Control Specification
3.4

Discharge Pipe Temperature Control

Outline
The discharge pipe temperature is used as the internal temperature of the compressor. If the
discharge pipe temperature rises above a certain level, the upper limit of frequency is set to keep
the discharge pipe temperature from rising further.
Detail
39
B
C
D
Discharge pipe
temperature
Zone
Stop zone
When the temperature reaches the stop zone, the compressor stops.
Dropping zone
The upper limit of frequency decreases.
Keep zone
The upper limit of frequency is kept.
Up zone
The upper limit of frequency increases.
Reset zone
The upper limit of frequency is canceled.
09/12 class
RKN18NMVJU
(°C)
(°F)
A
110
230.0
B
103
217.4
C
98
208.4
D
93
199.4
E
88
190.4
Control
RXN18NMVJU
RK(X)18NMVJU
24 class
(°C)
(°F)
110
230.0
103
217.4
101.5
214.7
100
212.0
95
203.0
SiUS041501E
Stop zone
A
Dropping zone
Keep zone
Up zone
E
Reset zone
(R14722)
Function and Control