45 and 60 kw wall mounted gas fired condensing boiler natural gas and lpg version (20 pages)
Summary of Contents for Viessmann VITODENS 200-W
Page 1
VIESMANN VITODENS 200-W Gas condensing boiler 12.0 to 150.0 kW As multi boiler system up to 900.0 kW Technical guide VITODENS 200-W Type B2HA Wall mounted gas condensing boiler With modulating MatriX cylinder burner for natural gas and For open flue or room sealed operation...
Vitodens 200-W 1.1 Product description Vitodens 200-W, 45 to 60 kW A Inox-Radial heat exchanger made from stainless steel – for high operational reliability and a long service life. Large heating output on a very small footprint B Modulating MatriX cylinder burner for extremely clean combustion...
Page 5
Vitodens 200-W (cont.) Vitodens 200-W, 80 to 100 kW A Inox-Radial heat exchanger made from stainless steel – for high operational reliability and a long service life. Large heating output on a very small footprint B Modulating MatriX cylinder burner for extremely clean combustion...
Page 6
Delivered condition especially suitable for installation in apartment buildings and commer- cial or public buildings. For these, the Vitodens 200-W offers an afford- Wall mounted gas condensing boiler with Inox-Radial heat exchanger, able, space-saving solution – either as a single unit up to 150 kW or...
Vitodens 200-W (cont.) 1.2 Specification Gas boiler, type B and C, category II Gas condensing boiler 2N3P Rated heating output range 45 and 60 kW: Specification to EN 677. 80 to 150 kW: Specification to EN 15417. = 50/30 °C when operating with natural gas 12.0 -...
Flue gas connection Ø mm Ventilation air connection Ø mm Vitodens 200-W, 45 and 60 kW Multi boiler systems For further details regarding multi boiler systems, see page 34. Calculation values for sizing the flue system to EN 13384. Flue gas temperatures as actual gross values at 20 °C combustion air temperature.
Page 9
Vitodens 200-W (cont.) A Expansion vessel connection G 1 K Connection sets (accessories) B Safety valve Shown without thermal insulation (standard delivery) L Without connection sets C Heating flow G 1½ M With connection sets D Cylinder flow G 1½...
Page 10
Vitodens 200-W (cont.) Residual head of the circulation pump 1200 1100 1000 1000 2000 3000 4000 Flow rate in l/h Curve Pump rate, circulation pump 40 % 50 % 60 % 70 % 80 % 90 % 100 % Pressure drop on the heating water side...
Page 11
Vitodens 200-W (cont.) Circulation pump head 1000 1500 2000 Pump rate in l/h A Stage 1 B Stage 2 C Stage 3 Note When the heating circuit and circulation pumps are operated in parallel for cylinder heating (no DHW priority control), we recommend the installation of a DHW cylinder in the secondary side (downstream from the low loss header) of the heating system.
Vitodens 200-W (cont.) Vitodens 200-W, 80 and 100 kW Multi boiler systems For further details regarding multi boiler systems, see page 34. A Safety valve K Cable entry area at the back B Expansion vessel connection G1 L Without connection set (accessories)
Vitodens 200-W (cont.) Vitodens 200-W, 125 and 150 kW Multi boiler systems For further details regarding multi boiler systems, see page 34. 165,5 165,5 A Safety valve K Cable entry area at the back B Expansion vessel connection G1 L Without connection set (accessories)
Page 15
Vitodens 200-W (cont.) Circulation pump VI Para 30/1-12 Rated voltage Power consumption Max. Min. Variable speed (Δp constant or Δp variable), fully wired. Note For operation in multi boiler systems select speed control Δp con- stant. Residual head of the circulation pump...
Page 16
Vitodens 200-W (cont.) Note Observe information regarding the use of a low loss header (see page 47). If the residual head of the circulation pump available as an accessory is insufficient to overcome the following system pressure drop values, install an additional, external circulation pump on site.
