UVC Configuration Parameters

The UVC is been provided with a number of configuration variables as listed in the following table. These configuration
variables are stored in UVC non-volatile memory. For a description of supported network variables for each protocol,
refer to Protocol Data Packet bulletin ED 15065.
Table 25: UVC configuration parameters (OM 752)
Configuration Parameter Name
Occupied Cooling Setpoint
Standby Cooling Setpoint
Unoccupied Cooling Setpoint
Occupied Heating Setpoint
Standby Heating Setpoint
Unoccupied Heating Setpoint
Local Bypass Time
Space CO 2 Setpoint 2
Emergency Heat Enable
Emergency Heat Setpoint
Emergency Heat Shutdown Configuration
Wall Sensor Type
Slave Type Configuration.
OAD Min Position High-Speed Setpoint
OAD Min Position Med-Speed Setpoint
OAD Min Position Low-Speed Setpoint
Exhaust Interlock OAD Min Position
Setpoint
Energize Exhaust Fan OAD Setpoint
OAD Max Position Setpoint
OAD Lockout Enable
OAD Lockout Setpoint
Economizer Enable
Economizer OA Temp Setpoint
Economizer IA/OA Temp Differential
Economizer OA Enthalpy Setpoint
OM 752-4
Table 24: CO 2 versus voltage table
CO 2 (PPM)
VDC (V)
300
1.5
400
2.0
500
2.5
600
3.0
700
3.5
800
4.0
900
4.5
1000
5.0
Abr.
OCS
SCS
UCS
OHS
SHS
UHS
Tenant override
CO 2 S
0 = disable, 1 = enable
EHS
0 = no emergency heat during shutdown, 1 = emergency heat available during
shutdown
0 = +/- 3°F, 1 = 55°F to 85°F
0 = independent slave, 1 = dependent slave
(this variable will be factory set to 5% open when the unit is ordered with optional
OADH
CO 2 DCV)
OADM
(this variable is ignored when the unit is ordered with optional CO 2 DCV)
OADL
(this variable is ignored when the unit is ordered with optional CO 2 DCV)
EOAD
OA damper minimum position when the exhaust interlock input is energized
OADE
defines position above which exhaust fan output will be energized
OAMX
0 = disable, 1 = enable (this variable will be factory set to 1 when the unit is
ordered as a recirc unit with no OAD)
OA temperature below which the OA damper will remain closed (this variable will
OALS
be factory set to –99°C when the unit is ordered as a recirc unit with no OAD)
0 = disable, 1 = enable
ETS
ETD
EES
CO 2 (PPM)
1200
1300
1400
1500
1600
1700
1800
1900
Notes
42
d
IaGnostICs and
VDC (V)
6.0
6.5
7.0
7.5
8.0
8.5
9.0
9.5
Default
73°F (23°C)
77°F (25°C)
82°F (28°C)
70°F (21°C)
66°F (19°C)
61°F (16°C)
120 min
1200 PPM
1
54°F (12°C)
0
0
0
20% open
25% open
30% open
99% open
12% open
99% open
0
36°F (2°C)
1
68°F (20°C)
2°F (1°C)
25 btu/lb (58 kJ/
kg)