Refrigerant Piping - Toshiba RAV-SM562XT-E Installation Manual

Hide thumbs Also See for RAV-SM562XT-E:
Table of Contents

Advertisement

6

REFRIGERANT PIPING

Refrigerant Piping
1. If the outdoor units are to be mounted on a wall, make sure that the platform supporting is sufficiently strong. The
platform should be designed and manufactured to maintain its strength over a long period of time, and sufficient
consideration should be given to ensuring that the outdoor unit will not fall.
2. Use copper pipe with 0.8 mm or more thickness.
3. Flare nut and flare works are also different from those of the conventional refrigerant. Take out the flare nut
attached to the main unit of the air conditioner, and use it.
IMPORTANT 4 POINTS FOR PIPING WORK
1. Take away dust and moisture from the inside of the connecting pipes.
2. Tight connection (between pipes and unit)
3. Evacuate the air in the connecting pipes using VACUUM PUMP.
4. Check the gas leakage. (Connected points)
Permissible Piping Length and Head
The maximum piping length from the outdoor to indoor unit
30 m (Without charge 20 m)
(RAV-SM562AT-E)
Flaring
Insert a flare nut into the pipe, and flare the pipe.
As the flaring sizes of R410A differ from those of refrigerant R22, the flare tools
newly manufactured for R410A are recommended.
However, the conventional tools can be used by adjusting projection margin of the
copper pipe.
• Projection margin in flaring : B (Unit : mm)
Rigid (Clutch type)
R410A tool used
Outer diam.
of copper pipe
R410A
6.35/9.52
0 to 0.5
(Same as left)
12.7/15.9
0 to 0.5
(Same as left)
• Flaring dia meter size : A (Unit : mm)
Outer diam. of copper pipe
6.35
12.7/15.9
50 m (Without charge 20 m)
(RAV-SM802AT-E)
Conventional tools used
R22
R410A
R22
1.0 to 1.5
0.5 to 1.0
1.0 to 1.5
0.5 to 1.0
+ 0
A
– 0.4
R410A
R22
9.1
9.0
16.6
16.2
CAUTION
The maximum height difference outdoor/indoor unit
Outdoor unit is above
30 m
Imperial (Wing nut type)
Outer diam. of copper pipe
6.35/9.52
12.7/15.9
* In the case of the flaring for R410A with the
conventional flare tool, pull out it approx. 0.5 mm more
than that for R22 to adjust to the specified flare size.
The copper pipe gauge is useful for adjusting
projection margin size.
11
Outdoor unit is below
15 m
R410A
R22
1.5 to 2.0
1.0 to 1.5
2.0 to 2.5
1.5 to 2.0
A
B

Advertisement

Table of Contents
loading

This manual is also suitable for:

Rav-sm802xt-eRav-sm562at-eRav-sm802at-e

Table of Contents