22. Technical data

CE1P2522E / 30.03.2000
68/68
conformity to
EMC directive
Immunity
Emissions
Low voltage directive
Safety
Nominal operating voltage
Frequency
Power consumption
Degree of protection (cover closed)
Safety class
Output relays
Test class
Rated voltage
Rated current
Contact current at AC 24...90 V
Contact current at AC 90...250 V
Nominal current ignition transformer
Switch-on current ignition transformer
Bus loading number E (LPB)
Backup of clock controller
Perm. cable lengths to the sensors and ex-
ternal contacts
Copper cable 0.6 mm dia.
Copper cable 1.0 mm
Copper cable 1.5 mm
Perm. cable lengths to the room unit
Copper cable 0.25 mm
Copper cable from 0.5 mm
Perm. cable lengths for data bus
2
0.75...2.5 mm
Perm. ambient temperature
Transport and storage
Operation
Weight (net)
For setting ranges, refer to the description of the individual function blocks and individ-
ual operating lines.
Basic Documentation RVL470
Technical data
89/336/EEC
EN 50082-2
EN 50081-1
73/23/EEC
EN 60730-1
AC 230 V
50 Hz
8 VA
IP 42 to EN 60529
II to EN 60730
II EN 60730
AC 230 V
2 (2) A
0.1...2 A, cos ϕ >0.6
0.02...2 A, cos ϕ >0.6
max. 1 A (during max. 30 s)
max. 10 A (during max. 10 ms)
6
min. 12 hours
max. 20 m
2
max. 80 m
2
max. 120 m
2
max. 25 m
2
max. 50 m
according to special bus specification
−25...+65 °C
0...50 °C
1.1 kg
Siemens Building Technologies
Landis & Staefa Division