Unit Mode Priority

The UVC uses the network variables and binary inputs listed in Table 10 and Table 11
to determine the current unit mode. Special purpose UVC unit modes have higher prior-
ity than the normal UVC unit modes as shown in the tables.
Each table lists the highest priority items on the left to the lower priority items to the
right. The right-most columns indicate unit operation as a result of the left-most col-
umns. Certain inputs will be ignored when another network variable or binary input with
a higher priority has a specific input value.
Table 10: Special purpose UVC unit mode priority
Remote shut-
Emergency
down binary
override input 1
input
De-energized 4
Normal 3
Energized 5
Pressurize
Ignored
De-pressurize
Ignored
Purge
Ignored
Shutdown
Ignored
1. Network input.
2. Network output.
3. Normal indicates the UVC power-up condition.
4. De-energized indicates that the contacts connected to this binary input are open.
5. Energized indicates that the contacts connected to this binary input are closed.
Table 11: Normal UVC mode priority
Application override input 1
Normal (Auto) 3
Heat
Cool
Night purge
Off
Emergency heat
Fan only
1. Network input.
2. Network output.
3. Normal (Auto) is the normal UVC power-up state.
Energy hold off
Energy hold off
input 1
output 2
Normal
Normal
Energy hold off
Energy hold off
Ignored
Energy hold off
Ignored
Ignored
Ignored
Ignored
Ignored
Ignored
Ignored
Ignored
Unit mode override input 1
Normal (Auto) 3
Heat
Cool
Night purge
Off
Emergency heat
Fan only
Ignored
Ignored
Ignored
Ignored
Ignored
Ignored
23
d
o
esCrIptIon of
peratIon
Priority result
Unit mode
Actual UVC
output 2
action
See the normal UVC mode priority
(Table
11)
Off
Off
Off
Off
Off
Pressurize
Off
De-pressurize
Off
Purge
Off
Off
Priority result
Unit mode output 2
Heat
Cool
Emergency heat
Heat
Cool
Night purge
Off
Emergency heat
Fan only
Heat
Cool
Night purge
Off
Emergency heat
Fan only
OM 752-4