19. U
NIT SPECIFICATIONS
Technical specifications
Outdoor unit
Nominal capacity
(a)
• Cooling
• Heating
Dimensions H x W x D
(mm)
Weight
• Machine weight
(kg)
• Operation weight
(kg)
Connections
• water inlet/outlet
Field installed waterpiping
• Minimum pressure
(bar)
resistance
• Minimim temperature
(°C)
resistance
• Recommended diameter
(inch)
Refrigerant
• Type
• Charge
(kg)
Expansion vessel
• Volume
• Pre-pressure
(bar)
• Maximum working pressure
(bar)
(MWP)
Pump
• Type
• No. of speed
• Nominal ESP
(a)
• Cooling
(kPa)
• Heating
(kPa)
Sound level
(a)
• Sound power cooling
(dBA)
(a)
• Sound pressure cooling
(dBA)
• Sound power heating
(dBA)
• Sound pressure heating
(dBA)
Internal water volume
Pressure relief valve
(bar)
water circuit
Operation range - water side
• Heating
(°C)
(a)
• Cooling
(°C)
• Domestic hot water by heat
(°C)
pump
Operation range - air side
• Heating
(°C)
(a)
• Cooling
(°C)
• Domestic hot water by heat
(°C)
pump
(a) Only if connected to EKCBX008BAV3
(b) MBSP = Male British Standard Pipe
Indoor unit
Dimensions H x W x D
(mm)
Weight
(kg)
EBHQ006+008BAV3 + EKCBX/H008BAV3
Unit for air to water heat pump system
4PW64602-1A – 09.2010
EBHQ006BAV3
EBHQ008BAV3
Refer to the Technical Data
Refer to the Technical Data
805 x 1190 x 360
95
99
(b)
1" MBSP
4
65
1
R410A
1.7
6
(l)
1
3.0
water cooled
3
49.7
45.8
47.2
34.0
63
63
48
50
61
62
48
49
5.5
(l)
3
+15~+50
+5~+22
+25~+80
–15~+25
+10~+43
–15~+35
EKCBX008BAV3
EKCBH008BAV3
390 x 412 x 100
6
Electrical specifications
Outdoor unit
Power circuit
• Phase
• Frequency
(Hz)
(V)
• Voltage
(a)
Maximum running current
(b)
• Cooling
(A)
(A)
• Heating
(a) Equipment complying with EN/IEC 61000-3-12 (**)
(b) Only if connected to EKCBX008BAV3
Indoor unit
(a)
Power supply
• Phase
• Frequency
(Hz)
• Voltage
(V)
(A)
• Running current (heater kit)
• Z
(heater kit + booster
(Ohm)
max
heater (EKHWS* models))
• Running current (heater kit +
booster heater (EKHWS* models)
• EK*V3
(A)
• EK*Z2
(A)
(b)
• Minimum S
value
SC
• EK*V3
(kVA)
• EK*Z2
(kVA)
Operation range
• Ambient temperature
(°C)
(a) Above mentioned power supply is for the booster heater (EKW* option) and
backup heater kit (EKMBUH).
The switch box of the EKCB indoor unit is supplied via the outdoor unit.
The EKMBUH heater kit can be installed as a single step 3 kW heater or a 2 step
6 kW heater, for detailed information, refer to the heater kit installation manual.
(b) In accordance with EN/IEC 61000-3-11 (*), it may be necessary to consult the
distribution network operator to ensure that the equipment is connected only to a
supply with Z
(***) ≤Z
sys
max
(c) Equipment complying with EN/IEC 61000-3-12 (**)
(*) European/International Technical Standard setting the limits for voltage
changes, voltage fluctuations and flicker in public low-voltage supply
systems for equipment with rated current ≤75 A.
(**) European/International Technical Standard setting the limits for harmonic
currents by equipment connected to public low-voltage systems
with input current >16 A and ≤75 A per phase
(***) System independence
EBHQ006BAV3
EBHQ008BAV3
1~
50
230 (±10%)
16.25
18
EKCBX008BAV3
EKCBH008BAV3
1~
50
230 (±10%)
26
0.29
39 (26 + 13)
33.5
(c)
(c)
5~35