Item
URL
Username
Password
(3) Enter Maintenance Mode.
See Appendix B.1.1, "Enabling maintenance Mode (APP0201010)".
(4) Confirm the mounting locations of the PSUs. See table 8.2.2-2.
(5) Remove FAN units at the mounting locations of PSUs.
See Appendix C.11, "FANU (APP0311000)".
Do not remove more than a FAN unit at the same time.
(6) Mount the PSU. See Appendix C.8 PSU (APP0308000).
(7) Install the power cable to the main unit. See Table 8.2.2-2.
Unit type
Cisco C880
(8) Turn on AC power of the added PSUs.
(9) Navigation Bar [System] → Click on Sub Menu [System Setup].
→ The window shown in "System Setup" appears.
(10) Change the appropriate radio buttons under [Power Feed Mode] and [PSU Redundant Mode].
See Appendix B.7, "Redundant Power Supply and Dual Power Feed Configuration
(APP0207000)".
(11) Change Maintenance Mode disabled. See Appendix B.1.2," Disabling maintenance mode
(APP0201020)".
Table 8.2.2-1
Setting values
http://<Maintenance IP Address>:<http port#> or
https://<Maintenance IP Address>:<https port#>
This depends on the system configuration.
http port#:Default(8081)
https port#:Default(432)
Account username
Account password
Table8.2.2-2
Power Supply configuration
200V
standard configuration
200V
redundant power supply configuration
200V
dual power feed configuration
41
Refer to
"Input Power Systems"
(APP0501010)
(APP0501020)
(APP0501030)
CA92344-0577-01