Installation accessories 2.1 Product description Installation accessories for the Vitodens 200-W, 45 and 60 kW Heating circuit connection set without circulation pump DHW cylinder connection set Part no. 7245 738 Part no. ZK00 657 Connections G 1½ Connections G 1½...
Installation accessories (cont.) Installation accessories for the Vitodens 200-W, 80 and 100 kW Heating circuit connection set with variable speed high efficiency circulation pump Part no. 7501 318 Comprising: ■ Circulation pump ■ 2 ball valves with adaptors Ø 42 mm (locking ring fitting) ■...
Page 19
Connections: Ø 42 mm (locking ring fitting) Components: Comprising: ■ Casing with integrated CO sensor, relay and displays for operation ■ Connecting lines for flow and return and alarm. ■ Fittings ■ Fixing materials. ■ Cylinder temperature sensor VIESMANN VITODENS 200-W...
■ Individually wall mounted or with a double or triple manifold. ■ Also available as a kit. For further details see the Viessmann pricel- ist. For part numbers in conjunction with the different circulation pumps, see the Viessmann pricelist.
Page 21
Specific thermal capacity ´ = = 665 0.665 µ Mass flow rate c · ΔT 1.163 Wh · (75-60) K ² Heating output ´ Flow rate Select the smallest possible mixer within the application limit with the value ´. VIESMANN VITODENS 200-W...
Page 22
0.5 1.0 1.5 2.0 2.5 3.0 3.5 Flow rate in m³/h A Divicon R ¾ with mixer B Divicon R 1 with mixer C Divicon R ¾ and R 1 without mixer VIESMANN VITODENS 200-W...
Page 23
Bypass valve Flow rate in m³/h Part no. 7464 889 For hydraulic balancing of the heating circuit with mixer. To be inserted into the Divicon. A Divicon R 1¼ with mixer B Divicon R 1¼ without mixer VIESMANN VITODENS 200-W...
Page 24
A Connection option for expansion vessel HV Heating water flow HR Heating water return Part no. 7466 337 for Divicon R 1¼. G 1½ G 1½ Rp ¾ A Connection option for expansion vessel HV Heating water flow HR Heating water return VIESMANN VITODENS 200-W...
Page 25
Part no. 7465 894 Part no. 7465 439 For individual Divicon. For manifold. With screws and rawl plugs. With screws and rawl plugs. For Divicon With mixer Without mixer For Divicon R ¾ and R 1 R 1¼ VIESMANN VITODENS 200-W...
With thermal insulation and integral sensor well. The connection between boiler and low loss header must be made on site. Pressure drop Flow rate in m³/h Rp 2 Installation accessories for multi boiler systems Hydraulic cascades See page 34. VIESMANN VITODENS 200-W...
Page 27
(cont.) Flue gas cascade (positive pressure) ■ 4-boiler system installed in series – For the Vitodens 200-W, 45 and 60 kW: Part no. ZK00 681 Comprising: – For the Vitodens 200-W, 80 to 100 kW: Part no. ZK00 682 ■ Flue gas header –...
The surface temperatures of the Vitodens and the flue system never locally applicable standards. exceed 85 ºC. Vitodens 200-W from 60 kW and multi boiler systems Extractors Install boilers from 50 kW in accordance with the Combustion Order When installing appliances with extraction to the outside (cooker (FeuVo) [Germany] [or local regulations] in a separate installation hoods, extractor fans etc.), ensure that air extraction will not create...
When installing the Vitodens in wet areas, observe the safety zones IP X 4D, splashproof) and minimum wall clearances according to VDE 0100 [or local regu- lations]. The Vitodens 200-W may be installed in safety zone 1. Electrical connection The power supply must comply with the requirements of your local power supply utility and current VDE [or local] regulations (a: ÖVE...
Design information (cont.) Vitodens 200-W, 125 to 150 kW A Reference point Vitodens top edge B Area for power cables Recommended leads/cables NYM 3 G 1.5 mm 2-core min. 0.75 mm 4-core 1.5 mm 3-core 1.5 mm without green/yellow wire –...
