Specifications - Omron POWLI BU100XR2 Instruction Manual

Table of Contents

Advertisement

9. Changing the setting of the functions
References
A. Specifications
Operation
Operation method
method
Cooling method
Input
Rated voltage range
Frequency
Maximum current
Number of phases
Output
Rated capacity
Output waveform
Frequency/accuracy
Number of phases
Overload protection
Switching time
(at power failure)
Bypass switching time
Bypass switching is
possible
Range of input current
Battery
Type
Voltage
Capacity/quantity
Backup time
Charging method
Charging time
Environ-
Operating ambient
ment
temperature
Operating ambient humidity
Storage temperature
Storage humidity
Withstand voltage
Insulation resistance
Leak current
Thunder surge resistance
Standards
Safety standard
VCCI
Input harmonics
Others
Internal power
consumption
Noise
Outer dimension (mm)
Weight
Full-time inverter power supply method
Forced air cooling method
87 to 120VAC
72 to 120VAC
50/60Hz
10.2A
20A
Single phase 2 lines
1KVA/700W
2KVA/1.4KW
100AVC ± 3%
Sine wave
In synch with input frequency (Line mode)
50/60Hz ± 1Hz (Battery mode)
Single phase 2 lines
Warning through the beeper and display at the
time of rated capacity or greater
Switched to the bypass mode when 105% or
larger of rating continues for 3 minutes or over
Switched to the bypass mode when 125% or
larger of rating continues for 30 seconds or over
Switched immediately to the bypass mode when
150% or larger takes place
Non intermittent
4msec or less
80 to 115ACV
Sealed lead-acid battery
36V
72V
7.2Ah/12V X 3 packs
7.2Ah/12V X 6 packs
5 minutes (at rated load)
Constant voltage constant current charging
8 hours (20°C)
0 to 40°C
25 to 85%RH
-15 to 40°C
20 to 90%RH
1500VAC, 1 one minute
10M ohm or more
1mA or less
To ground 4KV/between lines 20KV
Complied with UL1778
Adherence to Class A
IEC1000-3-2
170W or less
330W or less
50dB or less
W440 X D445 X H88
W440 X D426 X H88
19 Kg
12 Kg
26 Kg
W440 X D445 X H88
50
References
At the time of over 75% loading
At the time of below 75% loading
Bu100XR2
BU200XR2
Bu100XR2
BU200XR2
Auto retransfer system
At startup, Under abnormal
conditions, excessive capacity,
Under abnormal conditions,
excessive capacity,
Bu100XR2
BU200XR2
Bu100XR2
BU200XR2
Initial value 20°C, Rated load
80% for 4 hours
500VDC
BU100XR2
BU200XR2
BU100XR2
BU200XR2 (main unit)
MB1002/MB200XR2 (Battery unit)
BU100XR2
BU200XR2 (main unit)
MB1002/MB200XR2 (Battery unit)