General precautions on indoor installation location

The EKCB unit is to be wall mounted in an indoor location that meets
the following requirements:
The space around the unit is adequate for servicing. Refer to
"7.3. Service space" on page 10.
The space around the unit allows for sufficient air circulation.
The installation surface is a flat and vertical non-combustible
wall, capable of supporting the operation weight of the unit (refer
to the "Technical specifications" on page 47).
During normal operation the control box may produce sound
which could be observed as noise. The sound origin can be
contactor activation. Therefore it is advisable to install the
control box on a firm wall and not in nor close to a sound
sensitive environment (e.g. bedroom).
Do not install the unit in places with high humidity (e.g.
bathroom).
The equipment is not intended for use in a potentially explosive
atmosphere.
Do not install the unit in places often used as work place.
In case of construction works (e.g. grinding works) where a lot of
dust is created, the unit must be covered.
Do not place any objects or equipment on top of the unit.
CAUTION
If the installation is equipped with a domestic hot water
tank (optional), please refer to the domestic hot water tank
installation manual.
7.
D
IMENSIONS AND SERVICE SPACE

7.1. Dimensions of outdoor unit

20
22
360
107
Unit of measurement: mm

7.2. Dimensions of indoor unit

2
4 1
1 0 0
Unit of measurement: mm
Installation manual
10
1189
84
1170

7.3. Service space

The space around the unit is adequate for servicing and the minimum
space for air inlet and air outlet is available. (Refer to the figure
below).
>50
Unit of measurement: mm
NOTICE
The wall height on the air outlet side (marked with grey
arrow in the figure above) must be less than 1200 mm.
The installation space required on this drawing is for full load heating
operation without considering possible ice accumulation.
If the location of the installation is in a cold climate, then all
dimensions above should be >500 mm to avoid accumulation of ice
in between the outdoor unit and the nearest walls.
The connection piping outlet direction in the installation shown in
the figure is frontward or downward.
When routing the piping backward, secure space of ≥250 mm on
the right side of the unit.
NOTICE
(*) If shut off valves are directly installed on the water inlet
and outlet, increase installation space at the rear of the
unit to a minimum of 300 mm.
7.4. Service space of indoor unit
5 0
5 0
Unit of measurement: mm
>150
EBHQ006+008BAV3 + EKCBX/H008BAV3
Unit for air to water heat pump system
4PW64602-1A – 09.2010