
Connection to Building Structure for the SRX5800 Services Gateway Rack on page 52
The services gateway can be installed in an enclosed cabinet. The cabinet requirements
are described in the following topics:
SRX5800 Services Gateway Cabinet Size and Clearance Requirements on page 54
SRX5800 Services Gateway Cabinet Airflow Requirements on page 54
53