Dimensioning the renewable energy sources................19 Wiring diagrams ..........................19 Connecting the battery ........................19 4.5.1 Battery cable cross-section and DC protective devices ............20 4.5.2 Connecting the battery (Xtender side) ..................20 4.5.3 Fuse mounting on battery positive pole (XTM only) ..............21 4.5.4 Battery-side connection .......................21 4.5.5 Earthing of battery .........................22...
Page 4
Xtender POWERING UP THE INSTALLATION .......................25 Connecting the battery ........................25 Putting the Xtender(s) in operation using the main ON/OFF switch (1) if present ....25 Connecting the consumers at the output ..................25 Activating the input circuit breaker(s) (H) ..................25 DESCRIPTION OF THE MAIN FUNCTIONS ....................26 Inverter ..............................26...
Remote command module: RCM-10 Auxiliary relay module: ARM-02 For greater clarity, the device is referred to in this manual as Xtender, unit or device, when the description of its functioning applies indiscriminately to different Xtender models. These operating instructions serve as a guideline for the safe and efficient usage of the Xtender.
During the production and assembly of the Xtender, each unit undergoes several checks and tests. These are carried out with strict adherence to the established procedures. Each Xtender has a serial number allowing complete follow-up on the checks, according to the particular data for each device.
When the Xtender is running, it generates voltage that can be potentially lethal. Work on or close to the installation must only be carried out by thoroughly trained and qualified personnel.
This manual contains important safety information. Read the safety and working instructions carefully before using the Xtender. Adhere to all the warnings given on the device as well as in the manual, by following all the instructions with regard to operation and use.
ASSEMBLY AND INSTALLATION 3.1 H ANDLING AND MOVING The weight of the Xtender can be up to 50kg depending upon the model. Use an appropriate lifting method as well as help from a third party when installing the equipment. 3.2 S...
First fix the mounting bracket (26) supplied with the device using 2 Ø < 6-8 mm >screws**. Then hang the Xtender on the bracket. Fasten the unit permanently using 2 Ø <6-8 mm> screws** on to the two notches located at the underside of the case.
ONNECTIONS 3.6.1 General recommendations The Xtender falls within protection class I (has a PE connection terminal). It is vital that a protective earth is connected to the AC-In and/or AC-Out PE terminals. An additional protective earth is located at the bottom of the unit (See sect 3.6.4 – p. 11/13, tag (17)).
Studer Innotec SA Xtender 3.6.2 Connection compartment, XTH and XTM models The unit’s connection compartment must remain permanently closed when in operation. It is imperative to close the protection cap on the connection terminals after each intervention in the device.
Studer Innotec SA Xtender 3.6.3 Connection compartment, XTS model Any unused cable entry on the device must be sealed to prevent any intrusion. An intrusion of small animals in the unit may cause serious damage not covered by warranty. User manual...
The connection of any other Com. Bus the RCC-02/03 or other device (LAN etc.) may damage the Xtender units device. See chapter 4.5.9 – p. 23. Switch for terminating the On model XTH, the 2 termination switches communication bus.
Studer Innotec SA Xtender Pos. Denomination Description Comment Connection for supplementary This connection can also be used as protective earth. principal protective earth. See sect. 3.6.1– p. 11. Rotating knob to adjust the Only in XTS model. For other models, see...
Whatever system is selected, it is possible to realise systems composed of several units of the same type and the same power output. Up to three Xtender in parallel or three extenders forming a three- phase grid or three times two or three Xtender in parallel forming a three-phase / parallel grid, may be thus combined.
ARTHING SYSTEM The Xtender is a protection class I unit, which is intended for cabling in a grid type TT, TN-S or TNC-S. The earthing of the neutral conductor (E) is carried out at a sole installation point, upstream of the RCD circuit breaker (D) type A, 30 mA.
In a fixed installation where the neutral is connected to the earth at a single installation point upstream of the Xtender, it is permissible to carry out a connection of the neutrals in order to preserve an unchanged earthing system downstream, independent of the operating mode of the Xtender.
The inverter is dimensioned in such a way that the rated power output covers the power of all the consumers, which will be used at the same time. A dimensioning margin of 20 to 30% is recommended to guarantee that the Xtender will work well in an ambient temperature of more than 25 °C. 4.3.3 Dimensioning the generator The power output of the generator must be the same or more than the average daily power.
