On the software side, all settings can be locked to prevent tampering.
Also, the settings required for district heat applications can be locked on the hardware
side.
Line
Function, parameter
198
Locking of settings
On operating line 198, the settings made on the controller can be locked on the software
side. This means that the settings made can still be called up on the controller, but can-
not be changed.
Locking may comprise:
All settings
Only the settings required for the district heat parameters
The settings can be changed via the bus.
The procedure is the following:
1. Press buttons
and
2. Press buttons,
,
3. Now, operating line 198 appears in the display. The following locking choices are
available:
0 = no locking
1 = all settings are locked
2 = only the settings required for the district heat parameters are locked
(operating lines 101 to 117)
After locking all settings, the following setting elements remain operative:
The buttons for selecting the operating lines
The Info button
No longer operative will be:
The buttons for the readjustment of values
The bar for changing the basic setting of the heating curve
The setting knob for readjustment of the room temperature
The operating mode buttons
The manual mode button
The settings required for district heat applications (operating lines 101 to 117) can be
locked by bridging terminals H3–M. This kind of locking has priority over lockings on the
software side. If lockings are made on the hardware side, settings via the bus can no
longer be changed either.
To make the link across terminals H3–M inaccessible, the controller can be sealed to
prevent its removal.
Also refer to section "19. Handling".
Basic Documentation RVL470
Function block "Locking functions"
together until
appears in the display.
,
and
, one after the other.
Unit
Factory
Range
setting
0
0...2
Siemens Building Technologies
Landis & Staefa Division

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Rvl469

Table of Contents