Daikin EBHQ006BAV3 Installation Manual page 40

Unit for air to water heat pump system
Hide thumbs Also See for EBHQ006BAV3:
Table of Contents

Advertisement

[D] Benefit kWh rate power supply/Local shift value weather
dependent
Benefit kWh rate power supply
[D-00] Switching off heaters: Defines which heaters are
switched off when the benefit kWh rate signal of the
electricity company is received.
If [D-01]=1 or 2 and the benefit kWh rate signal of the
electricity company is received, following devices will be
switched off:
[D-00]
Compressor
0
Forced off
(default)
1
Forced off
2
Forced off
3
Forced off
NOTICE
[D-00] settings 1, 2 and 3 are only meaningful if
the benefit kWh rate power supply is of the type
that power supply is not interrupted,
[D-01] Unit connection to benefit kWh rate power supply:
Defines whether or not the outdoor unit is connected to a
benefit kWh rate power supply.
If [D-01]=0, the unit is connected to a normal power supply
(default value).
If [D-01]=1 or 2, the unit is connected to a benefit kWh rate
power supply. In this case the wiring requires specific
installation like explained in "Connection to a benefit kWh
rate power supply" on page 24.
When parameter [D-01]=1 at the moment that the benefit
kWh rate signal is sent by the electricity company, that
contact will open and the unit will go in forced off mode
When parameter [D-01]=2 at the moment that the benefit
kWh rate signal is sent by the electricity company, that
contact will close and the unit will go in forced off mode
(1) When the signal is released again, the voltage free contact will close and
the unit will restart operation. It is therefore important to leave the auto
restart function enabled. Refer to "[3] Auto restart" on page 32.
(2) When the signal is released again, the voltage free contact will open and
the unit will restart operation. It is therefore important to leave the auto
restart function enabled. Refer to "[3] Auto restart" on page 32.
Installation manual
38
Back up heater
Booster heater
Forced off
Forced off
Forced off
Permitted
Permitted
Forced off
Permitted
Permitted
(1)
.
(2)
.
Local shift value weather dependent
The local shift value weather dependent field setting is only relevant
in case weather dependent set point (see field setting "[1] Weather
dependent set point (heating operation only)" on page 31) is
selected.
[D-03] Local shift value weather dependent: determines the
shift value of the weather dependent set point around
outdoor temperature of 0°C.
T
t
[1-02]
S
R
[1-03]
[1-00]
0°C
[1-01]
T
Target water temperature
t
T
Outdoor temperature
A
R
Range
S
Local shift value
[1-00], [1-01],
Applicable field setting of the weather dependent set
point [1]
[1-02], [1-03]
[D-03]
Outdoor temperature range (T
0
1
–2°C~2°C
2
3
–4°C~4°C
4
[E] Unit information readout
[E-00] Readout of the software version (example: 23)
[E-01] Readout of the EEPROM version (example: 23)
[E-02] Readout of the unit model identification (example: 11)
[E-03] Readout of the liquid refrigerant temperature
[E-04] Readout of the inlet water temperature
NOTICE
[E-03] and [E-04] readouts are not permanently
refreshed. Temperature readouts are updated after
looping through the field setting first codes again only.
T
A
)
Local shift value
A
2
4
2
4
EBHQ006+008BAV3 + EKCBX/H008BAV3
Unit for air to water heat pump system
4PW64602-1A – 09.2010