Startup Procedures - All Systems - Flushing the System

SETTING THE TIME OF DAY WHILE THE TANK IS FILLING SLOWLY

17.
While tank is slowly filling, Set the Time of Day by presssing either the Up or Down Button.
The Parameter Display will read "TD" for Time of Day and the Programming Icon will appear
Continue to press either Up or Down Button until the Data Display reads the current time of day.
If after 12:00 (noon) then the PM Indicator should be lit.
Once set, allow up to 10 seconds and the "TD" and
What you will see on the display:
Current Time of Day, a PM Indicator (if applicable)
You will also see the Time of Day alternate (about every 10 seconds) to another number and than back to
the time of day - this is normal and tells the user the next time the system will backwash counting down
each day from 6 (factory pre-set) until backwash.
In Service Icon
The diagram to the right is an
illustration of the system valve
controls and all the displays
for your reference.
Please follow the directions
above to set the time of day.
Please follow the directions
below to manually advance
the system through each step
of the backwash and flushing
procedure.
FLUSHING THE SYSTEM
18.
With the inlet side of the Bypass Valve still only PARTIALLY open and the tank still filling slowly - it is time to
manually backwash and flush the system.
CAUTION:
The outlet side of the Bypass Valve remains closed and in the bypass position until this flushing procedure has
been completed
19.
Manually start a backwash to flush the system.
Press and hold (5 seconds) the Extra Cycle Button until the Parameter Display flashes "BW" and the Data
Display reads "----".
You will hear the valve engage and it will take about 1 minute (60 seconds) until the backwash "BW"
cycle is reached.
Once the backwash "BW" cycle begins the Parameter Display will stop flashing and reads "BW" and
the Data Display is counting down from 9:59 in 1 second increments. This backwash is a 10 minute cycle.
will disappear.