Section 3-3-3: Heat Shields - Montigo P38DFNI Installation & Maintenance Manual

P series residential fireplace
Table of Contents

Advertisement

Section 3-3-3: Heat Shields

Installing a Wall Mounted RHS8 Heat shield
The RHS8 Heat shield CANNOT be used when the Termination is WITHIN
(36" Min. horizontal and 60" Min. vertical) from the fireplace, or directly
off the rear of the fireplace, as shown figure 17a. The RHS101 Heat
Shield (Figure 18c and 18d) MUST be used within the noted dimensions.
To install the RHS8, frame an opening in combustible construction,
Figure 17 below. Slide the Heat shield in place over the vent pipe
which attaches to the fireplace. After the fireplace and vent pipe has
been installed, clearances should match the dimensions in Figure 17a.
1" Min.
Figure 17.
RHS8 Installation. (Install by sliding over vent pipe where it passes
through the combustible construction).
36" Min
60" Min.
Figure 17a.
RHS8 Installation. (Minimum requirements).
Note: Images are shown without screens for clarity purposes. However,
your fireplace should not be operated without proper installation of
screens.
XG0193 -150204.1
Installation
1" Min. Both sides Typical
RHS8 Heat Shield
Combustible Framing
RHS8 Heat
Shield
PTO Termination
Installing a Wall Mounted RHS101 Heat shield.
The RHS101 Heat shield MUST be used where the RHS8 Termination
(Figure 17 and 17a) CANNOT be used. Use the RHS101 where any
of the dimensions are within the parameters shown, figure 17a.
To install the RHS101, Slide the Inner Section over the vent pipe that
will connect to the fireplace. Then fasten the vent pipe to the back of the
fireplace with a minimum of three sheet metal screws. From the outside
slide the RHS101 outer section on see Figure 18. To complete the
installation fasten the Heat Shield Outer Section & Termination frame
to the structure Figure 18a.
RHS101 Heat Shield
Outer Section
Termination
Figure 18. RHS101 Installation. (Install by sliding Outer Section over vent pipe
where it passes through the combustible construction.
RHS101 Heat Shield
Outer Section
Termination
Figure 18a. RHS101 Heat Shield after sliding the outer section in place.
3/8" Min.
Figure 18b.
RHS101 Installation.
P38DF* Indoor Gas Fireplace
Drywall / sheetrock
RHS101 Heat Shield, inner Section
Vent pipe, from fireplace
Combustible
framing
Drywall / sheetrock
RHS101 Heat Shield, inner Section
3/8" Min. Both sides Typical
Inner Shield 9 3/8"
Outer Shield 10 1/4"
Combustible Framing
12" x 12"
Page 17

Advertisement

Table of Contents
loading

This manual is also suitable for:

P38dfliP38dfl

Table of Contents