Discharge Pipe Temperature Control - Daikin FTKN09NMVJU Service Manual

Inverter pair wall mounted type ftk(x)n-n, ftk(x)-n series
Hide thumbs Also See for FTKN09NMVJU:
Table of Contents

Advertisement

Troubleshooting

4.15 Discharge Pipe Temperature Control

F3
Error Code
Method of Error
An error is determined with the temperature detected by the discharge pipe thermistor.
Detection
Error Decision
Conditions
09/12 class, RKN18NMVJU
RXN18NMVJU, RK(X)18NMVJU, 24 class
Supposed
Causes
Troubleshooting
Check No.01
Refer to P.91
Check No.12
Refer to P.93
Check No.14
Refer to P.94
79
If the temperature detected by the discharge pipe thermistor rises above A, the compressor
stops.
The error is cleared when the discharge pipe temperature has dropped below B.
A
°C
°F
110
230
If the frequency drops, the temperature is lowered in compensation.
A
°C
°F
110
230
If the error repeats, the system is shut down.
Reset condition: Continuous run for about 60 minutes without any other error
Defective discharge pipe thermistor
(Defective outdoor heat exchanger thermistor or outdoor temperature thermistor)
Defective electronic expansion valve or coil
Refrigerant shortage
Defective four way valve
Water mixed in refrigerant
Defective stop valve
Defective outdoor unit PCB
Be sure to turn off the power switch before connecting or disconnecting
Caution
connectors, or parts may be damaged.
Check No. 01
Check the thermistors.
OK
Check No. 12
Check the electronic
expansion valve.
OK
Check No. 14
Check the refrigerant line.
OK
B
°C
°F
88
190.4
B
°C
°F
95
203
NG
Discharge pipe thermistor
Outdoor heat exchanger thermistor
Outdoor temperature thermistor
NG
NG
Refrigerant shortage
Four way valve
Water mixed
Stop valve
SiUS041501E
Replace the
defective
thermistor(s).
Replace the electronic
expansion valve or the coil.
Refer to the refrigerant line
check procedure.
Replace the outdoor unit
PCB (main PCB).
(R20417)
Service Diagnosis