21 TECHNICAL DATA

Inverter model
XTS 900-12
Nominal battery voltage
12Vdc
Input voltage range
9.5-17Vdc
Continuous power @ 25°C
650**/500VA
Power 30 min. @ 25°C
900**/700VA
Power 3 sec. @25°C
2.3kVA
Maximum load
Maximum asymmetric load
* Load detection (Stand-by)
Cos φ
Maximum efficiency.
93%
Consumption OFF/Stand-by/ON
1.1W/1.4W/7W
* Output voltage
* Output frequency
Harmonic distortion
Overload and short-circuit protection
Overheat protection
Battery charger
* Charge characteristics
* Maximum charging current
* Temperature compensation
Power factor correction (PFC)
General data
XTS 900-12
* Input voltage range
Input frequency
Input current max. (transfer relay) /
Output current max.
Transfer time (UPS)
Multifunction contacts
Module ARM-02 with 2 contacts as option
Weight
8.2 kg
Dimension h x w x l [mm]
110x210x310
Protection index
Conformity
Operating temperature range
Relative humidity in operation
Ventilation
Acoustic level
*
Adjustable value
* *
value with optional cooling fan module ECF-01
(1)
With -01 at the end of the reference (I.e. XTM3500-24-01), means 120V/60Hz. Available for all Xtender except XTH 8000-48
User manual
XTS 1200-24
XTS 1400-48 XTM 1500-12 XTM 2000-12 XTM 2400-24 XTM 2600-48 XTM 3500-24 XTM 4000-48 XTH 3000-12 XTH 5000-24
24Vdc
48Vdc
19-34Vdc
38-68Vdc
800**/650VA
900**/750VA
1500VA
1200**/1000
1400**/1200
1500VA
VA
VA
2.5kVA
2.8kVA
3.4kVA
93%
93%
1.2W/1.5W/8W 1.3W/1.6W/8W 1.2W/1.4W/8
W
35A
25A
12A
70A
XTS 1200-24
XTS 1400-48
XTM 1500-12 XTM 2000-12
16Aac/20Aac
9kg
9.3 kg
15 kg
110x210x310 110x210x310
IP54
100%
Optional cooling module ECF-01
V4.6.0
12Vdc
24Vdc
48Vdc
9.5-17Vdc
19-34Vdc
38 - 68Vdc
2000VA
2000VA
2400VA
2600VA
4.8kVA
6kVA
6.5kVA
Up to short-circuit
Up to Pcont.
2 to 25W
0.1-1
93%
94%
96%
1.2W/1.4W/10
1.4W/1.6W/9W 1.8W/2W/10W 1.4W/1.6W/12
W
Pure sine wave 230Vac (+/- 2%) / 120Vac (1)
50Hz / 60Hz(1) +/- 0.05% (crystal controlled)
<2%
Automatic disconnection with 3 restart attempts
Warning before shut-down – with automatic restart
6 steps : bulk - absorption - floating - equalization - reduced floating – periodic absorption
100A
55A
30A
WithBTS-01 or BSP 500/1200
EN 61000-3-2
XTM 2400-24
XTM 2600-48
150 to 265Vac / 50 to 140Vac(1)
45 to 65Hz
50Aac/56Aac
<15ms
Two independent switchover contacts ( potential free,16A-250 Vac / 3A-50Vdc)
18.5 kg
16.2 kg
133x322x466
IP20
Directive EMC 2004/108/CE : EN 61000-6-1, EN 61000-6-3, EN 55014, EN 55022, EN 61000-3-2, 62040-2
Low voltage directive : 2006/95/CE : EN 50178, EN 62040-1, EN 60950-1, EN 62109-1
-20 to 55°C
95% without condensation
Forced from 55°C
<40dB / <45dB (without / with ventilation)
24Vdc
48Vdc
12Vdc
24Vdc
19-34Vdc
38-68Vdc
9.5-17Vdc
19-34Vdc
3000VA
3500VA
2500VA
4500VA
3500VA
4000VA
3000VA
5000VA
9kVA
10.5kVA
7.5kVA
12kVA
94%
96%
93%
94%
1.8W/2.1W/14
1.2W/1.4W/14
1.4W/1.8W/18
W
W
W
90A
50A
160A
140A
XTM 3500-24
XTM 4000-48
XTH 3000-12
XTH 5000-24
21.2 kg
22.9 kg
34 kg
40 kg
133x322x466
230x300x500 230x300x500
54
XTH 6000-48
XTH 8000-48
48Vdc
38-68Vdc
5000VA
7000VA
6000VA
8000VA
15kVA
21kVA
96%
1.8W/2.2W/22W 1.8W/2.4W/30W
W
100A
120A
XTH 6000-48
XTH 8000-48
50Aac/80Aac
42 kg
46 kg
230x300x500

Hide quick links: