Flex Vent Installation - Vermont Castings VWDV70NTSCSB Installation And Operating Instructions Manual

Direct vent gas fireplace
Table of Contents

Advertisement

VWDV70 Series Gas Fireplace
1. Flexible UL1777 listed venting may be used in any
venting application where rigid direct vent components
can be used. All restrictions, clearances and allow-
ances that pertain to the rigid piping apply to the
fl exible venting. Flex kits may not be modifi ed. Flex
kits may be added to the end of a vent run made of rigid
vent sections using pipe manufacturer's approved fl ex
to pipe adapters. This may occur only if doing so does
not violate any of the venting length, height, routing,
horizontal to vertical ratio requirements or clearance
considerations detailed in this manual.
2. The fl ex adapter starter kit (DVFF8A/8) is used to attach
fl ex venting to the appliance starting collar. It includes
5" inner and 8" outer adapter rings. Figure 30
The inner and outer adapter rings are required to
start all fl ex runs.
Never install damaged or torn fl exible venting.
Over tightening clamps may rip, tear, or otherwise
damage fl exible venting.
The adapter kit does not include individual pipe sec-
tions which may be purchased separately. (UL1777
listed type venting only.)
3. Start the fl exible vent as follows:
A. Installing the inner fl ex adapter and pipe. Figure 30
1. Insert the long side of the 5" inner ring into
exhaust pipe, gently tap to seat into place, and
secure with screws.
2. Slide the small gear clamp over the inner fl exible
vent pipe, and push out of the way.
3. Pull and extend the inner fl exible vent.
4. Slide the inner vent onto the adapter collar, for a
minimum 1
" overlap.
3
4
5. Locate the clamp at approximately
fl ex end and tighten.
6. Secure the clamped inner section with three
self-tapping screws, drilled equidistant, just above
the clamp perimeter.
B. Installing the outer fl ex pipe. Figure 30
1. Firmly insert the 8" outer adapter ring into the
outer appliance starting collar and secure with
screws.
2. Slide the large gear clamp over the outer fl exible
vent pipe, and push out of the way.
3. Pull and extend the outer fl exible vent.
4. Slide the outer vent onto the appliance collar outer
adapter for a minimum 1
Flex vent pipe spacers: Refer to
manufacturer's specifi cations for correct
positioning of the spacer springs to
maintain proper distance between inside
and outside pipe.
22
" from the
3
4
"
3
overlap.
4

FLEX VENT INSTALLATION

1
" Flexible
3
4
Pipe and
Adapter
Outer
DVFF8A/8
Inner Adapter
Outer Adapter
Figure 30 -
Typical Appliance Connection
5. Locate the clamp at approximately 3/4" from the
fl ex end and tighten.
6. Secure the clamped outer section with three
self-tapping screws, drilled equidistant, just above
the clamp perimeter.
C. Routing UL1777 fl ex pipe.
1. Always maintain the required clearance when
routing the fl ex vent assembly.
2. Install fi restop spacers, Figure 32, when pene-
trating ceiling, attic spaces, or walls.
3. Do not allow the fl exible vent to bend in radius
tighter than 5°. Figure 31
UL1777
Flex Vent
Figure 31 -
Minimum Radius for Flex Vent Section
UL1777
Flex Vent
equidistant just
above gear
Appliance
Starting Collar
5° Radius
FP1973
20306745
Screws
(3 places,
clamp)