Studer Innotec SA Xtender Each Xtender is connected directly to the battery through its own protective device (fuse or circuit breaker. It should never be connected to the output of a DC voltage regulator like solar regulator, without having the battery as buffer.
When connecting the battery, a spark may occur when connecting the second pole. This spark is normal and due to the load of the internal filtering capacity of the Xtender even if the unit is halted by the main on off command (1).
AC terminals (13-14) and standards with regard to the rated current at protective earth (15). the Xtender output (see fig. 1a). Distribution must conform to the local standards and regulations, and generally, be realised via a distribution table.
4.5.7 Connecting the AC supply sources The Xtender is intended to be supplied by alternative voltage sources such as the public grid or a generator. Check that the rated voltage of the source corresponds to the rated voltage (34) of the Xtender specified on the nameplate (fig.
Studer Innotec SA Xtender In a system comprising a single Xtender, the connection of the RCC-02 or RCC-03 units may be conducted without stopping the Xtender (hot plug). The communication bus will be used to interconnect other Xtender inverters in the case of a multi- unit application or to connect other types of users who have the proprietary protocol of Studer Innotec.
Attention: only a complete tightening of all 4 mounting screws of the XTS enclosure guarantees the IP 54 protection index. The Power up of the Xtender must be carried out in the order given below. Any Power off must be carried out in the reverse order.
When the Xtender is operating the LED "ON" (43) is glowing. When the Xtender is in inverter mode, the LED "AC-Out" (46) is glowing. If it flashes, the inverter is in "load search" mode (see following sect. "Automatic load detection").
I.e. If the system have a 5kW source (22A) and a 5 kW Xtender, the available power at the output is 10kW! In this example, the wire gauge must be chosen for 45A.
This feature is also used when a variable power source is connected to the input of the Xtender. This is particularly the case of 230 Vac alternators type "Dynawatt" coupled to drive motors whose speed varies.
Page 29
Studer Innotec SA Xtender The charge cycle, programmed by default, as shown in the example ACin=OK described in the figure opposite, runs automatically. line (28) indicates {1138} development battery {1156} voltage. {1140} The lower line (29) indicates the {1159} battery current (input and output).
If the battery voltage exceeds the value set by the parameter {1121} the inverter stops and starts up again when the voltage is less than {1110}. If the Xtender is repeatedly encountering this situation 3 times during one minute, it will stop permanently and will only start up again via an operator’s manual control.
EAL TIME CLOCK The Xtender (see sect. 9.4 – p. 37) has a real time clock that allows programing the function of the auxiliary contacts according to a time schedule. This clock must be adjusted via the use of the RCC- 02/-03 remote control.
EMOTE ENTRY EMOTE CONTROL ON The Xtender has one remote entry that can be assigned to a function and programmed with the remote control RCC-02/-03 (see chapter 14.13.1 in the RCC-02/-03 user manual). By default, no function is defined for the remote entry.
ARM-02 (see chap. 9.5). In a multi-Xtender installation, the status of the remote entry of each Xtender is transmitted to all the other Xtenders. If a function is programmed on the remote entry of one of the Xtenders, it will be applied to all the Xtenders.
(10). It is vital to determine and select the phase for each Xtender. If the grid is not available at the input of the master unit (phase 1), all the units of the system will switch to inverter mode.
RCC-02/-03 EMOTE CONTROL An RCC-02/-03 remote control, display and programming unit can be connected to the Xtender via one of the two RJ45-8-type "Com. Bus" (3) connectors. Only Studer CAN compatible accessories and devices (mentioned in chapters 9 and 10) can be connected to the RJ45-8 connectors, excluding any other connections such as LAN, Ethernet, ISDN or other.
Up to three RCC-02/-03 remote controls can be connected in series on the communication bus of one Xtender or an Xtender multi-inverter system. In a system comprising a single Xtender, the connection of the RCC-02 or RCC-03 may be done without stopping the Xtender (warm). When...
IME AND COMMUNICATION MODULE This module, mounted inside the XTS, allows the XTS to be connected with the remote control RCC-02/03, as well as to Xtender compatible devices and accessories. The module also features a real time clock and connectors to connect the ARM-02, RCM-10 and BTS-01 modules.
