D. Mantel and Wall Projections
The combustible mantel may have a maximum depth of
12 in. (305 mm) positioned 12 in. (305mm) above the
fireplace opening. Combustible trim pieces that project no
more than 1 1/2 in. (38 mm) from the face of the fireplace
can be placed no closer than 6 in. (152 mm) from the top
of the opening. Combustible trim must not cover:
the metal surfaces of the fireplace
where the non-combustible board is placed over the
metal surfaces
the space between the metal face of the fireplace and
framing members
Combustible Wall
2 x 4 stud wall
Standoffs
Non-combustible
Decorative Facing
such as: Steel, iron,
brick, tile, concrete,
slate, tile, plasters
Seal joint with
non-combustible
sealant
Figure 7.10 Mantel Specifications
32
VCG Designer Series • DSR42 Installation Manual • 4012-134 • Rev A • 02/20/15
Grid lines at 1 in. scale
Combustible
Decorative Facing
12 in./305 mm
Mantel
12 in./305 mm
minimum
6 in./152 mm
1 1/ 2 in.
minimum
38 mm
maximum
Measured from top of fireplace opening
WARNING!
Vermont Castings Group is not responsible for
discoloration, cracking or other material failures of
finishing materials due to heat exposure or smoke.
• Choose finishing materials carefully.
7 ft (2134 mm)
minumum
base of fireplace
to ceiling