Connecting The Electrical Power - Getinge 600 Series Installation Manual

Steam sterilizers
Hide thumbs Also See for 600 Series:
Table of Contents

Advertisement

Optional Equipment
CONNECTING THE ELECTRICAL
POWER
5–14
To connect the single-phase supply to the booster pump junction box:
1. Connect the booster pump junction box to the booster pump as shown
in Figure 5–12 on page 5–15.
CAUTION
Route the cord so that it does not touch any hot steam lines or sterilizer
surfaces.
2. Connect the cords from the booster pump interface box to the sterilizer
control box.
a. Disconnect the cord from 6JO on the back of the control box (that
goes to solenoid valve 6SV) and connect it to 11A2J on the booster
pump interface box.
b. Using the cord provided (P/N 61311601245), connect 11A1J on the
junction box to 2A6JO on the control box.
3. Connect the electrical supply (provided by the customer) to the booster
pump interface box as follows:
a. Connect Line (L) to 1K relay terminal 1 (L1).
b. Connect Neutral (N) to 1k relay terminal 3 (L2).
c. Connect Protective Earth Ground (G) to the PE Ground screw
inside the box.
4. Install the overload relay inside the interface box and connect the wires
as shown in Figure 5–12 on page 5–15.
5. Set the overload relay current adjustment to match the current
stamped on the rating plate.