Daikin FTKN09NMVJU Service Manual page 75

Inverter pair wall mounted type ftk(x)n-n, ftk(x)-n series
Hide thumbs Also See for FTKN09NMVJU:
Table of Contents

Advertisement

SiUS041501E
Troubleshooting
Turn off the power supply.
Check No.03
(Unplug the power cable or turn
the breaker off.)
Refer to P.92
Check the connector for
connection.
Check No. 03
Check the fan motor for
breakdown or short circuit.
Check No. 03
Check the motor control voltage.
Check No. 03
Check the indoor unit PCB for
rotation pulse.
Service Diagnosis
Be sure to turn off the power switch before connecting or disconnecting
Caution
connectors, or parts may be damaged.
NO
OK?
YES
YES
Foreign matters in or
around the fan?
NO
Rotate the fan by hand.
NO
Fan rotates smoothly?
YES
Resistance OK?
YES
Turn the power on again.
NO
Is the motor control
voltage 15 VDC
generated?
YES
NO
Is the rotation pulse
generated?
YES
Note: The motor may break when the
motor connector is disconnected
with the power supply on.
(Turn off the power supply before
connecting the connector also.)
∗ To secure the connection,
once disconnect the connector
and then reconnect it.
Abnormal
sound occurs?
YES
Bearing
rubber
cushion
Is the rubber cushion
properly fitted?
NO
NO
Troubleshooting
Correct the connection.
Remove the foreign matters.
NO
Rubber
cushion
YES
Replace the bearing rubber
cushion.
Correct the position of
rubber cushion or replace
the rubber cushion.
Replace the indoor fan motor.
Replace the indoor unit PCB
(control PCB).
Replace the indoor fan motor.
Replace the indoor unit PCB
(control PCB).
(R20165)
64