Vitodens. Installing the Vitodens 200-W, 45 to 100 kW directly onto a wall (single boiler) The enclosed screws and rawl plugs are only suitable for concrete. For other construction materials, use fixing materials that are suitable for 100 kg loads.
The Vitodens can be mounted on the self-supporting mounting frame. Installing the Vitodens 200-W, 125 to 150 kW directly onto a wall (single boiler) The enclosed screws and rawl plugs are only suitable for concrete. For The mounting frame (accessories) is recommended for installing the other construction materials, use fixing materials that are suitable for Vitodens (see page 34).
Page 33
Ø 12 A Reference point Vitodens top edge C Top edge finished floor B Area for power cables. D Recommended dimension: 1975 mm Allow cables to protrude approx. 1200 mm from the wall. E Wall mounting bracket VIESMANN VITODENS 200-W...
2 to 8 boilers in series or 4 to 8 boilers arranged in a Order the low loss header or the heating circuit connecting kit as sep- block formation. Heating circuit connections can be either on the right arate accessories. or left. VIESMANN VITODENS 200-W...
Page 36
Max. flow rate 13.8 24.1 36.2 27.6 48.2 Dimensions 1044 1044 1044 1044 2220 2335 2917 3382 3497 – – – – – m mm – – – – – Installation in corners, with a low loss header VIESMANN VITODENS 200-W...
Page 37
For corner installation of multi boiler system and low loss header ■ 2 pipe bends ■ DN 65 ■ Thermal insulation Part no. 7164 976 ■ DN 80 Part no. 7164 977 ■ DN 100 Part no. 7164 978 VIESMANN VITODENS 200-W...
Page 39
■ Connection lines for hydraulic cascades with Rp ½ connections for Part no. 7453 093 safety and control equipment ■ DN 80 ■ Thermal insulation Part no. 7453 094 ■ DN 100 Part no. 7453 095 Corner installation of multi boiler system and heating circuit connecting kit VIESMANN VITODENS 200-W...
Page 40
For corner installation of multi boiler system and heating circuit con- ■ 2 pipe bends necting kit ■ Thermal insulation ■ DN 65 Part no. 7164 976 ■ DN 80 Part no. 7164 977 ■ DN 100 Part no. 7164 978 VIESMANN VITODENS 200-W...
Page 42
6x150 kW Multi boiler system standard delivery Accessories (subject to order) ■ Vitodens 200-W (2 to 8 boilers) ■ Low loss header with connection lines and thermal insulation ■ Cascade control unit Vitotronic 300-K ■ Cascade communication module for each boiler ■...
1422 Multi boiler system standard delivery Accessories (subject to order) ■ Vitodens 200-W (4 to 8 boilers) ■ Low loss header with connection lines and thermal insulation ■ Cascade control unit Vitotronic 300-K ■ Cascade communication module for each boiler ■...
■ PP pipes one fill may last longer than one year. ■ ABS/ASA pipes ■ Stainless steel pipes Neutralising system for single boiler systems with 45 and 60 kW ■ Borosilicate pipes Part no. 9535 742 DN 40 VIESMANN VITODENS 200-W...
Page 45
■ Two 7 24 mm connection apertures for condensate inlet The standard delivery comprises: ■ 6 m long drain hose 7 14 x 2 mm ■ Non-return valve A Condensate inlet B Condensate inlet with drain plug C Condensate drain VIESMANN VITODENS 200-W...
Installation examples Attic heating centre For installation examples for the Vitodens 200-W, see "System exam- The installation of a low water indicator specified as compulsory to EN ples". 12828 is not required when installing the Vitodens in an attic heating centre.
For this, order the low loss header that is available as an ■ Provide air vent valves (e.g. quick-action air vent valves) on the pri- accessory. See page 34 and the Viessmann pricelist. mary side (boiler side) and the secondary side (heating circuit side) Losses resulting from the use of third party low loss headers are exclu- of the plate heat exchanger.
