Daikin MicroTech II Operation And Maintenance Manual page 12

Used with daikin classroom unit ventilator model avv - floor-mounted, model ahv - ceiling-mounted
Table of Contents

Advertisement

Keypad menu
Display
item list
Exhaust Interlock OAD
EOAD
x5
Min Position set point
Energize Exhaust Fan
OADE Adjust OA damper minimum position when the exhaust interlock input is energized.
x6
OAD Set point
OAD Max Position Set
OAMX Adjust OA damper maximum position.
x7
point
OAD Lockout Enable
x8
OAD Lockout Set
x9
point
Economizer Enable
e1
Economizer OA Temp
e2
Set point
Economizer IA/OA
e3
Temp Differential
Economizer OA En-
e5
thalpy Set point
Economizer IA/OA
e6
Enthalpy Differential
Space Humidity Output
r1
Outdoor Air Humidity
EORH Display OA humidity (optional). 00 = No sensor connected.
r3
Output
Outdoor Air Temp Output EOAT Display OA temperature.
xt
Emergency Heat Enable
h1
Emergency Heat
h2
Set point
Emergency Heat Shut-
h3
down Configuration
External BI-3 Configu-
b3
ration
Fan Cycling
cf
Configuration
Filter Alarm Enable
ce
Reset Filter Alarm Input
cr
Space Temp Sensor
sp
Offset
Keypad/display
un
Temperature Units
1. RW = read and write capable, RO = read only.
2. If a menu value is greater than 2-digits (higher than 99), then
OM 752-4
Abr.
Adjust OA damper position above which the exhaust fan output will be energized. There is a fixed –5%
differential associated with this set point.
Set OA damper lockout feature status: 0 = disable, 1 = enable. (This variable is factory set to 1 when
the unit is ordered as a recirc unit with no OAD.)
Adjust OA temperature below which the OA damper closes if the OA damper lockout is enabled. (This
OALS
variable is factory set to –99°C when the unit is ordered as a recirc unit with no OAD.)
Set economizer status: 0 = disable, 1 = enable.
Adjust economizer OA temperature set point. DO NOT lower this set point below CCLO or you risk
ETS
creating a deadband where no cooling occurs.
ETD
Adjust economizer IA/OA temperature differential.
EES
Adjust economizer OA enthalpy set point.
EED Adjust economizer IA/OA enthalpy differential.
ERH Display room humidity (optional). 00 = No sensor connected.
Set emergency heat status: 0 = disable, 1 = enable.
EHS Adjust emergency heat set point.
Set emergency heat operation during shutdown, 0 = no emergency heat during shutdown: 1 = allow
emergency heat during shutdown.
Set the function external binary Input 3: 0 = ventilation lockout, 1 = exhaust interlock.
Set space fan cycles (switches off) during occupied, bypass, and standby mode: 2 = continuous, 3 =
cycling.
Set filter alarm status: 0 = disable, 1 = enable.
Enter 1 to clear filter alarm.
Adjust this setting to bias the UVC measured space temperature.
Set keypad/display temperature units in English or SI. This set point also effects which unit types dis-
played over Metasys N2 and BACnet MS/TP networks using the appropriate optional communications
modules.
will be displayed on the keypad/display.
Description
12
G
s
ettInG
tarted
RO
06
Default
RW 1
RW
x
99%
RW
x
12%
RW
x
99%
RW
x
0
35.6°F
RW
x
(2°C)
RW
x
1
68°F
RW
x
(20°C)
1.8°F
RW
x
(1°C)
25 Btu/lb
RW
x
(58 kJ/kg)
1.3 Btu/lb
RW
x
(3 kJ/kg)
RO
x
RO
x
RO
x
RW
x
1
53.6°F
RW
x
(12°C)
RW
x
0
RW
x
0
RW
x
2
RW
x
0
2
RW
x
RW
x
0
RW
x
F