TABLE 1a: GENERAL SPECIFICATIONS
KSZ SPACE HEATING RATINGS
BURNER
INPUT
BASIC BOILER
MODEL
(GAL/HR)
KSZ065
KSZ075
KSZ100
KSZ090
KSZ125
KSZ150
KSZ120
KSZ175
KSZ200
TABLE 1b: TANKLESS HEATER RATINGS
MODEL
KSZ065
KSZ075
KSZ100
KSZ090
KSZ125
KSZ150
KSZ120
KSZ175
KSZ200
1) Safe, reliable operation of this boiler depends upon installation by a professional heating contractor in strict accordance
with this manual and the requirements of the authority having jurisdiction.
In the absence of an authority having jurisdiction, installation must be in accordance with this manual and the latest
edition of Installation of Oil Burning Equipment (ANSI/NFPA31).
Where required by the authority having jurisdiction, this installation must conform to the latest edition of Standard for
Controls and Safety Devices for Automatically Fired Boilers (ANSI/ASME CSD-1).
2) Make sure that a properly sized chimney is available which is in good condition. Consult the authority having
jurisdiction, Part VI of this manual, and ANSI/NFPA31 for additional information on venting requirements.
3) Make sure that the boiler is correctly sized. Use an industry accepted sizing method such as the I=B=R Guide RHH
published by the Air-Conditioning, Heating and Refrigeration Institute (AHRI).
4) In some cases, boilers installed at altitudes above 2000ft may require a different burner configuration from that at sea level.
Consult the local Crown representative for more information.
HEATING
NET AHRI RATING,
CAPACITY
(MBH)
(Sq. ft)
0.65
79
0.75
90
1.00
119
0.90
110
1.25
149
1.50
177
1.20
147
1.75
207
2.00
235
RATING (gpm)
2.25
2.25
2.50
2.50
2.75
3.00
2.75
3.25
3.50
III Before Installing
AFUE %
STEAM
(MBH)
246
59
85.1
283
68
84.5
370
89
83.5
346
83
85.0
467
112
84.2
554
133
83.1
458
110
85.4
646
155
83.1
733
176
82.9
Notes:
1. Net Ratings are based on piping and pick-up allowances of 1.333.
2. Burner Capacity Rating, GPH is based on #2 oil with a Gross Heating
Value equal to 140000 BTU/Gal.
3. Maximum Working Pressure, Steam -15 PSI.
4. Tankless heater ratings based on 40F inlet water, 140F outlet water, and 190F
boiler water. Ratings are also based on 5 minute intermittent draws with 10 minutes
between draws.
6
DIMENSIONS (in.)
NUMBER
OF
"A"
"B"
SECTION
S
3
17-3/8
8 5/16
3
17-3/8
8 5/16
3
17-3/8
8 5/16
4
22-3/8
10 13/16
4
22-3/8 10 13/16
4
22-3/8
10 13/16
5
27-3/8 13 5/16
5
27-3/8
13 5/16
5
27-3/8
13 5/16
"C"
6
6
6
7
7
7
8
8
8