No. Installer Setting
(
Notes follow table)
11
Short Cycle Protection
Outdoor Sensor Compressor COM BAL
12
Balance Point
13
Outdoor Sensor Auxiliary
Heat Balance Point
14
Equipment Staging
15
Equipment Staging Lock
16
Second Stage Fan Control
17
Second Stage Fan
18
Priority Zone
19
Opposite Mode Timer
20
Zone to Activate
Emergency Heat
21
Fire Alarm
Normal Active /
Normal Inactive
NOTES - Configuration
[1] Only available if MSH system type is selected.
[2] Only available if outdoor sensor is connected.
[3] Thermostat type must be heat pump.
[4] All equipment and fans will shut down and all dampers will power close
[5] Disable will not show plenum temperature and will prevent staging by temperature.
[6] Only available if supply air sensor is enabled.
[7] O/B selection on equipment must match thermostat O/B selection.
[8] Multi-stage thermostats must be used.
[9] Set thermostats to conventional.
Display
Factory
Indicator
Default
SCP
5
NO
AUX BAL NO
STAGING ZON
STAGLOK 2
G2 FAN ZON
G2 ZONES 2
PRIORTY 1
OP MODE
15
EM HEAT 1
FIRE ALM NI
Setting
Comments
Options
(More information follows this table)
5 to 0
Selects a compressor short cycle protection delay of 5,
4, 3, 2 or zero minutes after a compressor call
NO
Disables Compressor Balance Point Control
0 to 50
Selects a Compressor Balance Point of 0 to 50° F
[Note 1, 2]
NO,
Disables Auxiliary Heat Balance Point Control
40 to70
Selects an Auxiliary Heat Balance Point of 40 to 70° F
[Note 1, 2]
ZON
Select to stage on number of zones calling (Setting 15)
TIM
Select to stage on Zone Panel Timer
TST
Select to stage on Thermostat Staging Calls [Note 8]
2 - # of
Selects the number of zones that must call before the
zones
equipment will upstage Zone Count (setting 14 = ZON)
ZON
Select to Turn on Second Stage Fan on number of calling
zones (Setting 17)
STG
Select to Turn on Second Stage Fan when second stage
is activated
2 - # of
Select the number of zones that must call before the
zones
second stage fan will turn on
OFF
Select to have opposite calls answered in any zone
1 to 4
Select zone 1 to 4 to limit calls so equipment will only
service call matching last call of zone 1-4
15 to 60
Select the number of minutes to delay system changeover
when zones are calling for heat and others zones are
calling for cooling.
NO
Select to allow Emergency Heat from Thermostats
1 to 4
Select to match the Zone on the main panel allowed to
call emergency heat. [Note 3]
NI
Select for a normally inactive (Open) fire relay
NA
Select for a normally active (Closed) fire relay
[Note 4]