Low loss header with distributor/manifold for multi boiler sys- Low loss header in conjunction with Divicon heating circuit dis- tems with Vitodens 200-W tributor For description and specification, see page 34. For description and specification, see page 20.
– Boiler water temperature and built into the boiler. – DHW temperature – Operating program Specification – Codes Sensor type Viessmann NTC, 10 kΩ at – Actuator tests 25 °C – Test mode Permissible ambient temperature ■ Displaying: – during operation 0 to +130 °C...
To reduce the heat-up output, the reduced room temperature will – Test mode be raised in case of low outside temperatures. The flow temperature will be raised for a limited time to reduce the heat-up time after a set- back phase. VIESMANN VITODENS 200-W...
Page 51
■ Standby mode External heating program changeover in conjunction with EA1 exten- Specification sion. Sensor type Viessmann NTC, 10 kΩ at 25 °C Frost protection function Permissible ambient temperature ■ The frost protection function will be started when the outside tem- –...
–13 to 40 K 5.3 Vitotronic 300-K, type MW2B for multi boiler systems Cascade control unit for the Vitodens 200-W with a Vitotronic 100 Weather-compensated, digital cascade and heating circuit control ■ With cylinder temperature controller or control unit of a primary store...
Page 53
– Flow temperature ■ Weather-compensated control of the system/boiler water tempera- – DHW temperature ture in a multi boiler system with Vitodens 200-W with Vitotronic 100, – Information type HC1B (modulating) and the flow temperature of the heating cir- – Operating data cuits with mixers –...
The flow temperature required to reach a specific room temperature Sensor type Viessmann NTC 10 kΩ, at depends on the heating system and the thermal insulation of the build- 25 °C ing to be heated.
Wireless outside temperature sensor Wireless repeater Room temperature sensor for Vitotrol 300A Immersion temperature sensor Mounting base for programming unit Radio clock receiver KM BUS distributor Extension kit for one heating circuit with mixer with integral mixer mo- VIESMANN VITODENS 200-W...
– Constant manual mode with adjustable set room temperature ■ With switching output (two-point output) – Frost protection mode ■ With digital time switch – Holiday program ■ With individual and 7-day programs ■ With selector keys for party and economy mode VIESMANN VITODENS 200-W...
(e.g. direct sunlight, fireplace, TV set, etc.). Room temperature controller operation independent of mains power supply (two 1.5 V round alkaline batteries, type LR6/AA, which run for approx.1.5 years). Receiver with relay state indication. VIESMANN VITODENS 200-W...
■ 2-core lead, length max. 50 m (even if connecting several remote ■ Integral room temperature sensor for room temperature hook-up control units) (only for one heating circuit with mixer) ■ Never route this lead immediately next to 230/400 V cables ■ LV plug as standard delivery VIESMANN VITODENS 200-W...
Note The Vitotrol 200 RF can regulate one heating circuit; the The wireless remote controls cannot be combined with hardwired Vitotrol 300 RF up to 3 heating circuits. remote control units. VIESMANN VITODENS 200-W...
■ Integral room temperature sensor Note Observe the "Wireless accessories" technical guide. Standard delivery: ■ Vitotrol 300 RF ■ Table-top dock ■ Plug-in power supply unit ■ 2 rechargeable NiMH batteries for operating outside the table-top dock VIESMANN VITODENS 200-W...
IP rating IP 30 to EN 60529; ensure through design/installation Permissible ambient temperature – Operation 0 to +40 °C – Storage and transport −25 to +60 °C Setting range for set room temperature 3 to 37 °C VIESMANN VITODENS 200-W...
Wireless, light-activated outside temperature sensor with integral wire- ■ 2 to 2.5 m above the ground, for multi storey buildings in the upper less transmitter for operation with the wireless base station and the half of the second floor Vitotronic control unit. VIESMANN VITODENS 200-W...
■ Never route this lead immediately next to 230/400 V cables Specification Safety category IP rating IP 30 to EN 60529; ensure through design/installation Sensor type Viessmann NTC 10 kΩ at 25 °C Permissible ambient temperature – Operation 0 to +40 °C – Storage and transport −20 to +65 °C...
