Solar Control Module, Type Sm1 - Viessmann VITODENS 200-W Technical Manual

Gas condensing boilers 17.0 to 150.0 kw as multi boiler system up to 900.0 kw
Table of Contents

Advertisement

Control units
(cont.)

Solar control module, type SM1

Part no. 7429 073
Specification
Construction
The solar control module contains:
■ PCB
■ Terminals:
– 4 sensors
– Solar circuit pump
– KM BUS
– Power supply (on-site ON/OFF switch)
■ PWM output for controlling the solar circuit pump
■ 1 relay for switching a pump or a valve
Collector temperature sensor
For connection inside the appliance.
On-site extension of the connecting lead:
■ 2-core lead, length up to 60 m with a cross-section of 1.5 mm
per)
■ Never route this lead immediately next to 230/400 V cables
Lead length
IP rating
Sensor type
Permissible ambient temperature
– during operation
– during storage and transport
Cylinder temperature sensor
For connection inside the appliance.
On-site extension of the connecting lead:
■ 2-core lead, length max. 60 m with a cross-section of 1.5 mm
5
per)
■ Never route this lead immediately next to 230/400 V cables
Lead length
IP rating
Sensor type
Permissible ambient temperature
– during operation
– during storage and transport
For systems with Viessmann DHW cylinders, the cylinder temperature
sensor is installed in the threaded elbow (standard delivery or acces-
sory for the respective DHW cylinder) in the heating water return.
Functions
■ Switching the solar circuit pump
■ Solar circuit pump speed control via wave packet control or solar
circuit pump with PWM input (Grundfos)
VIESMANN
66
■ Electronic limiter for the temperature in the DHW cylinder (safety
■ Collector safety shutdown
■ Switching an additional pump or valve via relay
■ Central heating backup is controlled in conjunction with a multi mode
■ Second differential temperature control, thermostat function or aux-
■ Suppression of DHW cylinder reheating by the boiler
■ Suppression of reheating by the boiler with central heating backup
■ Output statement and diagnostic system
The immersion temperature sensor, part no. 7438 702 is required if
the following functions should be realised:
■ Transfer for systems with two DHW cylinders
■ Return changeover between the boiler and the heating water buffer
2
Specification
(cop-
2.5 m
IP 32 to EN 60529; ensure
through design/installation
Viessmann NTC 20 kΩ at
25 °C
−20 to +200 °C
−20 to +70 °C
2
(cop-
Rated voltage
Rated frequency
3.75 m
Rated current
IP 32 to EN 60529; ensure
Power consumption
through design/installation
Safety category
Viessmann NTC 10 kΩ at
IP rating
25 °C
Function
0 to +90 °C
Permissible ambient temperature
−20 to +70 °C
– during operation
– during storage and transport
Rated relay output breaking capaci-
ty
– Semi-conductor relay 1
– Relay 2
– Total
shutdown at 90 °C)
heating water buffer cylinder
iliary function for DHW heating
or
cylinder
0
1 8
5 8
230 V~
50 Hz
2 A
1.5 W
I
IP 20 to EN 60529; ensure
through design/installation
Type 1 B to EN 60730-1
0 to +40 °C use in the living
space or boiler room (standard
ambient conditions)
−20 to +65 °C
1 (1) A, 230 V~
1 (1) A, 230 V~
max. 2 A
VITODENS 200-W