Phantom series high efficiency gas-fired hot water direct vent condensing boilers
Table of Contents

Advertisement

MAXIMUM
MODEL*
INPUT
(MBH)
PHNTM080
80
PHNTM100
100
PHNTM120
120
PHNTM150
150
PHNTM180
180
* The Net AHRI Water Ratings shown are based on a piping and pickup allowance of 1.15. The manufacturer should be consulted before
selecting a boiler for installations having unusual piping and pickup requirements, such as intermittent system operation, extensive piping
systems, etc.
MODEL
080
080
100
100
120
150
180
See Part VII (Venting) for additional requirements and details.
1) Safe, reliable operation of this boiler depends upon installation by a professional heating contractor in strict accordance
with this manual and the requirements of the authority having jurisdiction.
In the absence of an authority having jurisdiction, installation must be in accordance with this manual
and the National Fuel Gas Code, ANSI Z223.1. In Canada, installation must be in accordance with the B149.1
Installation Code.
Where required by the authority having jurisdiction, this installation must conform to the Standard for Controls
and Safety Devices for Automatically Fired Boilers (ANSI/ASME CSD-1).
2) Read Section VII to verify that the maximum combustion air and exhaust pipe lengths will not be exceeded in the
planned installation. Also verify that the vent terminal can be located in accordance with Section VII.
3) Make sure that the boiler is correctly sized:
For heating systems employing convection radiation (baseboard or radiators), use an industry accepted sizing
method such as the I=B=R Guide RHH published by the Air-Conditioning, Heating and Refrigeration Institute
(AHRI).
For new radiant heating systems, refer to the radiant tubing manufacturer's boiler sizing guidelines.
For systems which include an indirect water heater, make sure the boiler has the output called for by the indirect
water heater manufacturer's instructions.
Table 2.2: Specifi cations
D.O.E.
MINIMUM
HEATING
INPUT
CAPACITY
(MBH)
(MBH)
16
74
20
92
24
111
30
141
36
167
NOMINAL
VENT/INTAKE
SIZE (in)
2
3
2
3
3
3
3

III Before Installing

AHRI NET
WATER
RATING*
VOLUME
DIM "A"
(MBH)
(Gal.)
64
0.36
80
0.44
97
0.53
123
0.79
145
0.79
Table 2.3: Vent Lengths
MIN VENT
LENGTH (in)
12
12
12
12
12
52
52
5
SUPPLY &
RETURN
CONNECTION
CONNECTION
SIZE (NPT)
SIZE (NPT)
17"
1"
17"
1"
17"
1"
21"
1"
21"
1"
DERATE AT
MAX VENT
MAX VENT
LENGTH
60ft
135ft
60ft
135ft
135ft
135ft
135ft
APPROX.
GAS
NET
WEIGHT
(lb)
1/2"
100
1/2"
102
1/2"
105
1/2"
119
1/2"
119
APPROX.
(%)
9
2
15
3
7
7
9