Cable length 5.8 m, fully wired IP rating IP 32 to EN 60529; ensure through design/installation Sensor type Viessmann NTC 10 kΩ, at 25 °C Permissible ambient temperature – Operation 0 to +90 °C – Storage and transport −20 to +70 °C Mounting base for programming unit Part no.
KM BUS subscriber ensure through appropriate design/installation Components: Safety category ■ Mixer PCB with mixer motor for Viessmann mixer DN 20 to 50 and Permissible ambient temperature R ½ to 1¼ – during operation 0 to +40 °C ■ Flow temperature sensor (contact temperature sensor) –...
5.8 m, fully wired IP rating IP 32D to EN 60529 Ensure through design/instal- lation Sensor type Viessmann NTC 10 kΩ at 25 °C Permissible ambient temperature – During operation 0 to +120 °C – During storage and transport –20 to +70 °C Vitotronic 300-K extension for heating circuits 2 and 3 with mixers Part no.
Rated frequency 50 Hz Ensure through design/instal- Power consumption 2.5 W lation Safety category Sensor type Viessmann NTC 10 kΩ at IP rating IP 32D to EN 60529; en- 25 °C sure through design/instal- Permissible ambient temperature lation – Operation 0 to +120 °C...
– Storage and transport −20 to +70 °C To implement the following functions, also order immersion tempera- For systems with Viessmann DHW cylinders, the cylinder temperature ture sensor, part no. 7438 702: sensor is installed in the threaded elbow (standard delivery or acces- ■...
■ Switching the heating circuit pump for a directly connected heating circuit Specification Rated voltage 230 V~ Rated frequency 50 Hz Rated current Power consumption Rated relay output breaking capacity 2(1) A, 250 V~ each, total max. 4 A~ Safety category VIESMANN VITODENS 200-W...
Functions when operating with Vitotrol app: ■ Remote control of up to 3 heating circuits in one heating system ■ Setting of operating programs, set values and time programs. ■ Scanning system information ■ Displaying messages on the Vitotrol app user interface VIESMANN VITODENS 200-W...
■ Connecting cable with Rast 5 system connectors for connection to the control unit KM BUS ■ Mobile aerial (3.0 m long), magnetic base and adhesive pad ■ Power cable with plug-in power supply unit (2.0 m long) VIESMANN VITODENS 200-W...
■ The Vitocom 200 is connected to the Vitotronic control unit via LON. ■ Remote control: The Vitocom 200 does not need to be configured for the LON. Adjusting operating programs, set values, time programs and heat- ing curves VIESMANN VITODENS 200-W...
As an internet data transfer establishes a permanent connection ("always online"), access to the heating system is particularly fast. For heating systems with one or more heat sources, with or without heating circuits downstream For system operation with Vitodata 100 or Vitodata 300 VIESMANN VITODENS 200-W...
Page 74
– Remote setup of Vitotronic control parameters via coding – 0 − 10 V– addresses – 4 − 20 mA – Viessmann temperature sensors NTC 10 kΩ, Note NTC 20 kΩ, Ni500 or Pt500 ■ Alongside the data transfer telecommunication costs, usage –...
(stand- ard ambient conditions) – Storage and transport −20 to +85 °C LON connecting cable for data exchange between control units Vitotronic 300-K for the Vitotronic 200-H Cable length 7 m, fully wired. Part no. 7143 495 VIESMANN VITODENS 200-W...
The design and operational characteristics of the Vitodens gas con- In some regions, permits may be required for the flue system and con- densing boilers from Viessmann meet the requirements of EN 297. densate drain into the public sewage system.
Page 77
Systems comprising combustion equipment and flues VDI 2035 Prevention of damage in water heating installations - scale formation in DHW supply installations and water heating installations VdTÜV 1466 Water quality datasheet VDE regulations and the special regulations of local power supply utilities. VIESMANN VITODENS 200-W...