Studer Innotec SA Xtender 10 OTHER XTENDER SYSTEM COMPATIBLE DEVICES The devices listed below are compatible with and can be part of an Xtender system interconnected by the communication bus. Their complete description is available on our website www.studer- innotec.com 10.1 B...
RCM-10. 11.2 D ISPLAY AND CONTROL PANEL XTH et XTM The Xtender has an ON/OFF button and light indicators at the front of the unit, allowing clear identification of the operating mode. (41) The ON/OFF button allows the start-up or complete stop of the system.
Page 40
The equipment will restart automatically when the conditions that led to the temporary stoppage have gone away. In the systems with multi-units in parallel, the indicator (43) blinks 2 times when the Xtender is temporarily stopped by the master unit of the concerned phase while this mode is authorized. {1547}.
If the input current is exceeded nevertheless, and this exceed not permitted by parameter{1436}, the Xtender goes back to inverter mode (transfer relay open) and the indicator (42) will keep flashing as long as the user current exceeds the limit value of the input current {1107}.
Fixed installation with plug connection to the single-phase source – AC part Special feature: The connection of the neutral upstream and downstream of the Xtender (C) is prohibited in this configuration (presence of a plug upstream). See also sect. 4.2 – p. 17.
Page 43
(B) must be the same for all inverters in parallel in the same phase. 3. Variant: The sum of the lengths of the cables (A1) + (B1) of Xtender 1 must be the same as the sum of the lengths of the cables (A1) + (B1) of Xtender 2, and for Xtender 3 4.
Xtender and does not interfere with it. A control device may be connected to the terminals (7) of the Xtender. See sect. 7.7 – p. 31. On XTM and XTS this input is available on a separate Remote entry (external) device RCM-10 (see sect.
Distribution to the users supplied by the grid or the generator when this is present or by the Xtender within the limit of its power output from energy stored in the Secured grid battery. This distribution is carried out in conformity with the local standards and regulations.
This connection is deactivated by default. In may be used in certain specific cases for automatically re-establishing the neutral system type TT (TNC, TNS, Automatic TNC-S) when the Xtender is in inverter mode. The activation is carried out via earth-neutral RCC-02/-03 remote control by configuration of the parameter {1485}. This...
Studer Innotec SA Xtender 20 TABLE OF FACTORY DEFAULT PARAMETER SETTINGS Access Param. Mod. Denomination / description Fact. value level N° value Basic 1107 Maximum current of AC source (Input limit) 32 Aac Expert 1108 Battery undervoltage level without load 11.6/23.2/46.3 Vdc...
Page 51
Expert 1516 Deactivate if battery in floating phase (AUX 1) Expert 1517 Deactivate if battery in floating phase (AUX 2) Expert 1518 Xtender ON (AUX 1) Expert 1519 Xtender ON (AUX 2) Expert 1520 No overtemperature (AUX 1) Expert 1521...
Page 52
1545 Remote entry active Open Expert 1546 Max frequency increase 4 Hz Expert 1547 Allow slaves standby in multi-Xtender system Expert 1548 AC voltage increase according to battery voltage Expert 1549 Inverter frequency increase according to battery voltage Inst. 1550...
Page 53
1624 Cos phi at P = 100% Inst. 1627 ARN4105 frequency control enabled Inst. 1628 Xtender watchdog enabled Inst. 1629 Xtender watchdog delay 60 sec The second value concerns the 120Vac ranges NC=Factory setting not changeable To modify the parameters, please refer to the operating instructions for the RCC-02/-03 remote control.
Acoustic level <40dB / <45dB (without / with ventilation) Adjustable value value with optional cooling fan module ECF-01 With -01 at the end of the reference (I.e. XTM3500-24-01), means 120V/60Hz. Available for all Xtender except XTH 8000-48 User manual V4.6.0...
Page 55
Studer Innotec SA Xtender User manual V4.6.0...
Page 56
Studer Innotec SA Rue des Casernes 57 1950 Sion – Switzerland : +41(0) 27 205 60 80 Fax : +41(0) 27 205 60 88 info@studer-innotec.com www.studer-innotec.com...