Use ONLY R-410A rated service equipment or components with this unit. For specific handling concerns with R-410A, please contact your local Trane representative. Failure to use R-410A rated service equipment or components and/or failure to follow proper procedures or the use of non-approved refrigerants, refrigerant substitutes, or refrigerant additives could result in death or serious injury or equipment damage.
Page 3
Warnings, Cautions and Notices WARNING Personal Protective Equipment (PPE) Required! Installing/servicing this unit could result in exposure to electrical, mechanical and chemical hazards. • Before installing/servicing this unit, technicians MUST put on all Personal Protective Equipment (PPE) recommended for the work being undertaken. ALWAYS refer to appropriate MSDS and OSHA guidelines for proper PPE.
Page 4
USED WITH DESCRIPTION Coil Guard BAYGARD059A TTA120D Hail Guard HOT GAS BY-PASS BAYHGBP010A TTA120D Universal Hot Gas Bypass Kit Trane Communication Interface BAYICSI003A TTA120D Comm 3/4 Communications Interface Isolators BAYISLT005A TTA120D Rubber Isolator Kit BAYISLT023A TTA120D Steel Spring Isolator Kit...
Refrigerant Circuit Figure 1. COOLING ONLY CIRCUIT DIAGRAM COOLING ONLY CIRCUIT DIAGRAM DISCHARGE DISCHARGE TEMPERATURE TEMPERATURE LIMIT (DTL) LIMIT (DTL) HIGH PRESSURE HIGH PRESSURE GAUGE GAUGE SWITCH (HPCO) SWITCH (HPCO) CONNECTION CONNECTION NOTE A NOTE A NOTE A NOTE A FIELD SUPPLIED FIELD SUPPLIED INTER-CONNECTING...
Product Specifications Table 2. General Data — TTA120D 10 Tons Single Compressor TTA120D3, D4, DW, DK Cooling Performance Gross Cooling Capacity Matched Air Handler 124,000 Condensing Unit Only 112,000 ARI Net Cooling Capacity 120,000 Efficiency Matched Air Handler (EER) 11.2 Condensing Unit Only (EER) 12.2 System Integrated Part Load Value (IPLV)
Sequence of Operation NOTICE Equipment Damage! Ensure the disconnect for the indoor air handler is closed before operating the system. Operating the outdoor unit without the indoor fan energized can cause unit trip-out on high pressure control and/or liquid flood back to the compressor. Electromechanical Controls General Operation of the system cooling (and optional heating) cycles is controlled by the position of the...
Page 8
Sequence of Operation ReliaTel™ Control Cooling Mode For Zone Sensor Control When the system switch is set to the COOL position and the zone temperature rises above the cooling setpoint, the RTRM energizes the compressor contactor, provided the high and low pressure and the discharge temperature limit controls are closed.
Page 9
Cooling Pressure Curves Figure 2. TWE120D TTA120D with TWE120D (English) TTA120D with TWE120D (Metric) S uction P res s ure at 4 0 0 CFM/ Ton S uction P res s ure at 4 0 0 CFM/ Ton 1150 1100 1050 1000 68/57 DB/WB...
Troubleshooting SYSTEM FAULTS REFRIGERANT CIRCUIT Head Pressure Too High Head Pressure Too Low Suction Pressure Too High Suction Pressure Too Low Liquid Refrig. Floodback (TXV System) I.D. Coil Frosting Compressor Runs Inadequate or No Cooling ELECTRICAL Compressor & O.D. Fan Do Not Start Compr.